Plan Review Details - Permit 10040281
Plan Review Stops For Permit 10040281
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2011-03-31 Cont ID  
Sent By jwitmer Date 2011-03-31 Time 08:01 Rev Time 0.50
Received By jwitmer Date 2011-03-31 Time 07:30 Sent To  
Notes
2011-03-31 08:01:43TRUSS ENGINEERING AND LAYOUT SHEET

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2011-02-10 Cont ID  
Sent By jwitmer Date 2011-02-10 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2011-02-10 Time 08:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2011-01-24 Cont ID  
Sent By jwitmer Date 2011-01-24 Time 08:31 Rev Time 0.77
Received By jwitmer Date 2011-01-24 Time 08:00 Sent To  
Notes
2011-01-24 08:36:09BUILDING PLAN REVIEW
 PERMIT: 10040281
 ADD:720 N TAMARIND AVE
 CONT: TO BE DETERMINED
 TEL: (561)644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 5TH REVIEW
 JAN. 24/ 2011
 ACTION: DENIED
  
 1) CONTRACTOR TO SIGN ON PERMIT AND LICESING VERIFIED.
  
 2-8A) COMPLIED.
  
  
  
 8B) BUILDING ENVELOPE (PRODUCT APPROVALS)
  
  
 BUILDING APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 1) WINDOWS
 2) ROOFING ASSEMBLIES
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2010-12-02 Cont ID  
Sent By jwitmer Date 2010-12-02 Time 15:52 Rev Time 0.99
Received By jwitmer Date 2010-12-02 Time 15:02 Sent To  
Notes
2010-12-02 15:55:46BUILDING PLAN REVIEW
 PERMIT: 10040281
 ADD:720 N TAMARIND AVE
 CONT: TO BE DETERMINED
 TEL: (561)644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW
 DEC. 02 /2010
 ACTION: DENIED
  
 1) CONTRACTOR TO SIGN ON PERMIT AND LICESING VERIFIED.
  
 2-8A) COMPLIED.
  
 8B) BUILDING ENVELOPE (PRODUCT APPROVALS)
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 WINDOWS
 ROOFING ASSEMBLIES
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-07-26 Cont ID  
Sent By jwitmer Date 2010-07-26 Time 11:29 Rev Time 2.22
Received By jwitmer Date 2010-07-26 Time 11:29 Sent To  
Notes
2010-07-26 12:57:32BUILDING PLAN REVIEW
 PERMIT: 10040281
 ADD:720 N TAMARIND AVE
 CONT: TO BE DETERMINED
 TEL: (561)644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 JULY 269/2010
 ACTION: DENIED
  
 1A) SHEET G-101, A-001 DEMOLITION & SITE PLAN A-002
 INDICATE THERE TO BE WORK ON MULTIPLE LOTS, A UNITITY
 OF TITLE WILL BE REQUIRED. UNITY OF TITLE. THE PROPOSED
 BUILDING STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM 'THE SITE'. A
 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF OF
 TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
  
 1B) SEMI-COMPLIED SHEET G-101 THE BUILDING DATA
 INDICATES A BUILDING TYPE III-B AND BUSINESS OCCUPANCY
 PLEASE SEE COMMENTS LISTED UNDER COMMENET # 2 & 3.
  
  
 2 ) THE PLANS THAT WERE SUBMITTED ARE CONCEPTUAL IN
 NATURE A THOROUGH REVIEW CAN NOT BE COMPLETED AT THIS
 TIME. FBC-B 106.3.5THE MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS ARE AS FOLLOWS:
 BUILDING
  
 1. SITE REQUIREMENTS:
  
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES OR DISTANCE
 FROM THE PROPERTY LINE TO EACH OF THE STRUCTURES)
  
 2. SECOND REQUEST OCCUPANCY GROUP AND SPECIAL OCCUPANCY
 REQUIREMENTS SHALL BE DETERMINED.
 SHEET G-101 CLEARLY STATES THESE BUILDINGS ARE TO BE
 BUSINESS OCCUPANCY. THE EXISTING BUILDING INDICATES A
 MULTI-PURPOSE ROOM AND THE PLANS STATE THE BUILDINGS
 ARE ATHLETIC LEAGUE ACTIVITY CENTERS. THE EXISTING &
 NEW ADDITION ARE TO BE CONSIDERED A-3 OCCUPANCY, A
 COMMUNITY CENTER . PLEASE REVIEW FBC-B 303.1
  
 3.SECOND REQUEST, MINIMUM TYPE OF CONSTRUCTION SHALL BE
 DETERMINED (SEE TABLE 503). HEIGHT AND AREA ARE TAKEN
 FOR A BUSINESS OCCUPANCY, PLEASE REVIEW FBC-B 303.1 AND
 TABLE 503 FOR ALLOWABLE HEIGHT AND AREA.
  
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE -RESISTANCE BASED ON SEPERATION
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PLANS INDICATE A REQUIRED 2 HR EXTERIOR BEARING WALL,
 PLEASE PROVIDE THE EQUIVALENT THICKNESS FOR THE 2 HR
 RATED BLOCK FROM THE MANUFACTURER.FBC-B 721.2.1.1 &
 TABLE 721.2.1.1.
  
 5. N/A
  
  
 6.SECOND REQUEST, LIFE SAFETY SYSTEMS SHALL BE
 DETERMINED :
 OCCUPANT LOAD AND EGRESS CAPACITIES
 CURRENTLY IT APPEARS THE WRONG OCCUPANCY TYPE HAS BEEN
 LISTED FOR THE NEW CONSTRUCTION AND FOR THE EXISTING
 TWO STORY .
  
  
 7. COMPLIED.
 8A) . STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS:1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 8B) BUILDING ENVELOPE (PRODUCT APPROVALS)
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 WINDOWS
 ROOFING ASSEMBLIES
  
 9-12). COMPLIED.
  
  
  
 13.)P COMPLIED. PLAY GROUND EQUIPMENT FUTURE- UNDER
 SEPERATE PERMIT
  
 14)COMPLIED.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-06-09 Cont ID  
Sent By jwitmer Date 2010-06-09 Time 08:57 Rev Time 2.22
Received By jwitmer Date 2010-06-09 Time 08:57 Sent To  
Notes
2010-06-09 10:41:25BUILDING PLAN REVIEW
 PERMIT: 10040281
 ADD:720 N TAMARIND AVE
 CONT: TO BE DETERMINED
 TEL: (561)644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 JUNE 09/2010
 ACTION: DENIED
  
 1A) SHEET G-101, A-001 DEMOLITION & SITE PLAN A-002
 INDICATE THERE TO BE WORK ON MULTIPLE LOTS, A UNITITY
 OF TITLE WILL BE REQUIRED. UNITY OF TITLE. THE PROPOSED
 BUILDING STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM 'THE SITE'. A
 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF OF
 TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. THIS WOULD
 ALLOW TWO STRUCTURES ON THE SAME LOT. PLEASE REVIEW
 FBC-B 503.1.2 TWO OR MORE BUILDINGS ON THE SAME LOT
 SHALL BE REGULATED AS SEPARATE BUILDINGS OR SHALL BE
 CONSIDERED AS PORTIONS OF ONE BUILDING IF THE HEIGHT OF
 EACH BUILDING AND THE AGGREGATE AREA OF BUILDINGS ARE
 WITHIN THE LIMITATIONS OF TABLE 503 AS MODIFIED BY
 SECTIONS 504 AND 506. THE PROVISIONS OF THIS CODE
 APPLICABLE TO THE AGGREGATE BUILDING SHALL BE
 APPLICABLE TO EACH BUILDING.
  
 THE OTHER WAY THIS COULD BE CONFIGURED AS TWO SEPERATE
 BUILDINGS ON TWO SEPERATE LOTS WITH AN ENCLOSED WALKWAY
 BETWEEN BUILINGS. SEE FBC-B DEFINITION:
  
 WALKWAY, ENCLOSED. A ROOFED, UNOBSTRUCTED WALKWAY
 CONNECTING BUILDINGS AND USED AS A MEANS OF TRAVEL BY
 PERSONS AND WHERE 50 PERCENT OR MORE OF THE PERIMETER
 IS ENCLOSED AND THE MAXIMUM WIDTH PERPENDICULAR TO THE
 DIRECTION OF TRAVEL IS LESS THAN 30 FEET (9144 MM).
  
 THIS CONFIGURATION THE ENCLOSED WALKWAY WOULD HAVE TO
 MEET ALL THE REQUIREMENTS OF FBC-B 3104. THE SECOND
 ISSUE IS THE PERCENTAGE OF ALLOWABLE OPENINGS TO THE
 PROPERTY LINE FBC-B TABLE 704.8.
 UNTIL THIS ISSUE IS RESOLVED A THOROUGH REVIEW CAN NOT
 BE ACCOMPLISHED!!!!!!
  
 1B) THE SECOND ISSUE IS BOTH STRUCTURES ARE BEING
 DECLARED AS TYPE II BUILDINGS. PLEASE REVIEW ALLOWABLE
 COMBUSTIBLE IN FBC-B 603.1 AND TABLE 601 FOOTNOTE "C
 &D". PLEASE ALSO REVIEW COMMUNITY AFFAIRS/ BOAF
 INTERPRETATION #5106 THAT STATES THE ROOF FRAMING
 MEMBERS (TRUSSES) AND DECKING WILL BE REQUIRED TO BE
 NON-COMBUSTIBLE AS WELL AS THE REQUIREMENTS IN FBC-B
 3104.3 CONSTRUCTION OF PEDESTRIAN WALKWAYS OR ENCLOSED
 WALKWAYS.
  
 2 ) THE PLANS THAT WERE SUBMITTED ARE CONCEPTUAL IN
 NATURE A THOROUGH REVIEW CAN NOT BE COMPLETED AT THIS
 TIME. FBC-B 106.3.5THE MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS ARE AS FOLLOWS:
 BUILDING
  
 1. SITE REQUIREMENTS:
  
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES OR DISTANCE
 FROM THE PROPERTY LINE TO EACH OF THE STRUCTURES)
  
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 SHEET G-101 CLEARLY STATES THESE BUILDINGS ARE TO BE
 BUSINESS OCCUPANCY. THE EXISTING BUILDING INDICATES A
 MULTI-PURPOSE ROOM AND THE PLANS STATE THE BUILDINGS
 ARE ATHLETIC LEAGUE ACTIVITY CENTERS. FOR THE EXISTING
 BUILDING IT COULD BE POSSIBLY BUSSINESS SECOND FLOOR
 SINCE THE PLANS DO NOT INDICATE ANY OF THE USAGE ON THE
 SECOND FLOOR SO IT COULD BE A MIXED USE BUILDING. BUT
 THTE NEW CONSTRUCTION IS CLEARLY A A-3 OCCUPANCY.
 PLEASE REVIEW 303.1, 508 MIXED USE & TABLE 503 FOR A-3
 HEIGHT AND AREA.
  
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503). SEE COMMENTS ABOVE.
  
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 UNTIL THE ISSUES WITH PROPERTY LINES, OR PROPOSED
 PROPERTY LINES, TWO BUILDINGS ON THE SAME LOT ( FBC-B
 503.1.2) THE FIRE ISSUES CAN NOT BE REVIEWED.
  
  
 5.FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS SCHEMATIC FIRE
 SPRINKLERS
 STANDPIPES
 PREENGINEERED SYSTEMS
 RISER DIAGRAM
  
  
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED :
 OCCUPANT LOAD AND EGRESS CAPACITIES
 CURRENTLY IT APPEARS THE WRONG OCCUPANCY TYPE HAS BEEN
 LISTED FOR THE NEW CONSTRUCTION AND FOR THE EXISTING
 TWO STORY ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE IF THIS IS A MIXED USE BUILDING WITH OR
 WITHOUT SEPERATION (508.2.2 / 508.3.2.)
  
  
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 CONSTRUCTION REQUIREMENTS
 ONCE THE ABOVE OCCUPANCY CLASSIFICATION ARE KNOWN THEN
 THE MEANS OF EGRESS CAN BE REVIEWED.
  
  
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS:1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 BUILDING ENVELOPE (PRODUCT APPROVALS)
 ROOF SYSTEMS CAN NOT BE REVIEWED UNTIL WE KNOW THE TYPE
 OF ROOFING COMPONENTS METAL OR WOOD TRUSSES,
 NOTE THE LOADS TO BE RESISTED ARE NOT PROVIDED, UPLIFT,
 LATERAL OR GRAVITY LOADS.
  
 9. MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM
 INCLUDE THE FOLLOWING:
 WOOD
 STEEL
 ALUMINUM
 CONCRETE
 PLASTIC
 GLASS
 MASONRY
 GYPSUM BOARD AND PLASTER
 INSULATING (MECHANICAL)
 ROOFING
 INSULATION
  
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES: THE NEW BUILDING THE
 PLANS ACTUALLY SHOW WALL MOUNTED HAND RAILS/ GRAB BARS
 BEING MOUNTED WITHIN THE WINDOW.
 DRINKING FOUNTAINS
 EQUIPMENT
  
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) NOT
 PROVIDED
 LIGHT AND VENTILATION
 SANITATION
  
 12. SPECIAL SYSTEMS (POSSIBLY IF WORK IS TO BE
 COMPLETED ON THE SECOND FLOOR OF EXISTING BUILDING):
 ELEVATORS
 ESCALATORS
 LIFTS
  
 13.PLAY GROUND EQUIPMENT
  
 THE DESIGN PROFESSIONAL WILL NEED TO DETERMINE IF THIS
 PROJECT WILL BE DESIGNED UNDER SECTION FBC-B 503.1.2
 TWO BUILDINGS ON THE SAME LOT OR IF TWO SEPERATE
 BUILDINGS WHERE FIRE RATINGS WILL BE A CONCERN AND A
 ASSUMED PROPERTY LINE WILL OCCUR!
  
 14) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-27 Cont ID  
Sent By jwitmer Date 2010-04-27 Time 13:20 Rev Time 1.00
Received By jwitmer Date 2010-04-27 Time 13:20 Sent To  
Notes
2010-04-27 13:43:05BUILDING PLAN REVIEW
 PERMIT: 10040281
 ADD:720 N TAMARIND AVE
 CONT: TO BE DETERMINED
 TEL: (561)644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-001 DEMOLITION & SITE PLAN A-002 INDICATE
 THERE TO BE WORK ON MULTIPLE LOTS, A UNITITY OF TITLE
 WILL BE REQUIRED. UNITY OF TITLE. THE PROPOSED BUILDING
 STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE
 LOTS WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF
 TITLE' SHALL BE RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF OF TITLE'
 DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
  
 2 ) THE PLANS THAT WERE SUBMITTED ARE CONCEPTUAL IN
 NATURE A THOROUGH REVIEW CAN NOT BE COMPLETED AT THIS
 TIME. FBC-B 106.3.5THE MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS ARE AS FOLLOWS:
 BUILDING
  
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
  
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
  
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 5.FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS SCHEMATIC FIRE
 SPRINKLERS
 STANDPIPES
 PREENGINEERED SYSTEMS
 RISER DIAGRAM
  
  
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED :
 OCCUPANT LOAD AND EGRESS CAPACITIES
  
  
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 CONSTRUCTION REQUIREMENTS
  
  
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS:1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE (PRODUCT APPROVALS)
 FOUNDATION
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
  
 9. MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM
 INCLUDE THE FOLLOWING:
 WOOD
 STEEL
 ALUMINUM
 CONCRETE
 PLASTIC
 GLASS
 MASONRY
 GYPSUM BOARD AND PLASTER
 INSULATING (MECHANICAL)
 ROOFING
 INSULATION
  
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
  
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
  
 12. SPECIAL SYSTEMS (POSSIBLY IF WORK IS TO BE
 COMPLETED ON THE SECOND FLOOR OF EXISTING BUILDING):
 ELEVATORS
 ESCALATORS
 LIFTS
  
 13.PLAY GROUND EQUIPMENT
  
 THE DESIGN PROFESSIONAL WILL NEED TO DETERMINE IF THIS
 PROJECT WILL BE DESIGNED UNDER SECTION FBC-B 503.1.2
 TWO BUILDINGS ON THE SAME LOT OR IF TWO SEPERATE
 BUILDINGS WHERE FIRE RATINGS WILL BE A CONCERN AND A
 ASSUMED PROPERTY LINE WILL OCCUR!
  
 14) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2011-01-14 Cont ID  
Sent By jleahy Date 2011-01-14 Time 08:57 Rev Time 0.00
Received By jleahy Date 2011-01-14 Time 08:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2011-01-07 Cont ID  
Sent By jleahy Date 2011-01-07 Time 07:31 Rev Time 0.00
Received By jleahy Date 2011-01-07 Time 07:31 Sent To  
Notes
2011-01-07 07:34:21SEE NOTES FROM PREVIOUS REVIEWS NOTHING HAS CHANGED

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2010-08-16 Cont ID  
Sent By jleahy Date 2010-08-16 Time 07:36 Rev Time 0.00
Received By jleahy Date 2010-08-16 Time 07:36 Sent To  
Notes
2010-08-16 08:37:551) RISER DIAGRAM SHOWS NO WIRE SIZES.
  
 2) NEED TO SHOW SERVICE GROUNDING FOR BOTH MAINS AND
 METER
  
 3) CIRCUIT NUMBER 6 SHOWS OUTLETS WITHIN 6' OF SINK
 THAT ARE NOT GFCI PROTECTED.
  
 4) NEED CUT SHEETS ON THE FIXTURES TO BE ABLE TO CHECK
 WATTAGES OF THE FIXTURES
  
 5) CIRCUITS 14,16 SHOWN AS SINGLE POLES.
  
 6) FOR THE RECEPTACLE LOAD YOU USED 1 VA PER SQ FT THAT
 IS ONLY USED WHEN THE ACTUAL NUMBER OF OUTLETS IS
 UNKNOWN.
  
 7) LIGHTING IS A CONTINUOUS LOAD AND SHALL BE RATED AT
 125%
  
 8) PLEASE CHECK YOUR NOTES ON PAGE E-001 PLAN NOTES FOR
 ALL THE MISSING EQUIPMENT NOT INCLUDED IN THE LOAD
 CALCULATION.
 27-2, 27-4, 27-5, 27-6, 27-8.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-06-16 Cont ID  
Sent By jleahy Date 2010-06-16 Time 09:32 Rev Time 0.00
Received By jleahy Date 2010-06-16 Time 09:32 Sent To  
Notes
2010-06-16 09:33:42NEED RISER DIAGRAM SHOWING METER& MAINS.
  
 LOAD CALCULATION FOR SERVICE
  
 ENERGY CALCULATION FOR LIGHTING DESIGN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-04-19 Cont ID  
Sent By jleahy Date 2010-04-19 Time 14:08 Rev Time 0.00
Received By jleahy Date 2010-04-19 Time 14:06 Sent To  
Notes
2010-04-19 14:09:45NO ELECTRIC SHOWN JL 4/19

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2010-12-14 Cont ID  
Sent By mgonzale Date 2010-12-14 Time 12:54 Rev Time 0.50
Received By mgonzale Date 2010-12-14 Time 12:53 Sent To  
Notes
2010-12-14 12:54:23PASSED
  
 PROJECT IS EXEMPT FROM EROSION CONTROL.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2010-08-12 Cont ID  
Sent By mgonzale Date 2010-08-12 Time 10:15 Rev Time 0.50
Received By mgonzale Date 2010-08-12 Time 10:15 Sent To  
Notes
2010-08-12 10:16:06FAILED: PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2010-05-18 Cont ID  
Sent By   Date 2010-05-18 Time   Rev Time 1.00
Received By mgonzale Date 2010-05-18 Time 13:53 Sent To  
Notes
2010-05-18 14:03:21FAIL STATUS COMMENTS
  
 AS PER ORDENANCE NO. 4060-07 ALL DEMOLITION AND NEW
 CONSTRUCTION PERMITS SHALL SUBMIT A STORMWATER
 POLLUTION PREVENTION PLAN (SWPPP)
 EROSION CONTROL AND LAND STABILIZATION BOND IS
 REQUIRED.
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 PLEASE CONTACT BRIAN MOREE AT ENGINEERING SERVICES
 DEPARTMENT FOR INFORMATION (561) 494-1098.
  
 A COPY OF THE ORDINANCE NO. 4060-07 MAY BE OBTAINED
 FROM THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR
 CITY HALL.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2010-12-30 Cont ID  
Sent By mcarsill Date 2010-12-30 Time 14:53 Rev Time 0.00
Received By mcarsill Date 2010-12-30 Time 14:47 Sent To  
Notes
2010-12-30 14:53:00POLICE ATHLETIC LEAGUE
 720 NORTH TAMARIND AVENUE
 PERMIT NUMBER 10040281
  
  
 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM INSTALLATION. A SMOKE DETECTOR IS REQUIRED ABOVE
 THE FIRE ALARM CONTROL PANEL IN THE STORAGE /
 MECHANICAL ROOM.
  
 2. A WARNING PLACARD WILL BE NEEDED TO IDENTIFY THE
 TRUSS ROOF ASSEMBLY. THE PLACARD SHALL BE A MALTESE
 CROSS THAT CONTAINS THE LETTER 'R" FOR ROOF.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2010-09-01 Cont ID  
Sent By mcarsill Date 2010-09-01 Time 14:49 Rev Time 0.00
Received By mcarsill Date 2010-09-01 Time 14:16 Sent To  
Notes
2010-09-01 14:49:25POLICE ATHLETIC LEAGUE
 720 NORTH TAMARIND AVENUE
 PERMIT NUMBER 10040281
  
  
 1. PLANS LIST A BUSINESS USE FOR THE BUILDING(S).
 PLEASE DECLARE THE CORRECT OCCUPANCY TYPE ON THE PLANS.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 ALARM SYSTEM INSTALLATION. A SMOKE DETECTOR IS REQUIRED
 ABOVE THE FIRE ALARM CONTROL PANEL IN
 STORAGE/MECHANICAL ROOM.
  
 3. A WARNING PLACARD WILL BE NEEDED TO IDENTIFY THE
 TRUSS ROOF ASSEMBLY. THE PLACARD SHALL BE A MALTESE
 CROSS THAT CONTAINS THE LETTER "R" FOR ROOF.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-06-14 Cont ID  
Sent By mcarsill Date 2010-06-14 Time 09:35 Rev Time 0.00
Received By mcarsill Date 2010-06-14 Time 09:23 Sent To  
Notes
2010-06-14 09:35:41720 NORTH TAMARING AVENUE
 PERMIT NUMBER 10040281
  
 1) THE MULTI-PURPOSE ROOM IS AN ASSEMBLY OCCUPANCY
 SINCE THE OCCUPANT LOAD EXCEEDS 50 PERSONS. ONE PAGE
 G-101 THE MULTI-PURPOSE ROOM IS APPROXIMATELY 803
 SQUARE FEET AND AN OCCUPANT LOAD OF 59 PERSONS IS
 DECLARED.
  
 2) TACTILE SIGNS ARE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3) PLEASE INDICATE THE PURPOSE OF THE STOVE/OVEN
 LOCATED IN BREAKROOM. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH NFPA 96, UNLESS IT IS
 OUTDOOR EQUIPMENT, PORTABLE EQUIPMENT NOT FLUE
 CONNECTED, OR IS USED FOR FOOD WARMING.
  
 4) NO EMERGENCY LIGHTS SHOWN ON PAGE E-001.
  
 5) PLEASE INDICATE THE TYPES OF DEADBOLTS PLANNED FOR
 USE. DOUBLE CYLINDER DEADBOLTS ARE NOT PERMITTED ON
 EXIT DOORS.
  
 6) PLEASE PROVIDE MORE DETAILS ON PORTABLE FIRE
 EXTINGUISHERS PLANNED FOR SITE.
  
 7) PLEASE INDICATE WHAT STORAGE MATERIALS WILL BE
 CONTAINED IN THE STORAGE/MECHANICAL ROOM 104. PLEASE
 SEE PROTECTION FROM HAZARDS SECTION OF THE FLORIDA FIRE
 PREVENTION CODE.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-05-24 Cont ID  
Sent By mcarsill Date 2010-05-24 Time 09:01 Rev Time 0.00
Received By mcarsill Date 2010-05-24 Time 08:54 Sent To  
Notes
2010-05-24 09:01:51WEST PALM BEACH POLICE ATHLETIC LEAGUE ACTIVITY CENTER
 720 NORTH TAMARIND AVENUE
 PERMIT NUMBER 10040281
  
 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 2. SITE PLAN DOES NOT ILLUSTRATE ANY FIRE HYDRANT
 LOCATIONS.
  
 3. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 4. PLEASE ILLUSTRATE DOOR HARDWARE ON DOOR SCHEDULE.
  
 5. SUBMIT COMPLETE ARCHITECTURAL, MECHANICAL,
 ELECTRICAL, AND PLUMBING PLANS FOR REVIEW.
  
 6. PLEASE INDICATE LOCATIONS OF ALL SAFETY EQUIPMENT.
  
 7. PLEASE ILLUSTRATE ALL EXIT SIGNS, EMERGENCY LIGHTS
 AND ANY OTHER SAFETY EQUIPMENT.
  
 8. PLEASE INDICATE OCCUPANT LOADS FOR THE NEW AND
 EXISTING BUILDING.
  
 9. PLEASE INDICATE OCCUPANCY CLASSIFICATIONS FOR EACH
 BUILDING.
  
 10. PLEASE DECLARE CONSTRUCTION TYPE FOR BOTH
 BUILDINGS.
  
 11. PLEASE INDICATE PURPOSE OF THE STOVE.
  
 12. PLEASE DISPLAY THE FIRE ALARM EQUIPMENT IN THE NEW
 AND OLD BUILDING.
  
 13. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4724 PHONE
 804-4774 FAX
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2011-02-09 Cont ID  
Sent By fmittner Date 2011-02-09 Time 14:56 Rev Time 0.00
Received By fmittner Date 2011-02-09 Time 14:56 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2010-04-12 Cont ID  
Sent By swurafti Date 2010-04-12 Time 16:43 Rev Time 0.00
Received By swurafti Date 2010-04-12 Time 16:43 Sent To  
Notes
2010-04-12 16:44:13HISTORIC DENIED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 7 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2011-06-29 Time 09:10 Sent To  
Notes
2011-06-29 09:11:05C9
 P & E REVISION
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2011-03-28 Time 15:06 Sent To  
Notes
2011-03-28 15:06:40SENT TO JIM'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2011-01-11 Cont ID  
Sent By lmartine Date 2011-01-11 Time 13:02 Rev Time 0.00
Received By lmartine Date 2011-01-11 Time 13:02 Sent To  
Notes
2011-01-11 13:02:48C--5

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-12-01 Cont ID  
Sent By lmartine Date 2010-12-01 Time 15:30 Rev Time 0.00
Received By lmartine Date 2010-12-01 Time 15:30 Sent To  
Notes
2010-12-01 15:30:38C--5

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-07-22 Cont ID  
Sent By jgomez Date 2010-07-22 Time 15:24 Rev Time 0.00
Received By jgomez Date 2010-07-22 Time 15:24 Sent To  
Notes
2010-07-22 15:27:05SENT TO C1.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-12-01 Cont ID  
Sent By vmolina Date 2010-05-26 Time 11:01 Rev Time 0.00
Received By lmartine Date 2010-05-26 Time 11:01 Sent To  
Notes
2010-05-26 11:01:23C-33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-25 Cont ID  
Sent By mawillia Date 2010-05-25 Time 10:47 Rev Time 0.00
Received By mawillia Date 2010-04-14 Time 08:50 Sent To  
Notes
2010-04-14 08:53:17C 39
  

Review Stop L LANDSCAPING
Rev No 5 Status N Date 2011-02-03 Cont ID  
Sent By rkussner Date 2011-02-03 Time 15:51 Rev Time 0.00
Received By rkussner Date 2011-02-03 Time 15:51 Sent To  
Notes
2011-02-03 15:52:39***LANDSCAPE NOT REQUIRED***
  
 PLEASE REFER TO PERMIT #11020102 FOR LANDSCAPE PERMIT
 AND PLANS---RAK

Review Stop L LANDSCAPING
Rev No 4 Status F Date 2011-01-18 Cont ID  
Sent By rkussner Date 2011-01-18 Time 11:56 Rev Time 0.00
Received By rkussner Date 2011-01-18 Time 11:56 Sent To  
Notes
2011-01-18 13:21:14*LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. REPEAT COMMENT: PLEASE APPLY FOR A LANDCAPE PERMIT.
 SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN SIGNED AND
 SEALED BY A REGISTERED LANDSCAPE ARCHITECT. PROVIDE A
 CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 2. REPEAT COMMENT: A SEPARATE IRRIGATION PERMIT IS
 REQUIRED. SUBMIT TWO COPIES OF AN IRRIGATION PLAN THAT
 PROVIDES 120% COVERAGE TO ALL LANDSCAPED AREAS,
 INCLUDING RIGHTS-OF-WAY.
  
 3. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 4. PLEASE PROVIDE THE SIZE OF ALL PROPOSED PLANT
 MATERIAL--NOT JUST THE CONTAINER SIZE.
  
 5.THE REQUIRED CURBS SHOULD NOT WRAP AROUND THE
 LANDSCAPE ISLANDS. THE CURB NEEDS TO BE INSTALLED ONLY
 WHEN A LANDSCAPE AREA ABUTS A PARKING STALL OR OTHER
 VEHICULAR USE AREA. CURBING SHALL BE INSTALLED ALONG
 THE LANDSCAPE STRIP ADJACENT TO TAMARIND AVENUE TO
 SEPARATE THE VEHICULAR USE AREA FROM THE LANDSCAPE
 STRIP.
  
 6. PURSUANT TO SECTION 94-443 (A) (D) AT LEAST ONE
 SHADE OR FLOWERING TREE SHALL BE PLANTED IN A REQUIRED
 BUFFER FOR EACH 30 LINEAR FEET OR PORTION THEREOF WHEN
 A NONRESIDENTIAL USE IS ADJACENT TO RESIDENTIAL
 PROPERTY. THIS APPLIES TO THE EAST PERIMETER OF THE
 SITE.
  
 7. PURSUANT TO SECTION 94-443 (C) (2), SHADE TREES
 SHALL BE PLANTED AT 30 FOOT INTERVALS IN A REQUIRED
 LANDSCAPE BUFFER THAT SEPARATES A VEHICULAR USE AREA
 FROM A THOROUGHFARE. THIS APPLIES TO THE SOUTH SIDE OF
 THE PARKING LOT.
  
 8. PURSUANT TO SECTION 94-443 (B) (4), AT LEAST ONE
 SHADE OR FLOWERING TREE SHALL BE PLANTED IN A REQUIRED
 BUFFER STRIP FOR EACH 30 LINEAR FEET OF PORTION
 THEREOF. THIS APPLIES TO THE NORTH PERIMETER OF THE
 SITE. ADDITIONAL TREES WILL NEED TO BE PLANTED ADJACENT
 TO THE EXISTING BUILDING.
  
 9. PURSUANT TO SECTION 94-443 (B) (1), THE BUFFER STRIP
 SHALL BE AT LEAST FIVE FEET IN WIDTH ALONG THE ENTIRE
 EDGE OF PROPERTY WHEN ADJACENT TO A PUBLIC
 THOROUGHFARE. THIS APPLIES TO THE WEST PERIMETER OF THE
 PARKING LOT. A TWO FOOT LANDSCAPE STRIP IS NOT WIDE
 ENOUGHT TO ACCOMMODATE A HEDGE AND THE ROOT BALLS OF
 THE PROPOSED TREES.
  
 10. A TREE ALTERATION PERMIT IS REQUIRED. PLEASE SUBMIT
 AN APPLICATION AND TWO SETS OF LANDSCAPE PLANS TO THE
 PLANNING AND ZONING DEPARTMENT.
  
 11, THE SITE PLAN SHALL BE FULLY DIMENSIONED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2010-12-10 Cont ID  
Sent By rkussner Date 2010-12-10 Time 14:45 Rev Time 0.00
Received By rkussner Date 2010-12-10 Time 14:45 Sent To  
Notes
2010-12-10 14:52:05***FAILED LANDSCAPE REVIEW***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. REPEAT COMMENT: PLEASE APPLY FOR A LANDCAPE PERMIT.
 SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN SIGNED AND
 SEALED BY A REGISTERED LANDSCAPE ARCHITECT. PROVIDE A
 CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 2. REPEAT COMMENT: PROVIDE THE TABULATION NECESSARY FOR
 THE EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 3. REPEAT COMMENT: A SEPARATE IRRIGATION PERMIT IS
 REQUIRED. SUBMIT TWO COPIES OF AN IRRIGATION PLAN THAT
 PROVIDES 120% COVERAGE TO ALL LANDSCAPED AREAS,
 INCLUDING RIGHTS-OF-WAY.
  
 4. PURSUANT TO SECTION 94-448 (D) (2), ALL OF THE ITEM
 ENUMERATED IN THIS SECTION SHALL BE ADDRESSED ON THE
 LANDSCAPE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-08-03 Cont ID  
Sent By rkussner Date 2010-08-03 Time 17:09 Rev Time 0.00
Received By rkussner Date 2010-08-03 Time 17:09 Sent To  
Notes
2010-08-03 17:19:53***FAILED LANDSCAPE REVIEW***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. REPEAT COMMENT: PLEASE APPLY FOR A LANDCAPE PERMIT.
 SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN SIGNED AND
 SEALED BY A REGISTERED LANDSCAPE ARCHITECT. PROVIDE A
 CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 2. REPEAT COMMENT: PROVIDE THE TABULATION NECESSARY FOR
 THE EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 3. REPEAT COMMENT: A SEPARATE IRRIGATION PERMIT IS
 REQUIRED. SUBMIT TWO COPIES OF AN IRRIGATION PLAN THAT
 PROVIDES 120% COVERAGE TO ALL LANDSCAPED AREAS,
 INCLUDING RIGHTS-OF-WAY.
  
 4. TERMINAL LANDSCAPE ISLANDS WITH SHADE TREES ARE
 REQUIRED. ALL LANDSCAPED AREAS SHALL BE SEPARATED FROM
 VEHICULAR USE AREAS BY THE USE OF CURBING KNOWN AS
 "TYPE D". ALL GROUND LEVEL AIR CONDITIONING UNITS AND
 OTHER MECHANICAL EQUIPMENT SHALL BE SCREENED. PLEASE
 REVISE PLANS ACCORDINGLY TO SHOW THESE ITEMS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-05-26 Cont ID  
Sent By rkussner Date 2010-05-26 Time 12:19 Rev Time 0.00
Received By rkussner Date 2010-05-26 Time 12:19 Sent To  
Notes
2010-05-26 12:32:26***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR A LANDCAPE PERMIT. SUBMIT TWO (2)
 COPIES OF A LANDSCAPE PLAN SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT. PROVIDE A CERTIFIED
 COST ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL
 LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO UNIT
 COST.
  
 2. PROVIDE THE TABULATION NECESSARY FOR THE EVALUATION
 OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, INCLUDING THE XERISCAPE DESIGN
 OPTIONS.
  
 3. A SEPARATE IRRIGATION PERMIT IS REQUIRED. SUBMIT TWO
 COPIES OF AN IRRIGATION PLAN THAT PROVIDES 120%
 COVERAGE TO ALL LANDSCAPED AREAS, INCLUDING
 RIGHTS-OF-WAY.
  
 4. THE STRIPING AND CAR STOP DETAILS ARE INCORRECT.
 PLEASE PROVIDE DETAILS THAT ARE APPROVED BY THE CITY. A
 COPY OF THESE DETAILS CAN BE OBTAINED AT THE FRONT DESK
 OF THE PLANNING AND ZONING DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2010-12-29 Cont ID  
Sent By hmoser Date 2010-12-29 Time 13:55 Rev Time 0.00
Received By hmoser Date 2010-12-28 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2010-07-29 Cont ID  
Sent By hmoser Date 2010-07-29 Time 09:28 Rev Time 0.00
Received By hmoser Date 2010-07-29 Time 09:28 Sent To  
Notes
2010-07-29 09:47:22PLAN DENIED
 1) COMMENT # 2 FROM LAST REVIEW WAS NOT ANSWER , PLEASE
 PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.
 2) PLEASE REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM
 AND 606.3 INSTALLATION 2007 FBC (M)
 3) PLEASE PROVIDE WHAT APPLIANCES ARE IN THE KITCHEN ON
 THE PLANS.
 4) PLEASE PROVIDE MODEL NUMBER OF THE EQUIPMENT ON THE
 EQUIPMENT SCHEDULE TO COMPLY WITH 14.4 SEER.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-06-21 Cont ID  
Sent By hmoser Date 2010-06-21 Time 14:44 Rev Time 0.00
Received By hmoser Date 2010-06-21 Time 13:28 Sent To  
Notes
2010-06-21 14:53:17PLAN DENIED
 1) PLEASE PROVIDE GRILL SIZES ON PLANS.
 2) PLEASE PROVIDE FRESH AIR CALCULATIONS ON THE PLANS .
 3) PLEASE PROVIDE A WALL KEY SHOWING WALL TIPES ON THE
 PLANS .
 4) PLEASE PROVIDE THE MODEL NUMBER OF THE EQUIPMENT
 SCHEDULE .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-04-20 Cont ID  
Sent By hmoser Date 2010-04-20 Time 09:30 Rev Time 0.00
Received By hmoser Date 2010-04-20 Time 09:30 Sent To  
Notes
2010-04-20 09:35:01THERE NO MECHANICAL PLANS IN PACKAGE. HAVE MECHANICAL
 CONTRACTOR SUBMIT PLANS , ENERGY CALCULATIONS AND HEAT
 LOADS WITH THE APPLICATION .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2010-12-17 Cont ID  
Sent By lwagner Date 2010-12-17 Time 16:03 Rev Time 0.00
Received By lwagner Date 2010-12-17 Time 09:01 Sent To  
Notes
2010-12-17 09:18:00*****PROVISO*****
 SINK TOPS TO BE 2'-10" FROM FINISHED FLOOR.
 FBC 2007 11-4.24.2

Review Stop P PLUMBING
Rev No 3 Status F Date 2010-08-02 Cont ID  
Sent By lwagner Date 2010-08-02 Time 14:28 Rev Time 0.00
Received By lwagner Date 2010-08-02 Time 13:07 Sent To  
Notes
2010-08-02 13:49:27PLUMBING REVIEW #3
 DENIED:
  
 FBC PLUMBING 2007 1003.3.1
  
 WITH THE INCLUSION OF THE RANGE THE BREAKROOM APPEARS
 TO BE A COMMERCIAL KITCHEN, PLEASE ADDRESS.
 A COMMERCIAL KITCHEN WILL REQUIRE:
  
 1. THREE COMPARTMENT SINK WITH INDIRECT WASTE 802.1.1
  
 2. GREASE TRAP OR INTERCEPTOR 1003.3.1:
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR OR
 AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH
 GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS,
 SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS,
 SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS.
 FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS,
 PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK
 STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE
 DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS
 WITHOUT PRERINSE SINKS. GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE
 ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS
 OR GREASE TO BE DISCHARGED.
  
  
 3. DISHWASHER REQUIRES AN INDIRECT WASTE ROUTED TO THE
 GREASE TRAP. EXCEPTION : DISHWASHER WITH PRE-RINSE
 SINK. 802.1.7
  
 4. THE FOOD WASTE DISPOSER WOULD BE REQUIRED TO BE
 ROUTED TO THE SANITARY, OR A SOLIDS INTERCEPTOR WOULD
 BE REQUIRED BEFORE CONNECTING TO THE GREASE
 INTERCEPTOR OR GREASE TRAP.
  
 NOTE - GREASE INTERCEPTORS SHALL BE SIZED PER TABLE
 1003.3.4.1
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-06-09 Cont ID  
Sent By lwagner Date 2010-06-09 Time 14:16 Rev Time 0.00
Received By lwagner Date 2010-06-08 Time 14:51 Sent To  
Notes
2010-06-09 14:02:04PLUMBING REVIEW #2
 DENIED
  
 FBC PLUMBING 2007 1003.3.1
 THE KITCHEN IN A COMMERCIAL BUILDING WILL REQUIRE:
 1. THREE COMPARTMENT SINK WITH INDIRECT WASTE 802.1.1
 2. GREASE TRAP OR INTERCEPTOR 1003.3.1
 3. DISHWASHER REQUIRES AN INDIRECT WASTE ROUTED TO THE
 GREASE TRAP. EXCEPTION : DISHWASHER WITH PRE-RINSE
 SINK. 802.1.7
 4. THE FOOD WASTE DISPOSER WOULD BE REQUIRED TO BE
 ROUTED TO THE SANITARY, OR A SOLIDS INTERCEPTOR WOULD
 BE REQUIRED BEFORE CONNECTING TO THE GREASE
 INTERCEPTOR.
  
 NOTE - GREASE INTERCEPTORS SHALL BE SIZED PER TABLE
 1003.3.4.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-04-26 Cont ID  
Sent By lwagner Date 2010-04-26 Time 09:12 Rev Time 0.00
Received By lwagner Date 2010-04-26 Time 09:06 Sent To  
Notes
2010-04-26 09:13:39NO PLUMBING DRAWINGS HAVE BEEN SUBMITTED.

Review Stop Z ZONING
Rev No 5 Status P Date 2011-01-18 Cont ID  
Sent By aaponte Date 2011-01-18 Time 11:28 Rev Time 0.00
Received By aaponte Date 2011-01-18 Time 11:18 Sent To  
Notes
2011-01-18 11:22:291. LANDACPAE AND IRRIGATION SHALL BE SUBMITTED UNDER A
 SEPARATE PERMIT.
 2. FENCE SHALL BE SUBMITTED UNDER SEPARATE PERMIT.
 3. DATA TABLE SHALL BE UPDATED FOR AS-BUILT SET.
 EXISTIGN BUILDING IS 3,100SF;EXISTING PARKING INCLUDES
 4 REGULAR SPACES AND 1 HANDICAP. 3 NEW PARKING SPACES
 REQUIRED FOR ADDITION. 1 PROVIDED ON SITE, 2 ON-STREET.
 4. PARKING SPACE WIDTH SHALL BE MEASURED FROM CENTER
 LINE.

Review Stop Z ZONING
Rev No 4 Status F Date 2010-12-15 Cont ID  
Sent By aaponte Date 2010-12-15 Time 13:31 Rev Time 0.00
Received By aaponte Date 2010-12-15 Time 13:31 Sent To  
Notes
2010-12-15 14:39:241. BASED ON THE 2004 APPROVAL OF THE 2 STORY PAL
 BUILDING, 6 SPACES WERE REQUIRED FOR THE USE. 3 NEW
 PARKING SPACES ARE REQUIRED FOR THE ADDITION. PLEASE
 INDICATE THE ON-STREET PARKING IN FRONT OF THE BUILDING
 TO CONFIRM COMPLIANCE WITH THE REQUIRED PARKING.
 2. PARKING DETAIL INCLUDED IN DRAWINGS DOES NOT MEET
 CITY STANDARDS. PLEASE LOOK AT THE STALL PAINTING
 DETAIL IN SECTION 94-485 AND WHEEL STOP DETAIL IN
 SECTION 94-443 OF THE ZONING CODE.
 3. PLEASE INDICATE HOW THE CALCULATION FOR TRANSPARENCY
 WAS DONE. IN ONE SHEET IS INDICATED AS 23% IN OTHER IS
 INDICATED AS 41%. THE DEFINITION OF TRANSPARENCY STATES
 THAT" TRANSPARENCY MAY BE PROVIDED THROUGH THE USE OF
 WINDOWS AND DOOR GLAZING AS WELL AS UNOBSTRUCTED
 OPENINGS IN THE BUILDING FACADE" (SEC 94-109).
 4.FENCE DEPICTED ON FRONT ELEVATION (SHEET A-201) IS 6
 FEET IN HEIGHT. FENCE WITHIN FRONT SETBACK SHALL NOT
 EXCEED 4FEET IN MAXIMUM HEIGHT.
 5. PLEASE PROVIDE A SRUVEY OF THE PROPERTY.

Review Stop Z ZONING
Rev No 3 Status F Date 2010-08-18 Cont ID  
Sent By aaponte Date 2010-08-18 Time 11:44 Rev Time 0.00
Received By aaponte Date 2010-08-18 Time 11:43 Sent To  
Notes
2010-08-18 12:12:011. A DEMOLITION PERMIT CANNOT BE APPROVED UNTIL A
 BUILDING PERMIT FOR THE NEW CONSTRUCTION HAS BEEN
 APPROVED.
 2. NEW CONSTRUCTION REQUIRES 3 PARKING SPACES. PLEASE
 PROVIDE INFORMATION ON ORIGINAL PAL BUILDING APPROVAL
 TO DETERMINE THE NUMBER OF PARKING SPACES INCLUDED ON
 THE APPROVAL AS REQUIRED PARKING.
 3. LANDSCPE DRAWINGS ARE REQUIRED. SEE LANDSCAPE
 COMMENTS.
 4. EXISTING PARKING AREA REQUIRES ENHANCEMENT OF
 LANDSCAPE AREAS.
 5. PARKING DETAIL SHALL COMPLY WITH CITY STANDARDS,
 INLCUDING WHEEL STOP.
 6. PLEASE PROVIDE A SUEVEY OF THE ENTIRE PROPERTY,
 INCLUDING UNDERGROUND AND ABOVE GROUND UTILITY
 LOCATIONS.
 7. A TREE ALTERATION PERMIT WILL BE REQUIRED FOR THE
 REMOVAL OF EXISTING TREES.
 8. UNITY OF TITLE WILL BE REQUIRED.
 9. PLEASE PROVIDE INFORMATION TO COMFIRM COMPLIANCE
 WITH 30% TRANSPARENCY REQUIREMENT ON THE NORTH
 ELEVATION.
 10. MECHANICAL EQUIPMENT SHALL BE SCREENED ACCORDING TO
 SECTION 94-444(B).
 11. BIKE RACKS SHALL BE LOCATED OVER A CONCRETE PATH.
 12. STREET LIGHTING SHALL BE PROVIDED TO ATTAIN THE
 APPROPRIATE FOOTCANDLE MEASUREMENT NECESSARY FOR SAFE
 PEDESTRIAN MOVEMENT. A MINIMUM 0.6 FOOTCANDLES AS
 MEASURED AT THE BACK OF THE CURB AND ONE FOOT ABOVE THE
 SIDEWALK IS REQUIRED.

Review Stop Z ZONING
Rev No 2 Status F Date 2010-06-15 Cont ID  
Sent By kdfreema Date 2010-06-15 Time 09:43 Rev Time 0.00
Received By kdfreema Date 2010-06-15 Time 09:43 Sent To  
Notes
2010-06-15 10:04:37***FAILED***
  
 1. SEE LANDSCAPE COMMENTS.
  
 2. IT IS MY UNDERSTANDING THAT THE PARKING LAYOUT WILL
 CHANGE BASED UPON A CONVERSATION WITH BRENDA KELLEY ON
 6/15/10. IT WILL BE REVIEWED FOR ZONING COMPLIANCE AT
 THAT TIME.
  
 3. PLEASE REVIEW THE FIRST ROUND OF ZONING COMMENTS
 MADE BY ANA MARIA APONTE. A NUMBER OF THOSE COMMENTS
 HAVE NOT BEEN ADDRESSED SATISFACTORALLY, OR NOT
 ADDRESSED AT ALL.
  
 PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT
 561-822-1458 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-05-11 Cont ID  
Sent By aaponte Date 2010-05-10 Time 16:14 Rev Time 0.00
Received By aaponte Date 2010-05-10 Time 16:14 Sent To  
Notes
2010-05-11 08:20:011. A DEMOLITION PERMIT CANNOT BE APPROVED UNTIL A
 BUILDING PERMIT FOR THE NEW CONSTRUCTION HAS BEEN
 ISSUED.
 2. COMMUNITY SERVICES REQUIRE 1 PARKIGN SPACE FOR EVERY
 500 SQUARE FEET. PLEASE PROVIDE A TOTAL BUILDING SQUARE
 FOOTAGE CALCULATION TO CONFIRM COMPLIANCE. THE PROPOSAL
 IS REMOVING THE EXISTING PARKING SPACES. A FULL PARKING
 CALCULATION MUST BE DONE.
 3. PLEASE INCLUDE DIMENSION TO INDICATE PROPOSED
 BUILDING SETBACK.
 4. UNITY OF TITTLE WILL BE REQUIRED FOR THE PROJECT.
 5. PARKING IS PROVIDED FROM AN ALLEY THAT IS NOT
 PLATTED. LEGAL INFORMATION SHALL BE PROVIDED TO VERIFY
 THE "ALLEY" COULD BE USED.
 6. PLEASE PROVIDE INFORMATION FOR DUMPSTER LOCATION.
 7. LANDSCAPE DRAWINGS WILL BE REQUIRED.
 8. A TREE REMOVAL PERMIT WILL BE REQUIRED.
 9. PARKING SHALL BE SCREENED WITH HEDGES AND TREES
 EVERY 30 FEET.
 10. PLEASE SUBMIT A SURVEY OF THE ENTIRE PROPERTY,
 INCLUDING UNDERGROUND AND ABOVE GROUND UTILITY
 LOCATIONS.