Plan Review Details - Permit 10040209
Plan Review Stops For Permit 10040209
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-05-24 Cont ID  
Sent By jwitmer Date 2010-05-24 Time 10:04 Rev Time 0.77
Received By jwitmer Date 2010-05-24 Time 10:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-19 Cont ID  
Sent By jwitmer Date 2010-04-19 Time 10:45 Rev Time 3.50
Received By jwitmer Date 2010-04-19 Time 08:15 Sent To  
Notes
2010-04-19 14:19:42BUILDING PLAN REVIEW
 PERMIT: 10040209
 ADD: 222 LAKEVIEW AVE #120
 CONT: HOLT LEE CONSTRUCTION
 TEL: (954)270-1894
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A1.1 NOTE #1 INDICATES THE STORE FRONT WINDOWS
 WILL BE REPLACED AND BUILDING HAS HURRICANE SHUTTERS.
  
 1A) PLEASE PROVIDE PRODUCT APPROVALS FOR STOREFRONT
 WINDOWS , 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 1B) PLEASE INDICATE HOW THE EXISTING HURRICANE SHUTTERS
 MEET TODAY???S STANDARDS WHEN WERE THEY PERMITTED? AN
 ENGINEERS REPORT ANALYZING TYPE OF SHUTTER OR PANEL
 SYSTEM GAUGE OF METAL, FASTENER SPACING WITH A CURRENT
 FLORIDA APPROVAL OR MIAMI-DADE NOA WOULD BE ACCEPTABLE.
 104.11 ALTERNATE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT.
  
 2) SHEET A1.1 TENANT SEPARATION WALLS:
 2A) DOOR #1 THE MAIN ENTRY DOOR NOTE ON A3.2 INDICATES
 RATED DOUBLE ENTRY DOORS TO MATCH EXISTING STORE FRONT
 SYSTEM. IS THE EXISTING STOREFRONT DOORS AND SIDE
 LIGHTS TO REMAIN? 106. 1.2 ADDITIONAL INFORMATION
 REQUIRED, THESE DOORS ARE LOCATED WITHIN A 1 HR TENANT
 SEPARATION WALL.
  
 2B) SHEET A1.1 WINDOW #102 WILL ALSO NEED TO PROVIDE
 FIRE RATING SINCE IT IS LOCATED WITHIN A 1 HOUR TENANT
 SEPARATION WALL. SEE TABLE 715.4.
  
 2C) THERE IS A ONE HOUR WALL BETWEEN STORAGE ROOM #1
 AND THE GYM, ARE THE TWO STORAGE ROOMS UNDER SEPARATE
 TENANCY REQUIRING A ONE HOUR TENANT SEPARATION.
 708.1(7).
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-04-26 Cont ID  
Sent By btrobaug Date 2010-04-26 Time 12:23 Rev Time 0.00
Received By btrobaug Date 2010-04-26 Time 11:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-05-24 Cont ID  
Sent By mawillia Date 2010-05-24 Time 10:53 Rev Time 0.00
Received By mawillia Date 2010-05-24 Time 10:33 Sent To  
Notes
2010-05-24 10:52:57*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS D1.1, A2.1, A3.2, E2, AND M1
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-04-23 Cont ID  
Sent By mcarsill Date 2010-04-23 Time 09:27 Rev Time 0.00
Received By mcarsill Date 2010-04-23 Time 09:21 Sent To  
Notes
2010-04-23 09:26:48 
 222 LAKEVIEW AVENUE, SUITE 120
 PERMIT NUMBER 10040209
  
 1. NO FIRE SPRINKLER DETAILS PROVIDED. NO INFORMATION
 ON EXISTING OR NEW FIRE SPRINKLER HEADS. SEPARATE PLANS
 AND PERMITS REQUIRED FOR ANY FIRE SPRINKLER SYSTEM
 REMODELING.
  
 2. NO FIRE ALARM DETAILS PROVIDED. NO INFORMATION ON
 EXISTING OR NEW FIRE ALARM EQUIPMENT. SEPARATE PLANS
 AND PERMITS REQUIRED FOR ANY FIRE ALARM SYSTEM
 REMODELING.
  
 3. NEW FIRE RATED WALLS ARE TO BE PROPERLY IDENTIFIED
 AND ALL OPENINGS PROTECTED. NEW WALLS ARE TO BE
 LABELED.
  
 4. NO EMERGENCY LIGTHING CONTAINED IN LARGE RESTROOMS.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 6. ALL NEW FIRE DAMPERS SHALL BE DROP TESTED TO ENSURE
 PROPER OPERATION.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-09-27 Cont ID  
Sent By hmoser Date 2010-09-27 Time 10:50 Rev Time 0.00
Received By hmoser Date 2010-08-11 Time 14:22 Sent To  
Notes
2010-08-11 14:22:59REVISION# 10080319 SENT TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-17 Cont ID  
Sent By lmartine Date 2010-05-17 Time 09:44 Rev Time 0.00
Received By shill Date 2010-05-17 Time 09:44 Sent To  
Notes
2010-05-20 11:11:39****EXPEDITED AS OF 5/20/10****
2010-05-17 11:16:17C--20
2010-05-17 09:44:55IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-30 Cont ID  
Sent By lmartine Date 2010-04-28 Time 14:02 Rev Time 0.00
Received By lmartine Date 2010-04-12 Time 09:25 Sent To  
Notes
2010-04-12 09:25:30SENT TO C5.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-09-27 Cont ID  
Sent By hmoser Date 2010-09-27 Time 10:50 Rev Time 0.00
Received By hmoser Date 2010-09-27 Time 10:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-04-20 Cont ID  
Sent By rregueir Date 2010-04-20 Time 15:43 Rev Time 0.00
Received By rregueir Date 2010-04-20 Time 15:43 Sent To  
Notes
2010-04-20 15:44:00**PROVISO**
  
 PROVIDE LOUVER PRODUCT APPROVAL TO FIELD INSPECTOR PER
 FBC 106 AND FAC RULE 9B-72.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-04-20 Cont ID  
Sent By lwagner Date 2010-04-20 Time 09:19 Rev Time 0.00
Received By lwagner Date 2010-04-12 Time 12:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2010-06-03 Cont ID  
Sent By ajones Date 2010-06-03 Time 09:15 Rev Time 0.00
Received By ajones Date 2010-06-03 Time 09:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-04-28 Cont ID  
Sent By aaponte Date 2010-04-28 Time 13:05 Rev Time 0.00
Received By aaponte Date 2010-04-28 Time 13:05 Sent To  
Notes
2010-04-28 13:08:20PLEASE PROVIDE SQUARE FOOTAGE INFORMATION TO CONFIRM
 COMPLIANCE WITH ORDINANCE 2980-96 FOR THE PLANNED
 DEVELOPMENT WHICH ESTABLISHES THAT A MINIMUM OF 30% OF
 THE TOTAL GROSS LEASABLE SQUARE FOOTAGE OF THE GROUND
 FLOOR SHALL BE OCCUPIED BY PRIMARY RETAIL USES.
 FOR ADDITIONAL INFORMATION CONTACT ANA MARIA APONTE AT
 561-822-1439