Plan Review Details - Permit 10040222
Plan Review Stops For Permit 10040222
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-06-11 Cont ID  
Sent By wjolin Date 2010-06-11 Time 10:44 Rev Time 0.00
Received By wjolin Date 2010-06-11 Time 10:06 Sent To  
Notes
2010-06-11 10:28:54*****APPROVED*****
  
 DRAWING FP-1, HYDRAULIC CALCULATION AND CUTSHEETS WERE
 STAMPED, DATED AND APPROVED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-05-07 Cont ID  
Sent By wjolin Date 2010-05-07 Time 09:03 Rev Time 0.00
Received By wjolin Date 2010-05-07 Time 08:45 Sent To  
Notes
2010-05-07 09:03:14*****UNSAT*****
  
 1) STANDARD SPRAY SPRINKLERS IN OPEN OFFICE AREA SPACED
 GREATER THAN 15'-0" APART.
  
 2) PROVIDE MINIMUM PUMP SUCTION PRESSURE OF 20 PSI
 (HYDRAULIC CALCULATIONS).
  
 3) HYDRAULIC CALCULATION BRANCH LINE LENGTH NOT PER
 NFPA.
 NODES 107 AND 102 ARE BEYOND THE 36' BRANCH LINE LENGTH
 AND SHOULD NOT BE CALCULATED.
 REVISE CALCULATED AREA EXCLUDING NODES 107 AND 102.
  
  
 WESLEY JOLIN
 FIRE PROTECTION ENGINEER
 561.805.6730
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561.805.6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2010-04-16 Time 17:55 Rev Time 0.00
Received By mawillia Date 2010-04-16 Time 17:25 Sent To  
Notes
2010-04-18 21:03:54*****UNSAT*****
  
  
 1. THE CALCULATED BRANCH LINE WIDTH OF 28 FEET IS NOT
 PER NFPA GUIDELINES. A REMOTE AREA OF 900 SQUARE FEET
 CORRESPONDS TO A BRANCH LINE CALCULATION OF 36 FEET.
  
 2. LEFT SIDE OF CROSS MAIN (3 TOTAL SPRINKLERS) APPEARS
 TO BE MORE DEMANDING THAN SUBMITTED CALCULATION OF TWO
 SPRINKLERS ON BRANCH LINES.
  
 3. VERIFY THAT PENETRATIONS OF THE NEW 2-HOUR RATED
 FIRE WALL ARE SEALED.
  
  
 WESLEY JOLIN
 FIRE PROTECTION ENGINEER
 561-805-6730
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-06-10 Cont ID  
Sent By vmolina Date 2010-06-10 Time 08:49 Rev Time 0.00
Received By vmolina Date 2010-06-10 Time 08:49 Sent To  
Notes
2010-06-10 08:49:24IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-04 Cont ID  
Sent By jgomez Date 2010-05-04 Time 11:16 Rev Time 0.00
Received By jgomez Date 2010-05-04 Time 11:15 Sent To FIRE
Notes
2010-05-04 11:16:37SENT TO FIRE BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-04-19 Time 11:07 Rev Time 0.00
Received By jgomez Date 2010-04-12 Time 16:00 Sent To  
Notes
2010-04-12 16:00:36SENT TO FIRE BOX.