Plan Review Details - Permit 10030823
Plan Review Stops For Permit 10030823
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-04-07 Cont ID  
Sent By mawillia Date 2010-04-07 Time 14:10 Rev Time 0.00
Received By mawillia Date 2010-04-07 Time 13:35 Sent To  
Notes
2010-04-07 13:39:57*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED. PLAN SHEET FP1 OF 1 STAMPED, INITIALED, AND
 DATED; READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-04-01 Cont ID  
Sent By mcarsill Date 2010-04-01 Time 14:05 Rev Time 0.00
Received By mcarsill Date 2010-04-01 Time 11:41 Sent To  
Notes
2010-04-01 14:05:14 
  
 701 SOUTH OLIVE AVENUE
 PERMIT NUMBER 10030823
  
  
 1. CONFERENCE ROOM 101 REQUIRES SPRINKLER PROTECTION
 BELOW THE 8" WIDE SOFFIT WHEN UTILIZING SIDEWALL
 SPRINKLERS FOR PROTECTION.
  
 2. IT APPEARS THAT THE WRONG TYPE OF FIRE SPRINKLER
 HEADS ARE BEING USED. IT APPEARS THE SPACE WILL NO
 LONGER BE RESIDENTIAL BUT OFFICE SPACE. THE HEADS SHOWN
 HAVE A LOWER K FACTOR. PLEASE EXPLAIN RATIONALE FOR THE
 CONTINUED USE OF RESIDENTIAL SPRINKLERS IN THIS OFFICE
 SPACE.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
  
 WESLEY JOLIN, FIRE PROTECTION ENGINEER
 BUREAU OF FIRE PREVENTION
 (561) 805-6730 PHONE
 (561) 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-01 Cont ID  
Sent By jwitmer Date 2010-04-01 Time 08:17 Rev Time 0.00
Received By jwitmer Date 2010-04-01 Time 08:17 Sent To FIRE
Notes
2010-04-01 08:18:20INCOMING TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-04-01 Cont ID  
Sent By mcarsill Date 2010-04-01 Time 14:06 Rev Time 0.00
Received By mcarsill Date 2010-04-01 Time 14:06 Sent To  
Notes
***NONE***