Plan Review Details - Permit 10030690
Plan Review Stops For Permit 10030690
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-05-19 Cont ID  
Sent By jwitmer Date 2010-05-19 Time 14:18 Rev Time 0.77
Received By jwitmer Date 2010-05-19 Time 14:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-19 Cont ID  
Sent By jwitmer Date 2010-04-19 Time 16:21 Rev Time 4.50
Received By jwitmer Date 2010-04-19 Time 16:21 Sent To  
Notes
2010-04-19 16:23:06BUILDING PLAN REVIEW
 PERMIT:10030690
 ADD: 525 OKEECHOBEE BLVD/ 14TH FLOOR
 CONT: BALFOUR BEATTY CONST
 TEL: (954) 248-0107
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET G0201 BUILDING CODE INFORMATION: PLEASE ADD
 2007 EXISTING BUILDING CODE, LEVEL OF ALTERATION 401.4
 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) SHEET G0201 BUILDING CODE NOTE #8 INDICATES FIRE
 PROOFING OF WALLS AND FLOORS BUT MISSING DETAILS FOR
 SUCH PENETRATIONS,
 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. FIRE
 -RESISTANCE-RATED WALLS
 712.4.1.1 THROUGH PENETRATIONS.HORIZONTAL ASSEMBLIES.
  
 3) SHEET A0200 FLOOR PLAN X-RAY ROOM TO COMPLY WITH :
 435.5.1.3 PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND
 EQUIPMENT ARRANGEMENT OF ALL NEW INSTALLATIONS, OR
 MODIFICATIONS OF EXISTING INSTALLATIONS, UTILIZING
 X-RAY ENERGIES OF 200 KEV AND ABOVE FOR DIAGNOSTIC OR
 THERAPEUTIC PURPOSES SHALL BE SUBMITTED TO THE
 DEPARTMENT OF HEALTH FOR REVIEW AND APPROVAL. IN
 COMPUTATION OF PROTECTIVE BARRIER REQUIREMENTS, THE
 MAXIMUM ANTICIPATED WORKLOAD, USE FACTORS, OCCUPANCY
 FACTORS AND THE POTENTIAL FOR RADIATION EXPOSURE FROM
 OTHER SOURCES SHALL BE TAKEN INTO CONSIDERATION.
  
 4) SHEET A0200 DOOR # 320B LEFT SIDE OF DOORWAY IT
 APPEARS THAT TTHTE PLAN DOES NOT COMPLY WITH 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE FLOOR
 OR GROUND AREA WITHIN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL. MINIMUM OF 18 INCHES.
  
 5) SHEET M0700 EF-1 IT APPEARS TO BE A NEW ROOFTOP
 EXHAUST FAN, MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE SUPPORTS AS DETERMINED
 IN ACCORDANCE WITH THE FL BLD CODE. THIS MAY BE
 ACCOMPLISHED BY DESIGN OR BY APPLICATION OF SECTION
 301.13.1.
  
 1511.7 ROOF MOUNTED MECHANICAL UNIT S SHALL BE MOUNTED
 ON CURBS RAISED A MINIMUM OF 8 INCHES ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARENCE HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-05-26 Cont ID  
Sent By dwise Date 2010-05-26 Time 20:43 Rev Time 0.00
Received By dwise Date 2010-05-26 Time 20:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-04-28 Cont ID  
Sent By dwise Date 2010-04-27 Time 13:26 Rev Time 0.00
Received By dwise Date 2010-04-27 Time 13:26 Sent To  
Notes
2010-04-28 13:34:35ELECTRICAL REVIEW 04/27/2010
  
 1. PROVIDE ESSENTIAL TASK LIGHING REQUIRED PURSUANT TO
 517.33(A)(4) FOR X-RAY ROOM.
 2. RELOCATE POWER SHUT-OFF CONTROL FOR X-RAY TO
 ADJACENT CONTROL STATION PURSUANT TO 517.72(B)
 3. PLEASE REVIEW USE OF BREAKROOM RECEPTACLES WITH
 CLIENT. IF MICROWAVE(S) AND COFFEE EQUIPMENT ARE
 DESIRED ADDITIONAL CIRCUITS MAY BE INDICATED TO PREVENT
 NUISANCE TRIPPING OR OVERLOADING OF CIRCUITS.
  
 NOTE: IF DELAYS ARE ANTICIPATED IN CORRECTING THESE
 ISSUES WHICH MAY DETRIMENTALLY IMPACT THE PROJECT, A
 PROVISO OR PROVISOS MAY BE ISSUED TO ALLOW WORK TO
 BEGIN.
  
 PLEASE CONTACT ME WITH ANY QUESTIONS OR CONCERNS
 REGARDING THIS REVIEW.
  
 DOUG WISE
 561-805-6650
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-05-27 Cont ID  
Sent By mcarsill Date 2010-05-27 Time 14:25 Rev Time 0.00
Received By mcarsill Date 2010-05-27 Time 14:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-04-14 Cont ID  
Sent By mcarsill Date 2010-04-14 Time 11:06 Rev Time 0.00
Received By mcarsill Date 2010-04-14 Time 10:40 Sent To  
Notes
2010-04-14 11:03:28 
 14TH FLOOR PHASE II FIT OUT
 PERMIT NUMBER 10030690
  
 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 2. THE INSTALLATION OF THE TEMPORARY WALL SHALL NOT
 INTERFERE WITH ANY FIRE SAFETY EQUIPMENT.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER AND FIRE ALARM SYSTEM REMODEL.
  
 4. AN EXIT SIGN WITH ARROWS NEAR HALL 14-070 ON PAGE
 E0200 IS DIRECTING PERSONS WHERE?
  
 5. ALL NEW FIRE DAMPERS AFTER INSTALLATION SHALL BE
 DROP TESTED TO ENSURE PROPER OPERATION.
  
 6. WATER FLOW DATA REFERENCED ON PAGE FP0001 IS 5 YEARS
 OLD. ACCORDING TO INFORMATION TEST PERFORMED ON
 11/3/2005. THIS TEST DATA IS NOT ACCEPTABLE DUE TO ITS
 AGE.
  
 7. DIFFERENT ADDRESSES APPEAR TO EXIST ON THE DRAWINGS.
 525 AND 524 OKEECHOBEE CAN BE LOCATED ON THE DRAWINGS.
  
 8. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 9. ON PAGE A1002 IT REFERENCES THE OHIO BUILDING CODE
 AS IT RELATES TO INTERIOR FINISH.
  
 10. ON PAGE G0201 WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 2006 EDITION NOT THE 2003 EDITION.
  
 11. ANY ELECTRONIC LOCKING DEVICES ON EXIT DOORS SHALL
 COMPLY WITH SPECIAL LOCKING ARRANGEMENTS OF THE FLORIDA
 FIRE PREVENTION CODE (FFPC) 101 CHAPTER 7.
  
 12. COULD NOT LOCATE ANY FIRESTOPPING DETAILS FOR ANY
 RATED WALLS OR FLOORS.
  
 13. ON PAGE E0300 KEY # 3 AND GENERAL NOTES # 5
 REFERENCE SAW CUTTING OF FLOORS. PLEASE ADVISE IF
 GASOLINE POWERED SAWS ARE TO BE USED AND IF SO THE
 METHODS TO PREVENT CARBON MONOXIDE.
  
 14. SUPPORTING DOCUMENTS REQUIRED FOR ANY CHEMICALS
 THAT ARE PLANNED TO BE USED OR STORED.
  
 15. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 16. ANYTIME ANY REQUIRED FIRE PROTECTION SYSTEMS ARE
 DOWN FOR MORE THAN FOUR HOURS IN A TWENTY FOUR HOUR
 PERIOD A FIRE WATCH IS TO BE ESTABLISHED. ALL FIRE
 WATCHES SHALL BE IN WRITING TO THE BATTALION CHIEF OF
 FIRE PREVENTION OR THE ASSISTANT FIRE MARSHAL. FIRE
 WATCH PERSONNEL SHALL HAVE NO OTHER DUTIES EXCEPT TO
 WALK THE FLOORS, BE CELLULAR OR TELEPHONE EQUIPPED AND
 MUST MAINTAIN A LOG.
  
 17. TRASH AND DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 18. ANY CUTTING OR WELDING OPERATIONS TO COMPLY WITH
 NFPA 51B.
  
 19. NO DETAILS PROVIDED FOR REPAIRING ANY FIRE PROOFING
 DISCOVERED DAMAGED.
  
 20. MORE DETAILS REQUIRED ON NEW FIRE EXTINGUISHERS
 SHOWN IN PHASE II.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-04-28 Time   Rev Time  
Received By   Date 2010-04-13 Time   Sent To  
Notes
2010-04-15 08:15:05***DIGITAL PLAN REVIEW*** PLANS UPLOADED 4/6. REVIEWS
 DISTRIBUTED ON 4/13 UPON SUCCESSFUL PRE-SCREEN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-05-24 Cont ID  
Sent By rregueir Date 2010-05-24 Time 14:42 Rev Time 0.00
Received By rregueir Date 2010-05-24 Time 14:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-04-19 Cont ID  
Sent By rregueir Date 2010-04-19 Time 12:53 Rev Time 0.00
Received By rregueir Date 2010-04-15 Time 08:45 Sent To  
Notes
2010-04-15 13:57:14REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE PLANS FOR THIS PROJECT WERE SUBMITTED AND REVIEWED
 ELECTRONICALLY. ALL REVIEW COMMENTS ARE LOCATED HERE.
 HOWEVER, DRAWING MARK-UPS MAY BE AVAILABLE WITHIN
 PROJECTDOX TO AID IN UNDERSTANDING AND ADDRESSING THESE
 COMMENTS.
  
 1. ELECTRONIC SEAL AND SIGNATURE IS REQUIRED FOR PASSED
 PLANS PRIOR TO PERMIT ISSUANCE FOR ARCHITECT AND
 ENGINEER DESIGNED PLANS IN ACCORDANCE WITH FAC RULES
 61G1-16.005 AND 61G15-23.003.
  
 2. THE 8" ROUND DUCT IS SHOWN PENETRATING FIRE RATED
 WALL ASSEMBLIES AT TWO LOCATIONS THROUGH ROOM #14-201.
 ALSO, BASED ON THE ORIGINAL BUILDING PLANS, THE 8"
 ROUND DUCT IS ALSO PENETRATING A RATED WALL BETWEEN THE
 HALLWAY AND THE EXISTING MECHANICAL ROOM. SHOW HOW
 THESE PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE
 WITH FBC-M 607.5 AND 607.1.1.
  
 3. PAGE M0200 SHOWS FIRE DAMPERS AT LOCATIONS WHERE
 EXISTING PARTITIONS HAVE BEEN REMOVED. ARE THE FIRE
 DAMPERS TO BE REMOVED IN CONJUNCTION WITH THE WALL
 DEMO? FIRE DAMPERS SHALL BE INSTALLED IN RATED
 ASSEMBLIES IN ACCORDANCE WITH THEIR LISTING PER FBC-M
 607.2. ELIMINATE THE FIRE DAMPERS OR SHOW THEM LOCATED
 WITHIN A RATED WALL ASSEMBLY PER THE LISTING AND
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 4. THE ORIGINAL TENANT BUILD-OUT ON THIS FLOOR
 INCORMPRATED THE HVAC SYSTEM AS PART OF THE SMOKE
 CONTROL SYSTEM FOR THIS FLOOR. THE PROPOSED NEW SCOPE
 OF WORK WOULD INVOLVE MODIFICATIONS TO THE SYSTEM IN
 PLACE AT THIS TIME. PROVIDE AN ANALYSIS OF THE SYSTEM,
 WITH DESCRIPTIONS OF WHAT MODIFICATIONS ARE BEING MADE
 TO THE EXISTING SYSTEM IN ORDER TO ACCOMODATE THE NEW
 BUILD-OUT, INCLUDING ANY NEW EQUIPMENT AND/OR CHANGES
 TO THE SEQUENCE OF OPERATIONS AND/OR THE SMOKE CONTROL
 PANEL PER FBC-M 909.4.
  
 5. PLAN INDICATES NEW EXHAUST FAN ON ROOF. PROVIDE
 MANUFACTURER'S WIND RESISTANCE DATA AND INSTALLATION
 DETAIL FOR THIS FAN AND ANY EQUIPMENT/DUCTWORK WHICH
 MAY BE EXPOSED TO WIND IN ACCORDANCE WITH FBC-M 301.12.
 GUARDS MAY ALSO BE REQUIRED IN ACCORDANCE WITH FBC-M
 304.10.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-05-19 Cont ID  
Sent By lwagner Date 2010-05-19 Time 11:02 Rev Time 0.00
Received By lwagner Date 2010-05-19 Time 11:01 Sent To  
Notes
2010-05-19 11:02:27***PROVISO***
  
 RESTROOM 230-E VENT IS REQUIRED FOR LAVATORY.
  
 DISPOSER FOR BREAK ROOM SINK NOT TO INTERFERE WITH KNEE
 CLEARANCE 11-4.24.3
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-04-28 Cont ID  
Sent By lwagner Date 2010-04-28 Time 10:53 Rev Time 0.00
Received By lwagner Date 2010-04-21 Time 13:20 Sent To  
Notes
2010-04-28 11:02:36FBC 2007
  
 REVIEW 1
 ACTION: DENIED
  
 1. LAV SHOWN IS AN S-TRAP. A VENT WOULD BE REQUIRED.
 FBC PLUMBING 906.2
  
 2. DISPOSER MAY INTERFERE WITH KNEE SPACE UNDER SINK -
 PLEASE ADDRESS. 27" HIGH X 30" WIDE X 19" DEEP UNDER
 SINK.
  
  
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status N Date 2010-05-27 Cont ID  
Sent By eschneid Date 2010-05-17 Time 13:28 Rev Time 0.10
Received By eschneid Date 2010-05-17 Time 13:28 Sent To  
Notes
2010-05-17 13:29:36INTERIOR BUILD-OUT OF NEW BLDG.

Review Stop Z ZONING
Rev No 1 Status N Date 2010-04-14 Cont ID  
Sent By eschneid Date 2010-04-14 Time 14:34 Rev Time 0.50
Received By eschneid Date 2010-04-14 Time 14:34 Sent To  
Notes
2010-04-14 14:35:27INTERIOR BUILD-OUT OF NEW BUILDING.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved