Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-22 Cont ID  
Sent By jgomez Date 2010-03-22 Time 16:59 Rev Time 0.00
Received By jgomez Date 2010-03-22 Time 16:54 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-22 Cont ID  
Sent By jgomez Date 2010-03-22 Time 15:49 Rev Time 0.00
Received By jgomez Date 2010-03-22 Time 14:40 Sent To  
Notes
2010-03-22 15:54:38RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 TO MEET THE DESIGN PRESSURES OF SEC. 1609
 FBC 2007.
  
 2- PROVIDE PRODUCT APPROVAL FOR POLYFOAM USED FOR ROOF
 TILE INSTALLATION AS REQUIRED BY DCA RULE 9B-72.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712