Plan Review Details - Permit 10030552
Plan Review Stops For Permit 10030552 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2010-03-31 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2010-03-31 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2010-03-31 |
Time |
14:40 |
Sent To |
|
|
Notes |
2010-03-31 14:49:44 | | | | | 403 NORTHWOOD ROAD | | PERMIT NUMBER 10030552 | | | | | | 1. INITIATING DEVICES SHOWN ON THE PLANS SHALL | | CORRESPOND WITH THE RISER DIAGRAM IDENTIFIERS. | | | | 2. THE REVISED PLAN IS MISSING REVISION CLOUDS. THE | | REVISED PLANS ARE DIFFERENT FROM THE FIRST SUBMITTED | | PLANS. | | | | 3. THE ENTIRE INSTALLATION IS SUBJECT TO FIELD | | INSPECTION AND APPROVAL. | | | | 4. NEW DEVICES ARE TO BE TESTED AFTER INSTALLATION TO | | ENSURE PROPER OPERATION. | | | | 5. THE REMOTE TEST SWITCHES ARE CLOUDED AS NEW DEVICES | | HOWEVER THE LEGEND INDICATES THEY ARE EXISTING. | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | (561) 804-4724 PHONE | | (561) 804-4774 FAX | | | | WESLEY JOLIN, FIRE PROTECTION ENGINEER | | BUREAU OF FIRE PREVENTION | | (561) 805-6730 PHONE | | (561) 804-4774 FAX |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2010-03-23 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2010-03-23 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2010-03-23 |
Time |
13:00 |
Sent To |
|
|
Notes |
2010-03-23 13:25:37 | ***** DENIED ***** | | | | | | 1) THE INFORMATION CONTAINED IN THE PROJECT DESCRIPTION | | DOES NOT CORRESPOND WITH WHAT IS SHOWN ON THE FLOOR | | PLAN. | | | | 2) FLOOR PLAN DOES NOT DISTINGUISH BETWEEN EXISTING | | DEVICES AND NEW DEVICES. | | | | 3) ONLY ONE SMOKE DETECTOR IS SHOWN IN THE FIRE ALARM | | RISER DIAGRAM WHEREAS, TWO SUCH DEVICES ARE SHOWN ON | | THE FLOOR PLAN. TO BETTER IDENTIFY DEVICES LIST ADDRESS | | NUMBERS. | | | | 4) THE BATTERY CALCULATION SHOWS A QUANTITY OF 40 | | DEVICES FOR THE HORN/STROBE DEVICES, PLEASE VERIFY | | QUANTITY OF HORN/STROBE DEVICES. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-03-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-03-31 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-03-31 |
Time |
10:00 |
Sent To |
|
|
Notes |
2010-03-31 10:01:13 | SENT TO FIRE BOX |
|
|
|