Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-03-25 Cont ID  
Sent By mawillia Date 2010-03-25 Time 15:35 Rev Time 0.00
Received By mawillia Date 2010-03-25 Time 14:23 Sent To  
Notes
2010-03-25 15:18:59***** APPROVED *****
  
 PLAN SHEET 1 OF 1 STAMPED, INITIALED AND DATED; READY
 FOR PERMIT ISSUANCE.
  
 PLEASE VERIFY THE BRANCH LINE SIZES SUPPLYING THE
 FLEXIBLE SPRINKLER CONNECTIONS ARE NOT AFFECTED BY THE
 ADDITIONAL PRESSURE REQUIRED TO ACCOUNT FOR THE
 FRICTION LOSS ASSOCIATED WITH THE FLEXIBLE CONNECTIONS.
  
  
  