2010-04-21 08:38:53 | BUILDING PLAN REVIEW |
| PERMIT:09120266 /REV 10040368 |
| ADD: 400 N FLAGLER |
| CONT: ROBB CONSTRUCTION |
| |
| TEL: (561)856-1643 |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS AND FEES. |
| |
| NOTE THE NEW TENANT SEPARATION SECTION OF WALL MAY |
| REQUIRE A REVISION FOR MECHANICAL IF DUCT PENETRATE |
| THIS PORTION OF THE TENANT SEPARATION WALL. |
| |
| 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL |
| HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR. |
| WALL SEPARATING INDIVIDUAL TENANT SPACES.708.1(7). |
| |
| 712.3.3 DUCTS AND AIR TRANSFER OPENINGS. PENETRATIONS |
| OF FIRE-RESISTANCE-RATED WALLS BY DUCTS THAT ARE NOT |
| PROTECTED WITH DAMPERS SHALL COMPLY WITH SECTIONS 712.2 |
| THROUGH 712.3.1. DUCTS AND AIR TRANSFER OPENINGS THAT |
| ARE PROTECTED WITH DAMPERS SHALL COMPLY WITH SECTION |
| 716. |
| |
| 716.3.1 FIRE PROTECTION RATING. FIRE DAMPERS SHALL HAVE |
| THE MINIMUM FIRE PROTECTION RATING SPECIFIED IN TABLE |
| 716.3.1 FOR THE TYPE OF PENETRATION. |
| |
| TABLE 716.3.1 FIRE DAMPER RATING |
| |
| TYPE OF PENETRATION MINIMUM DAMPER RATING |
| (HOURS) |
| LESS THAN 3-HOUR FIRE-RESISTANCE-RATED ASSEMBLIES 1.5 |
| |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |