Plan Review Details - Permit 10030472
Plan Review Stops For Permit 10030472
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2010-09-15 Cont ID  
Sent By rmcdouga Date 2010-09-15 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2010-09-15 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2010-07-30 Cont ID  
Sent By rmcdouga Date 2010-07-30 Time 13:38 Rev Time 0.00
Received By rmcdouga Date 2010-07-30 Time 13:38 Sent To  
Notes
2010-07-30 14:21:18TRUSS DRAWING REVIEW FOR MODEL "F" WITH GABLE AND HIP
 ROOF OPTIONS
  
 DENIED BY BUILDING
  
 1) THE TRUSS LAYOUTS FROM THE TRUSS ENGINEER ARE NOT
 SIGNED AND SEALED AS REQUIRED BY FS 471.
  
 2) THE TRUSS LAYOUT FOR THE HIP ROOF OPTION DIFFERS
 FROM THE ROOF DESIGN ON SHEET S-1 OF THE PLANS AS NOTED
 BY THE ENGINEER AND ARCHITECT OF RECORD FOR THE
 STRUCTURE. PLEASE MAKE CORRECTIONS AS REQUESTED IN
 THEIR REVIEW COMMENTS.
  
 3) THE TRUSS REVIEW LETTERS THAT WERE SUBMITTED BY THE
 ENGINEER OF RECORD ARE NOT SIGNED AND SEALED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-06-25 Cont ID  
Sent By rmcdouga Date 2010-06-25 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2010-06-25 Time 12:39 Sent To  
Notes
2010-06-25 12:40:08REVISION REQUIRED
  
 SUBMIT ENGINEERED TRUSS DRAWINGS AND LAYOUT FOR REVIEW
 AND APPROVAL PRIOR TO INSTALLING TRUSSES,

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-05-14 Cont ID  
Sent By rmcdouga Date 2010-05-14 Time 13:54 Rev Time 0.00
Received By rmcdouga Date 2010-05-14 Time 13:54 Sent To  
Notes
2010-05-14 13:55:142007 FBC W/2009 REVISIONS
 MODEL 'F' - MASTER
  
 1) THE COVER SHEET INCORRECTLY LISTS THE 2005 EDITION
 OF THE NATIONAL ELECTRICAL CODE AND THE FAIR HOUSING
 GUIDELINES. THE 2008 EDITION OF THE NEC IS APPLICABLE
 AND FAIR HOUSING GUIDELINES DO NOT APPLY. PLEASE
 CORRECT.
  
 2) TWO COPIES OF CURRENT PRODUCT APPROVALS FOR EXTERIOR
 DOORS, WINDOWS, WINDOW MULLIONS, OVERHEAD GARAGE DOOR,
 ROOF SHINGLES, BLOCK LINTELS, HARDI-PLANK, HURRICANE
 CONNECTORS/STRAPS, ETC. PER DCA RULE 9B-72. THE
 DESIGNER OF RECORD IS REQUIRED TO REVIEW AND APPROVE
 THE PRODUCT APPROVALS IN WRITING PER FBC 106.3.3 CITY
 AMENDMENTS.
  
 3) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS DRAWINGS
 COMPLYING WITH R802.1.6.1 THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE STRUCTURAL DESIGNER OF RECORD FOR EACH
 OF THE ROOF OPTIONS.
  
 4) THE ENERGY CALCULATIONS THAT WERE SUBMITTED DO NOT
 LIST THE INTERIOR METAL FRAME ADJACENT WALLS THAT
 SEPARATE THE CONDITIONED SPACE FROM THE UNCONDITIONED
 GARAGE. PLEASE CORRECT. ALSO CHECK THAT THE CONDITIONED
 FLOOR AREA ON THE FORM MATCHES THE A/C AREA THAT IS
 SPECIFIED ON THE PLANS.
  
 NOTE: BECAUSE THESE PLANS ARE TO BE MASTERS, THE
 PRODUCT APPROVALS AND TRUSS DRAWINGS ARE REQUIRED TO BE
 SUBMITTED FOR REVIEW BEFORE THE MASTERED PLANS ARE
 APPROVED. THEY WILL BE FILED WITH THE MASTER AND WILL
 NOT BE REQUIRED TO BE SUBMITTED WITH THE PERMITS
 APPLIED FOR UNDER THE MASTER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-05 Cont ID  
Sent By rmcdouga Date 2010-04-05 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2010-04-05 Time 13:50 Sent To  
Notes
2010-04-05 13:56:432007 FBC W/2009 REVISIONS
 MODEL 'F' -MASTER
  
 DENIED BY BUILDING
  
 1) PERMIT, RADON AND COUNTY IMPACT FEES WILL BE
 REQUIRED WHEN APPLYING FOR PERMIT.
  
 2) A CONTRACTOR THAT HAS BEEN REGISTERED WITH THE
 CONSTRUCTION SERVICES DEPARTMENT WILL BE REQUIRED
 BEFORE A BUILDING PERMIT CAN BE ISSUED. THE STATUS AT
 THIS TIME IS TBD.
  
 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED BY THE TIME OF THE FIRST INSPECTION.
  
 4) TWO COPIES OF A SURVEY SHOWING THE PROPOSED LOCATION
 OF THE STRUCTURE AND THE DISTANCE TO PROPERTY LINES IS
 REQUIRED.
  
 5) THE FAIR HOUSING DESIGN GUIDE LINES DO NOT APPLY TO
 SINGLE FAMILY DWELLINGS. ACCORDING TO THE FAIR HOUSING
 DESIGN MANUAL, THE FAIR HOUSING DESIGN AND CONSTRUCTION
 REQUIREMENTS OF THE FAIR HOUSING ACT APPLY TO NEW
 MULTIFAMILY HOUSING CONSISTING OF FOUR OR MORE DWELLING
 UNITS.
  
 6) TWO COPIES OF CURRENT PRODUCT APPROVALS ARE REQUIRED
 FOR THE EXTERIOR DOORS, WINDOWS, WINDOW MULLIONS,
 OVER-HEAD GARAGE DOOR, ROOF SHINGLES, BLOCK LINTELS,
 HARDY-PLANK SIDING, ETC. PER DCA RULE 9B-72.
  
 7) FBC R301.2.1.2 REQUIRES ALL GLAZED OPENINGS TO BE
 PROTECTED FROM WIND-BORNE DEBRIS. IF THE LARGE MISSILE
 IMPACT RATED WINDOWS INDICATED ON THE PLANS, ARE NOT
 INSTALLED, THEN STORM PANELS WILL BE REQUIRED. TWO
 COPIES OF THE PRODUCT APPROVALS FOR THE STORM PANELS,
 INSTALLATION SCHEDULES AND KEY PLANS WILL BE REQUIRED.
  
 8) THE WINDOW SCHEDULE ON SHEET A1.1 DOES NOT SPECIFY
 THE TYPE OF WINDOW, SUCH AS SINGLE HUNG, DOUBLE HUNG,
 CASEMENT, ETC. PLEASE CORRECT.
  
 9) NOTE: THE BATH EXHAUST RATE IS SPECIFIED AS 100 CFM
 ON THE PLANS, HOWEVER, FBC R M1507.3 REQUIRES 50 CFM.
  
 10) THE ENERGY CALCULATIONS SPECIFY R-7 INSULATION AT
 THE EXTERIOR BLOCK WALLS. SHEET A4.1 SPECIFIES R-3
 RIGID INSULATION AT EXTERIOR BLOCK WALLS. SECTION
 N1100.A.1.1 OF THE 2007 FBC ENERGY GLITCH AMENDMENTS
 ONLY ALLOWS THE R-VALUE OF ADDED INSULATION FOR THE
 CALCULATIONS. PLEASE CORRECT.
  
 11) SPECIFY THE ATTIC ACCESS SIZE AND LOCATION ON THE
 PLANS AS REQUIRED BY R807.1.
  
 12) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION REQUIREMENTS FOR THE
 SPRAY FOAM INSULATION TO SHOW COMPLIANCE WITH R806.4
 AND R314.
  
 13) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS DRAWINGS
 COMPLYING WITH R802.1.6.1 THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE STRUCTURAL DESIGNER OF RECORD OF THE
 STRUCTURE FOR THE TWO ROOF OPTIONS.
  
 14) ON SHEET A1.1 THE SAFETY GLAZING NOTE SHOULD
 REFERENCE SECTION FBC R308.4 AND NOT FBC 2406.3.
  
 15) DETAIL 3 ON SHEET A2.1 FAILS TO PROVIDE A
 CONTINUOUS LOAD PATH FOR THE PENT. ROOF. PLEASE SPECIFY
 THE RAFTER TO HEADER, HEADER TO KNEE BRACE, BRACE TO
 POST AND POST TO WALL CONNECTIONS. R 301.1
  
 16) NOTE 0907 SPECIFIES METAL STUDS AT 18" OC. IS THIS
 MEANT TO BE 16" OC PLEASE CLARIFY.
  
 17) ON A4.1 NOTE 0903 SPECIFIES 5/8" STUCCO OVER 3/4"
 PLYWOOD ON THE SOFFIT. TYPICALLY HIGH RIB METAL LATH
 WITHOUT BACKING IS USED ON THE SOFFIT. HOWEVER, ASTM C
 926 REFERENCED BY FBC R703.6.1 REQUIRES THE STUCCO TO
 BE 7/8" WHEN APPLIED VERTICALLY TO METAL LATH OVER A
 SOLID BASE. PLEASE CORRECT.
  
 18) SPECIFY THE METHOD AND FASTENERS THAT WILL BE USED
 TO ATTACH THE FAUX WOOD OUT-LOOKERS.
  
 19) THE TRUSS ANCHOR SCHEDULE ON SHEET S-2 LISTS AN
 EXPIRATION DATE OF 1/1/2010 FOR ALL CONNECTORS. PLEASE
 CLARIFY.
  
 20) THE TRUSS ANCHOR SCHEDULE ALSO LISTS PRODUCT
 APPROVAL NUMBERS THAT ARE EXPIRED. PLEASE CORRECT. ONLY
 PRODUCTS WITH CURRENT PRODUCT APPROVALS WILL BE
 ACCEPTED. DCA RULE 9B-72
  
 21) SPECIFY THE CONNECTORS FOR THE TRUSS TO 4 X 8 WOOD
 BEAM CONNECTION AT THE FRONT PORCH. FBC R301.1
  
 22) THE MAXIMUM RISER HEIGHT FOR STAIRS IS 7-3/4" PER
 FBC R311.5.3.1. PLEASE REVISE THE 8" RISER HEIGHTS
 SPECIFIED AT THE EXTERIOR PORCHES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-06-23 Cont ID  
Sent By btrobaug Date 2010-06-23 Time 16:28 Rev Time 0.00
Received By btrobaug Date 2010-06-23 Time 16:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-04-13 Cont ID  
Sent By btrobaug Date 2010-04-13 Time 13:45 Rev Time 0.00
Received By btrobaug Date 2010-04-13 Time 13:45 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2010-03-17 Cont ID  
Sent By swurafti Date 2010-03-17 Time 16:50 Rev Time 0.00
Received By swurafti Date 2010-03-17 Time 16:49 Sent To  
Notes
2010-03-17 16:50:17HISTORIC APPROVED W/PROVISO BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-06 Cont ID  
Sent By lmartine Date 2010-05-06 Time 09:44 Rev Time 0.00
Received By lmartine Date 2010-05-06 Time 09:44 Sent To  
Notes
2010-05-06 09:46:03R--25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-06 Cont ID  
Sent By lmartine Date 2010-04-15 Time 09:44 Rev Time 0.00
Received By lmartine Date 2010-03-18 Time 09:45 Sent To  
Notes
2010-03-18 09:45:54INCOMING TO R-25

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-05-14 Cont ID  
Sent By rmcdouga Date 2010-05-14 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2010-05-14 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-04-05 Cont ID  
Sent By rmcdouga Date 2010-04-05 Time 14:18 Rev Time 0.00
Received By rmcdouga Date 2010-04-05 Time 14:18 Sent To  
Notes
2010-04-05 14:22:572007 FBC W/2009 REVISIONS
 MODEL 'F' - MASTER
 DENIED BY MECHANICAL
  
 1) SHOW COMPLIANCE WITH FBC R M1602.4 FOR BALANCED
 RETURN AIR. SHOW LOCATIONS AND SIZES OF TRANSFER DUCTS
 OR GRILLS IN THE BEDROOMS.
  
 2) SUBMIT SPECIFICATIONS FROM THE MECHANICAL EQUIPMENT
 MANUFACTURER SHOWING THAT THE EQUIPMENT, APPLIANCES AND
 SUPPORTS ARE DESIGNED TO RESIST THE WIND PRESSURES
 GENERATED BY A 140 MPH WIND SPEEDS REQUIRED BY FBC R
 M1307.3.
  
 3) THE MECHANICAL SYSTEM SIZING SUMMARY DOES NOT MATCH
 THE SIZE OF THE UNITS SPECIFIED IN THE EQUIPMENT
 SCHEDULE ON THE MECHANICAL PLANS.
  
 4) NOTE: THE EQUIPMENT SIZING SUMMARY USES WORST CASE
 ORIENTATION OF THE STRUCTURE. WHEN SUBMITTING FOR
 INDIVIDUAL PERMITS THE ACTUAL ORIENTATION OF THE
 STRUCTURE WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-05-14 Cont ID  
Sent By rmcdouga Date 2010-05-14 Time 13:55 Rev Time 0.00
Received By rmcdouga Date 2010-05-14 Time 13:55 Sent To  
Notes
2010-05-14 13:55:57REVIEW NEW SHEETS

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-04-05 Cont ID  
Sent By rmcdouga Date 2010-04-05 Time 14:41 Rev Time 0.00
Received By rmcdouga Date 2010-04-05 Time 14:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2010-07-29 Cont ID  
Sent By jroach Date 2010-07-29 Time 13:55 Rev Time 0.00
Received By jroach Date 2010-07-29 Time 13:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2010-06-15 Cont ID  
Sent By jroach Date 2010-06-15 Time 15:50 Rev Time 0.00
Received By jroach Date 2010-06-15 Time 15:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-04-15 Cont ID  
Sent By jroach Date 2010-04-15 Time 18:16 Rev Time 0.00
Received By jroach Date 2010-04-15 Time 18:16 Sent To  
Notes
***NONE***