Plan Review Details - Permit 10030555
Plan Review Stops For Permit 10030555
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-31 Cont ID  
Sent By mcarsill Date 2010-03-31 Time 10:41 Rev Time 0.00
Received By mcarsill Date 2010-03-31 Time 10:35 Sent To  
Notes
2010-03-31 10:40:56 
 534 DATURA STREET
 PEMIT NUMBER 10030555
  
  
 1. REMOVE FLEXIBLE PIPE CONNECTION FROM ARMOVER DETAIL
 ON PAGE FP-1.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
  
 WESLEY JOLIN, FIRE PROTECTION ENGINEER
 BUREAU OF FIRE PREVENTION
 (561) 805-6730 PHONE
 (561) 804-4774 FAX
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-25 Cont ID  
Sent By mawillia Date 2010-03-25 Time 14:01 Rev Time 0.00
Received By mawillia Date 2010-03-25 Time 12:05 Sent To  
Notes
2010-03-25 13:54:05***** DENIED *****
  
 1) PROVIDE MEANS FOR ROOM IDENTIFICATION (ROOM NAME OR
 COLUMN BUBBLES ETC.).
  
 2) UPRIGHT SPRINKLER SYMBOL IS THE SAME SYMBOL AS THE
 BRANCH LINE OUTLET.
  
 3) FLEXIBLE SPRINKLER SYMBOL FROM KEY DOES NOT APPEAR
 ON THE FLOOR PLAN ANYWHERE.
  
 4) USE OF FLEXIBLE SPRINKLER CONNECTIONS NEED TO BE
 SUPPORTED BY HYDRAULIC SPRINKLER CALCULATIONS.
  
 5) SHOW LOCATION OF SYSTEM CONTROL VALVE.
  
 6) SHOW SIZE OF EXISTING CROSS MAIN.
  
 7) SHOW PIPE HANGER LOCATIONS.
  
 8) SOME EXISTING PIPING IS SHOWN IN GRAY WHILE OTHER
 EXISTING PIPING IS SHOWN IN BLACK.
  
 9) ROOM NORTH OF DINING ROOM DOES NOT PROVIDE PROPER
 SPRINKLER COVERAGE BELOW THE 10'-0" SOFFITS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-25 Cont ID  
Sent By mawillia Date 2010-03-25 Time   Rev Time 0.00
Received By mawillia Date 2010-03-22 Time 09:55 Sent To  
Notes
2010-03-25 10:30:09IN FIRE BOX
2010-03-24 09:56:11UNDER 5 K, PLUMBING