Plan Review Details - Permit 10040177
Plan Review Stops For Permit 10040177
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-12 Cont ID  
Sent By rmcdouga Date 2010-04-12 Time 08:00 Rev Time 0.00
Received By rmcdouga Date 2010-04-12 Time 08:00 Sent To  
Notes
2010-04-12 08:01:42THE PULL TAS 105-98 TEST RESULTS AND PLANS SHOWING
 RE-LOCATED ROOF HATCH WERE SUBMITTED, AS REQUESTED.
  
 1) THE REVISED LOCATION OF THE ROOF HATCH TO ROOF ZONE
 1 IS CODE COMPLIANT.
  
 2) THE FASTENER WITHDRAWL RESISTANCE TEST REPORT IS
 INCOMPLETE AND HAS BEEN DENIED.
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR THE TAS
 105-98 REPORT.
  
 - THE CERTIFICATION OF THE DYNAMETER CALABRATION WITHIN
 3 MONTHS OF THE FIELD TEST DATE WAS NOT SUBMITTED. TAS
 105-98 (10.1.1)
  
 - THE DECK SUBSTRATE TESTED WAS NOT SPECIFIED. TAS
 105-98 (10.1.3)
  
 - THE FASTENER TYPE AND MANUFACTURER IS NOT SPECIFIC
 AND THE ROOFING COMPONENT TO BE SECURED IS NOT
 SPECIFIED. TAS 105-98 (10.1.4)
  
 - THE SPEED OF THE INSTALLATION TOOL AND LITERATURE ON
 THE FASTENING DEVICE WAS NOT PROVIDED. TAS 105-98
 (10.1.7)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-12 Cont ID  
Sent By rmcdouga Date 2010-04-12 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2010-04-08 Time 12:11 Sent To  
Notes
2010-04-09 12:12:11******************EXPEDITED******************
 GAVE TO ROBBIE