Plan Review Details - Permit 10030605
Plan Review Stops For Permit 10030605 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-04-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-04-19 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-04-16 |
Time |
13:26 |
Sent To |
|
|
Notes |
2010-04-19 16:18:03 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) THE LOCATION OF THE STRUCTURE PLACES IT IN EXPOSURE | | CATEGORY 'C' PER FBC R301.2.1.4.3. PLEASE CORRECT THE | | PLANS AND INCREASE THE COMPONENT AND CLADDING PRESSURES | | ACCORDINGLY. | | | | 2) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | STRUCTURAL WINDOW MULLIONS THAT WILL BE USED PER DCA | | RULE 9B-72. | | | | 3) IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | COPY OF RECEIPT SUBMITTED TO CITY OF | | WEST PALM BEACH BUILDING DEPARTMENT, | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | 4) THE ENERGY CALCULATION FORM DOES NOT SPECIFY THE NEW | | R-19 INSULATION THAT WILL BE INSTALLED TO THE SINGLE | | ASSEMBLY CEILING AREA. FBC N1104.AB.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2010-04-09 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-04-09 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-04-09 |
Time |
09:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-04-30 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-04-27 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2010-03-24 |
Time |
11:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-04-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-04-16 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-04-16 |
Time |
13:01 |
Sent To |
|
|
Notes |
2010-04-19 15:41:16 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) THE SIGNED AND SEALED MECHANICAL PLAN ON SHEET P-M1 | | DOES NOT CORRESPOND WITH THE PLAN M.1 FROM MARMEK INC. | | ATTACHED TO THE EQUIPMENT SIZING CALCULATIONS. PLEASE | | SPECIFY WHICH ONE IS CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2010-04-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-04-19 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-04-19 |
Time |
09:19 |
Sent To |
|
|
Notes |
2010-04-19 10:11:59 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY PLUMBING | | | | 1) FBCR P3108 ONLY ALLOWS BATHROOM FIXTURES TO BE WET | | VENTED. ANY ADDITIONAL FIXTURES ARE REQUIRED TO | | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. | | | | 2) THE LAUNDRY SINK AND LAVATORY ARE REQUIRED TO BE | | VENTED PER FBCR P3105.1. | | | | 3) SPECIFY THE SIZE OF ALL DRAIN PIPING ON THE PLANS. | | FBCR P3005.4 | | | | 4) ON SHEET P-M1, THE NOTES SPECIFY THE 2004 FBC | | PLUMBING CODE. PLEASE CORRECT TO THE 2007 FBCR PLUMBING | | CODE. | | | | 5) THE PLANS SPECIFY 1/2" PVC FOR THE LAUNDRY SINK AND | | LAVATORY PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2010-04-27 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2010-04-27 |
Time |
18:40 |
Rev Time |
0.50 |
Received By |
lfranco |
Date |
2010-04-27 |
Time |
18:40 |
Sent To |
I |
|
Notes |
2010-04-27 18:45:56 | PLANNING AND ZONING: | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | INCLUDES THE PROPERTY???S ADDRESS AND LEGAL | | DESCRIPTION. | | | | 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED SCOPE OF | | WORK TO ALL PROPERTY LINES. | | | | PURSUANT TO SECTION SEC. 94-72 OF THE ZONING AND LAND | | DEVELOPMENT REGULATIONS ("ZLDR"), THE MINIMUM SETBACKS | | FOR PRINCIPAL BUILDING IN A SINGLE-FAMILY LOW DENSITY | | ("SF7") RESIDENTIAL DISTRICT IS AS FOLLOWS: | | | | (2) | | A. FRONT: 25 FEET; | | B. CORNER: 12.5 FEET; | | C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER | | IS LESS; | | D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | | | |
|
|
|