Plan Review Details - Permit 10040374
Plan Review Stops For Permit 10040374
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-04-14 Cont ID  
Sent By jgomez Date 2010-04-14 Time 15:28 Rev Time 0.00
Received By jgomez Date 2010-04-14 Time 15:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-14 Cont ID  
Sent By jgomez Date 2010-04-14 Time 14:43 Rev Time 0.00
Received By jgomez Date 2010-04-14 Time 14:34 Sent To  
Notes
2010-04-14 14:45:27RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- MISSING PRODUCT APPROVAL (2 COPIES) FOR SHINGLES TO
 BE INSTALLED AS REQUIRED BY DCA RULE 9B-72. NONE
 SUBMITTED.
  
 2- FLAT ROOF COMMENTS:
 A) NOA 07-1203.01 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE COUNTY. GO TO THE MIAMI-DADE WEBSITE AND
 DOWNLOAD CURRENT NOA.
  
 B) SPECIFY WHICH BASE SHEET FASTENING OPTION IS GOING
 TO BE USED FOR THE SELECTED INSULATED ASSEMBLY ON SHEET
 #22 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF
 SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 C) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED TO MEET THE DESIGN PRESSURES OF SEC. R301 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 ***NOTE: ACCORDING TO SEC. R301.2.1.4.3 OF 2009
 REVISIONS THIS BUILDING IS LOCATED ON EXPOSURE "C".
 DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS TO
 TAKE THIS INTO CONSIDERATION WHEN DOING THE RAS 117
 CALCULATIONS.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-14 Cont ID  
Sent By jgomez Date 2010-04-14 Time 14:43 Rev Time 0.00
Received By jgomez Date 2010-04-14 Time 14:35 Sent To  
Notes
***NONE***