Plan Review Details - Permit 10040264
Plan Review Stops For Permit 10040264
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-06-08 Cont ID  
Sent By jwitmer Date 2010-06-08 Time 14:34 Rev Time 0.77
Received By jwitmer Date 2010-06-08 Time 14:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-20 Cont ID  
Sent By jwitmer Date 2010-04-20 Time 13:04 Rev Time 1.66
Received By jwitmer Date 2010-04-20 Time 13:04 Sent To  
Notes
2010-04-20 13:06:26BUILDING PLAN REVIEW
 PERMIT: 10040264
 ADD: 624 NOTTINGHAM BLVD
 CONT: ABACOA CONSTRUCTION LLC
 TEL: (561)722-3890
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DESIGN PROFESSIONAL: ARCHITECT MICHAEL HALL
 TEL: UNKNOWN
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1 MAIN ENTRANCE INDICATES A NEW ACCESSIBLE
 RAMP.
 1A) TOP LANDING IS TO SHORT, 11-4.8 .4(2) THE TOP
 LANDING TO BE A MINIMUM OF 5'-0" IN THE DIRECTION OF
 TRAVEL.
  
 1B) THE RAMP ITSELF IS INDICATED AS 6'-6" LONG
 REQUIRING HANDRAILS ON BOTH SIDES. 11.4.8.5. HANDRAILS:
 IF A RAMP HAS A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN
 IT SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 1C) THE PLANS DO NOT PROVIDE A DIMENSION FOR THE BOTTOM
 LANDING, 11-4.8.4 (2) REQUIRES THE BOTTOM LANDING TO BE
 A MINIMUM OF 72" OF STRAIGHT AND LEVEL CLEARENCE.
  
 2) SHEET A-1 ALL OF THE OTHER ENTRANCES OR EXITS
 INDICATE A DROP MAKING THESE UN-ACCESSIBLE, SIGNAGE IS
 REQUIRED. SEE 11-4.1.3(8)(D) ENTRANCES WHICH ARE NOT
 ACCESSIBLE SHALL HAVE DIRECTIONAL SIGNAGE COMPLYING
 WITH SECTIONS 11-4.30.1, 11-4.30.2, 11-4.30.3, AND
 11-4.30.5, WHICH INDICATES THE LOCATION OF THE NEAREST
 ACCESSIBLE ENTRANCE.
  
 3) SHEET A-1 MEN'S RESTROOM DOOR# 16 IS MISSING THE 18"
 LATCH SIDE OF THE DOOR. 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 4) SHEET A-2 THE ROOF PRESSURES ARE LOW FOR 140 MPH,
 15' MEAN ROOF HEIGHT AND B EXPOSURE, 10 FT AREA, FOR A
 FLAT ROOF , 10 SQ FT:
 ZONE ONE +14.3/ -35.3
 ZONE TWO +14.3/ -59.2
 ZONE THREE +14.3/-89.0
  
 5) PLANS INDICATE THE FLAT ROOF IS TO BE REPLACED WITH
 MODIFIED BITUMEN, NO PRODUCT APPROVALS WERE SUBMITTED,
 WHEN SUBMITTED PLEASE INDICATE TYPE OF ROOF INSULATION
 WITH SYSTEM.
 RULE 9B-72 (31) ( D)
  
 6) WINDOW AND DOOR PRODUCT APPROVALS ARE TO BE REVIEWED
 BY THE DESIGN PROFESSIONAL, 106.3.3 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7) ARCH FG-4500 STOREFRONT SYSTEM WAS SUBMITTED BUT
 THTE PLANS DO NOT INDICATE WHERE THIS UNIT IS TO BE
 INSTALLED. 106.1.2. ADDITIONAL INFORMATION REQUIRED.
  
 8) THE ELEVATIONS INDICATE WITHIN THE EXTERIOR WALL
 GLASS BLOCK WINDOWS AS WELL AS A-3 WINDOW SCHEDULE
 WINDOW TYPE "H". RULE 9B-72 (31)(B) WILL REQUIRE
 PRODUCT APPROVAL.
  
 9) THE MASONITE PRODUCT APPROVAL PLEASE HIGHLIGHT WHICH
 OF THESE PRODUCT ARE GOING TO BE INSTALLED SINCE EACH
 MODEL HAS DIFFERENT POSITIVE & NEGATIVE PRESSURES.
  
 10) SHEET M-1 NOTE #20 INDICATES THE NEW A/C CONDENSING
 UNITS ARE TO SIT ON THE EXISTING ROOF CURBS. PLEASE
 NOTE MECH. 301.12 WIND RESISTANCE MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT & THE SUPPORTS AS DETERMINED IN
 ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMPLISHED BY
 DESIGN OR BY APPLICATION OF SECTION 301.12.1.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-06-09 Cont ID  
Sent By btrobaug Date 2010-06-09 Time 11:32 Rev Time 0.00
Received By btrobaug Date 2010-06-09 Time 11:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-04-22 Cont ID  
Sent By btrobaug Date 2010-04-22 Time 16:31 Rev Time 0.00
Received By btrobaug Date 2010-04-22 Time 14:16 Sent To  
Notes
2010-04-22 15:19:08THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING.
  
 1} 13-415.1.AB.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING.
 A. A CONTROL DEVICE SHALL BE INSTALLED THAT
 AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH
 MULTISCENE CONTROL, IN THE FOLLOWING:
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS).
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
 LOCATE SAME ON THE PLANS.
  
 2} THE PLANS THAT WERE SUBMITTED HAVE SHEETS E-1 AND
 E-3, BUT NO SHEET E-2.
  
 3} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  
 4} THE RISER DIAGRAM ON SHEET E-3 SHOWS A 200 AMP
 EXISTING PANEL AND A 100 AMP EXISTING PANEL, THE PANEL
 SCHEDULES ARE LABELED 100 AMP MAIN BREAKER, CORRELATE
 SAME.
  
 5} SHEET M1 HAS 10 KW HEAT FOR BOTH THE AHU'S WITH 60
 AMP BREAKERS, THE PANEL SCHEDULE SHOWS 30 AMP BREAKERS
 WITH #8 CONDUCTORS WHICH IS NOT CORRECT FOR 10 KW AND
 THE LOAD CALCULATION WOULD BE INCORRECT.SEE 310.16 2008
 NEC.
  
 6} THE NOTES ON SHEET E-3 INCORRECTLY REFERENCE 310.15,
 212.12(B) AND 406.11 ALL OF WHICH ARE RESIDENTIAL
 ARTICLES.
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-08 Cont ID  
Sent By mawillia Date 2010-06-08 Time 15:49 Rev Time 0.00
Received By mawillia Date 2010-06-08 Time 15:14 Sent To  
Notes
2010-06-08 15:49:49*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-1, A-2, A-3, LS-1, AND E-1
 WERE STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-04-30 Cont ID  
Sent By mawillia Date 2010-04-30 Time 15:49 Rev Time 0.00
Received By mawillia Date 2010-04-30 Time 14:27 Sent To  
Notes
2010-04-30 15:49:10*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. PROVIDE COMPASS ARROW/INDICATOR FOR THE PROPOSED
 FLOOR PLAN (SHEET A-1) .
  
 3. ON SHEET A-2, INSERT DIRECTION (NORTH, SOUTH, EAST,
 WEST) TO CORRESPOND WITH THE APPROPRIATE EXTERIOR
 ELEVATION.
  
 4. DISPLAY/SHOW THE BUILDING ADDRESS OF THE STRUCTURE
 ON THE APPROPRIATE EXTERIOR ELEVATION WHICH FRONTS
 NOTTINGHAM BOULEVARD.
  
 5. ON SHEET A-3, NO FIRE-RATING LISTED IN THE DOOR
 SCHEDULE. BE ADVISED THAT SELF CLOSER ARE REQUIRED FOR
 FIRE RATED DOORS.
  
 6. COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE
 WITH NFPA 96 - 2004 EDITION INCLUDING EXISTING APPROVED
 INSTALLATIONS WHICH HAVE BEEN TESTED, INSPECTED,
 SERVICED, AND APPROVED BY A LICENSED CONTRACTOR.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-06-02 Cont ID  
Sent By vmolina Date 2010-06-02 Time 12:53 Rev Time 0.00
Received By vmolina Date 2010-06-02 Time 12:53 Sent To  
Notes
2010-06-02 12:57:31B-13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-11 Cont ID  
Sent By hmoser Date 2010-05-11 Time 13:29 Rev Time 0.00
Received By hmoser Date 2010-04-14 Time 16:24 Sent To  
Notes
2010-04-14 16:25:24B 24
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-06-17 Cont ID  
Sent By hmoser Date 2010-06-17 Time 08:17 Rev Time 0.00
Received By hmoser Date 2010-06-17 Time 08:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-05-11 Cont ID  
Sent By hmoser Date 2010-05-11 Time 13:08 Rev Time 0.00
Received By hmoser Date 2010-05-11 Time 13:23 Sent To  
Notes
2010-05-11 13:20:13PLAN DENIED
 PLEASE REFER TO SECTION 601.4 2007 FBC (M) BALANCED
 RETURN AIR, FOR ROOMS 108,109,110, AND 111.REFER TO
 NOTE # 3 ROOM 116 IS NOT A HABITABLE ROOM .
 PLEASE REFER TO SECTION 606. 2.1 SUPPLY SYSTEM, AND
 606.4.1 SUPERVISION .
 PLEASE REFER TO SECTION 301.12 WIND RESISTANCE .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-06-14 Cont ID  
Sent By lwagner Date 2010-06-14 Time 14:04 Rev Time 0.00
Received By lwagner Date 2010-06-10 Time 13:26 Sent To  
Notes
2010-06-10 13:57:59****PROVISO****
  
 607.1.1 HANDWASHING LAVATORIES.
 IN PUBLIC FOOD SERVICE ESTABLISHMENTS, FOOD
 ESTABLISHMENTS OR WHERE OTHERWISE REQUIRED BY LAW,
 LAVATORIES INTENDED FOR THE PURPOSE OF EMPLOYEE
 HANDWASHING SHALL BE EQUIPPED WITH HOT OR TEMPERED
 WATER.
  
 ****PROVISO****
  
 403.7.7 PRIVACY. DOORS TO UNISEX TOILET
 AND BATHING ROOMS SHALL BE SECURABLE
 FROM WITHIN THE ROOM.
  
 ****NOTE****
  
 PLUMBING PERMIT REQUIRED
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-04-22 Cont ID  
Sent By lwagner Date 2010-04-22 Time 13:51 Rev Time 0.00
Received By lwagner Date 2010-04-22 Time 12:50 Sent To  
Notes
2010-04-22 13:51:16REVIEW ACTION: DENIED
  
 1. FBC 2007 106.3.5 PLUMBING SANITARY AND WATER PIPE
 ISOMETRICS REQUIRED.
  
 2. FBC 2007 PLUMBING 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
 EXCEPTIONS:
 1. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR
 PRIVATE FACILITIES.
 2. SEPARATE EMPLOYEE FACILITIES SHALL NOT BE REQUIRED
 IN OCCUPANCIES IN WHICH 15 OR LESS PEOPLE ARE EMPLOYED.
 3. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR FOOD
 SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS.
 4. SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 BUSINESS AND MERCANTILE OCCUPANCIES WITH A TOTAL FLOOR
 AREA OF 3,000 SQUARE FEET (279 M2) OR LESS.
  
 3. THE WOMENS ROOM #104 HAS A UNISEX AREA INSIDE OF IT.
 FBC 2007 PLUMBING 403.7.2 UNISEX TOILET ROOMS.
 UNISEX TOILET ROOMS SHALL INCLUDE ONLY ONE WATER CLOSET
 AND ONLY ONE LAVATORY. A UNISEX BATHING ROOM IN
 ACCORDANCE WITH SECTION 403.7.3 SHALL BE CONSIDERED A
 UNISEX TOILET ROOM.
 EXCEPTION: A URINAL IS PERMITTED TO BE PROVIDED IN
 ADDITION TO THE WATER CLOSET IN A UNISEX TOILET ROOM.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2010-04-28 Cont ID  
Sent By lwagner Date 2010-04-28 Time 15:04 Rev Time 0.00
Received By lwagner Date 2010-04-21 Time 10:35 Sent To  
Notes
***NONE***