Plan Review Details - Permit 10030427
Plan Review Stops For Permit 10030427
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-05-13 Cont ID  
Sent By jgomez Date 2010-05-13 Time 09:46 Rev Time 0.00
Received By jgomez Date 2010-05-13 Time 09:46 Sent To  
Notes
2010-05-13 10:32:48BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- A) PROVIDE HANDRAILS ON THE MIDDLE OF THE STAIRWAY
 AS REQUIRED BY SEC. R312.1 AND PROVIDE COMPLETE DETAILS
 AND SPECS TO SHOW COMPLIANCE WITH TABLE R301.5. PLANS
 PROVIDED DON'T SHOW ANY.
 B) PROVIDE COMPLETE FRAMING DETAILS AND SPECS FOR
 STAIRS LANDINGS. TABLE R301.5. PLANS DON'T SHOW ANY.
 C) PROVIDE COMPLETE SPECS AND DETAILS FOR LOGGIA
 GUARDRAIL TO SHOW COMPLIANCE WITH TABLE R301.5
  
 2- REVISE PLYWOOD SHEATHING NAILING SCHEDULE. ONLY THE
 SPACING FOR ZONE 3 WAS SPECIFIED. MISSING SPACING FOR
 THE OTHER ZONES.
  
 3- PROVIDE COMPLETE SPECIFICATIONS FOR DECORATIVE
 SHUTTERS SHOWN ON PLANS. SPECIFY TYPE/MATERIAL AND
 FASTENING TO SHOW COMPLIANCE WITH SEC. R301.
  
 4- PROVIDE PRODUCT APPROVAL (REVIEWED IN WRITING BY THE
 DESIGNER OF RECORD) AS REQUIRED BY DCA RULE 9B-72 FOR
 PRECAST LINTELS SPECIFIED ON PLANS.
  
 5- REVISE TRUSS PACKAGE TO INCLUDE THE ATTIC LIVE LOAD
 AS REQUIRED BY TABLE R301. TRUSS PACKAGE TO BE HANDLED
 TO THE INSPECTOR AT TIME OF FRAMING INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-31 Cont ID  
Sent By jgomez Date 2010-03-31 Time 17:26 Rev Time 0.00
Received By jgomez Date 2010-03-31 Time 17:26 Sent To  
Notes
2010-03-31 17:27:59RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- SHEET A-1:
 A) DIMENSION SHOWN ON FOUNDATION PLANS FOR REAR
 CONCRETE PATIO DOESN'T MATCH DIMENSION SHOWN ON SURVEY.
 REVISE AS REQUIRED TO MATCH.
 B) STAIRS DETAILS: * PROVIDE COMPLETE SPECS FOR
 STAIRWAY ATTACHMENT AT TOP AND BOTTOM. SPECIFY METAL
 HANGER AND FASTENING OF STAIRWAY TO CONCRETE SLAB. **
 PROVIDE DETAILS AND SPECS FOR STAIR LANDING. ***
 PROVIDE DETAILS AND SPECS FOR HANDRAILS TO VERIFY
 COMPLIANCE WITH THE DESIGN CRITERIA OF TABLE R301.5,
 SEC. R311 AND SEC. R312 OF 2007 FLORIDA RESIDENTIAL
 CODE.
 C) UPDATE FIREBLOCKING NOTE. REFERENCE CORRECT CODE
 SEC. R602.1.2 OF THE 2007 FLORIDA RESIDENTIAL CODE NOT
 THE SFBC.
  
 2- SHEET A-2:
 A) SPECIFY SIZE OF ATTIC ACCESS. SEC. R807.
 B) SHOW LOCATION OF HANDRAILS. SEC. R312.5
 C) CLARIFY TYPE OF RAILING ON FRONT LOGGIA. IS IT
 ALUMINUM OR WOOD RAILING. COORDINATE WITH EXTERIOR
 ELEVATION ON SHEET A-4.
  
 3- SHEET A-3:
 A) REVISE DESIGN PARAMETERS INFORMATION. ACCORDING TO
 SEC. R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE
 "C". NOT "B". REVISE ALL DOORS/WINDOWS DESIGN PRESSURES
 ACCORDINGLY.
 B) UPDATE ALL INFORMATION SHOWN ON DESIGN PARAMETERS TO
 REFLECT THE 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS. REVISE THE FBC CODE SECTIONS CITED AND THE
 YEAR FOR ASCE 7.
 C) REVISE PLYWOOD SHEATHING NAILING SCHEDULE FOR ROOF.
 NEED TO USE 8D RING SHANK NAILS AND SPACING IS 4"O.C.
 IN ROOF ZONE #3. SEE SEC. R803.2.3.1 AND REVISE AS
 REQUIRED.
  
 4- SHEET A-5. TWO STORY WALL SECTION: A) REVISE THE
 ATTIC INSULATION TO MATCH THE ENERGY CALCULATIONS.
 B) SPECIFY HOW MUCH EMBEDEMENT IS REQUIRED FOR THE
 ANCHOR BOLTS IN THE (2)2X10 LEDGER SUPPORTING THE
 SECOND FLOOR TRUSSES TO VERIFY COMPLIANCE WITH THE
 DESIGN LOADS OF SEC. R301 AND STRUCTURUAL NOTES ON
 SHEET A-7.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) SHUTTERS AS SHOWN ON ELEVATIONS. AND PROVIDE
 COMPLETE INSTALLATION SCHEDULE.
 B) PRECAST LINTELS AS SHOWN ON PLANS.
 C) ENTRY DOOR.
 D) FRENCH DOORS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT. DESIGN PRESSURES ON
 FLORIDA PRODUCT APPROVAL FL-7630.4 SUBMITTED DON'T MEET
 THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT. ALSO,
 CLARIFY WHICH FRENCH DOOR PRODUCT APPROVAL IS GOING TO
 BE USED. THERE ARE DIFFERENT PRODUCT APPROVALS
 SUBMITTED INCLUDING AN NOA 08-0409.04. PROVIDE ONLY THE
 ONE THAT IS GOING TO BE USED AND MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
  
 6- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 7- REVISE THE ENERGY CALCULATIONS. PROVIDE CORRECT
 BUILDER'S NAME AND COMPLETE THE REST OF THE INFORMATION
 ON TOP OF THE FORM.
  
 8- SURVEYS NEED TO HAVE SURVEYOR'S ORIGINAL SIGNATURE
 (NOT COPY) AS REQUIRED BY CHAPTER 472 OF FLORIDA
 STATUTES.
  
 9- TRUSS PACKAGE:
 A) TOTAL DESIGN LOAD TO MATCH DESIGN LOAD SPECIFIED BY
 THE ARCHITECT ON STRUCTURAL NOTES ON SHEET A-7.
 B) ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 COMPLETE TRUSS PACKAGE PRIOR TO SUBMITTAL TO THIS
 OFFICE.
 C) TRUSS ENGINEER TO PROVIDE ALL HIS INFORMATION AND
 PROVIDE ORIGINAL SEAL AND SIGNATURE ON TRUSS LAYOUT AND
 INDIVIDUAL TRUSSES AS REQUIRED BY CHAPTER 471 AND SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 10 BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT.
  
 11- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION
 IS TOO LOW. OWES $1762.01 FOR UPDATED PERMIT VALUATION
 AND RADON FEES.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-12-07 Cont ID  
Sent By rlecky Date 2010-12-07 Time 09:50 Rev Time 0.00
Received By rlecky Date   Time   Sent To  
Notes
2010-12-07 09:51:29ELECTICAL REVISIONS ACCEPTED. RL

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-05-10 Cont ID  
Sent By btrobaug Date 2010-05-10 Time 12:52 Rev Time 0.00
Received By btrobaug Date 2010-05-10 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-04-09 Cont ID  
Sent By btrobaug Date 2010-04-09 Time 08:58 Rev Time 0.00
Received By btrobaug Date 2010-04-09 Time 07:26 Sent To I
Notes
2010-04-09 08:58:14 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET E-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2008 NEC UNLESS
 OTHERWISE NOTED.
  
 1} PROVIDE ELECTRICAL LOAD CALCULATIONS PER ARTICLE
 220, 2008 NEC.
  
 2} INDICATE ROOM DESIGNATIONS ON THE ELECTRICAL PLAN.
 106.1.3 FBC AS AMENDED.
  
 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 4} INDICATE THE SIZE OF THE EQUIPMENT GROUNDING
 CONDUCTOR FOR THE FEEDER. 215.5.
  
 5} 250.94 BONDING FOR OTHER SYSTEMS.
 AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. INDICATE ON THE RISER DIAGRAM.
  
 6} 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS.
 IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15- AND
 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT
 RECEPTACLES. ADD TO NOTES.
  
 7} CIRCUIT #20 BATH/LAUNDRY GFI IS IN VIOLATION OF
 210.11 (C)(2) LAUNDRY BRANCH CIRCUITS. THIS CIRCUIT
 SHALL HAVE NO OTHER OUTLETS.
  
 8} PER 408.4 CIRCUIT DIRECTORY OR CIRCUIT
 IDENTIFICATION, CLARIFY CIRCUITS 29 & 31. ALSO CIRCUIT
 #25 MARKED DINING ROOM, SEE 210.52 (B)(1) FOR SMALL
 APPLIANCE 20 AMP CIRCUIT REQUIREMENT, CLARIFY.
  
 9} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2008 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES IN ALL BEDROOMS, DINING ROOM AND GREAT
 ROOM.
  
 10} INDICATE A DISCONNECTING MEANS FOR THE WATER
 HEATER. SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS,
 AND 422.31(B) FOR HARDWIRE REQUIREMENTS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2010-03-17 Cont ID  
Sent By ssherman Date 2010-03-17 Time 10:59 Rev Time 0.00
Received By ssherman Date 2010-03-17 Time 10:59 Sent To  
Notes
2010-03-17 10:59:46NO FEE PER JILLIAN PAPA

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-09-16 Cont ID  
Sent By lmartine Date 2010-09-16 Time 11:09 Rev Time 0.00
Received By lmartine Date 2010-09-07 Time 16:47 Sent To  
Notes
2010-09-16 11:24:11REVISION #10090124 RE-ROUTED TO HAROLD'S OFFICE
2010-09-07 16:48:00INCOMING SENT TO J G DESK/ JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-04 Cont ID  
Sent By shill Date 2010-05-04 Time 14:53 Rev Time 0.00
Received By shill Date 2010-05-04 Time 14:53 Sent To  
Notes
2010-05-04 14:54:06R 21
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-09 Cont ID  
Sent By btrobaug Date 2010-04-09 Time 08:59 Rev Time 0.00
Received By btrobaug Date 2010-03-18 Time 10:24 Sent To  
Notes
2010-04-09 08:59:50TO HOLDING BIN UNDER "I"./WRT.
2010-03-18 10:25:33INCOMING SENT TO R-5

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2010-05-13 Cont ID  
Sent By jgomez Date 2010-05-13 Time 09:39 Rev Time 0.00
Received By jgomez Date 2010-05-13 Time 09:39 Sent To  
Notes
2010-05-13 09:41:04TRACKING NO MU-2010-008151-0000.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-03-31 Cont ID  
Sent By jgomez Date 2010-03-31 Time 17:10 Rev Time 0.00
Received By jgomez Date 2010-03-31 Time 17:10 Sent To  
Notes
2010-03-31 17:11:571- BRING PLANS TO PALM BEACH COUNTY. (2300 N. JOG RD)
 TO CHECK IF IMPACT FEES ARE DUE. BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2010-05-17 Cont ID  
Sent By rkussner Date 2010-05-17 Time 10:38 Rev Time 0.00
Received By rkussner Date 2010-05-17 Time 10:38 Sent To  
Notes
2010-05-17 10:41:29***LANDSCAPE APPROVED WITH "PROVISO"***
  
 APPLY FOR LANDSCAPE PERMIT AND HAVE PLANS APPROVED,
 IMPLEMENTED AND SUCCESSFULLY INSPECTED PRIOR TO C/O.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-04-06 Cont ID  
Sent By rkussner Date 2010-04-06 Time 09:20 Rev Time 0.00
Received By rkussner Date 2010-04-06 Time 09:20 Sent To  
Notes
2010-04-06 09:35:01***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR A LANDSCAPE PERMIT. SUBMIT 2 COPIES
 OF A COMPLETE LANDSCAPE PLAN WITH A COST ESTIMATE THAT
 INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND
 LABOR, BROKEN DOWN INTO UNIT COST.
  
 2. PLEASE APPLY FOR AN IRRIGATION PERMIT. SUBMIT 2
 COPIES OF AN IRRIGATION PLAN. YOU MUST PROVIDE 120%
 COVERAGE TO ALL LANDSCAPED AREAS, INCLUDING THE
 RIGHT-OF-WAY. A BACK-FLOW PREVENTER AND RAIN GAUGE IS
 REQUIRED.
  
 3. ON THE LANDSCAPE PLAN, PLEASE PROVIDE THE TABULATION
 NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE
 XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS,
 INCLUDING THE XERISCAPE DESIGN OPTIONS.
  
 4. ON THE LANDSCAPE PLAN, PLEASE PROVIDE THE LOCATION
 OF ALL OVERHEAD AND UNDERGROUND LINES AND OTHER
 UTILITIES, EASEMENTS, EXISTING TREE CANOPIES ON THE
 PROPERTY OR ON ADJACENT PROPERTY NEAR THE PROPERTY
 LINES AND ANYTHING ELSE THAT MAY IMPACT THE PROPOSED
 LANDSCAPING.
  
 5. PURSUANT TO SECTION 94-448 (D) (2), THE LANDSCAPE
 PLAN SHALL INCLUDE ALL OF THE ITEMS ENUMERATED IN THIS
 SECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-05-13 Cont ID  
Sent By jgomez Date 2010-05-13 Time 13:54 Rev Time 0.00
Received By jgomez Date 2010-05-13 Time 13:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-03-31 Cont ID  
Sent By jgomez Date 2010-03-31 Time 17:12 Rev Time 0.00
Received By jgomez Date 2010-03-31 Time 17:12 Sent To  
Notes
2010-03-31 17:23:17RESIDENTIAL (R3) MECHANICAL REVIEW.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ARCHITECT SHOWN ON THE A/C PLAN NEED TO SIGN AND
 SEAL THE DRAWING WITH ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 481 FLORIDA STATUTES. COPY IS NOT
 ALLOWED.
  
 2- PROVIDE 2 COPIES OF A/C PLANS ONLY ONE WAS PROVIDED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-05-13 Cont ID  
Sent By jgomez Date 2010-05-13 Time 14:06 Rev Time 0.00
Received By jgomez Date 2010-05-13 Time 14:06 Sent To  
Notes
2010-05-13 14:08:04PLUMBING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE PLUMBING RISER DIAGRAM:
 A) MISSING THE BATHROOM SHOWERS.
 B) REVISE WATER CLOSET DRAIN SIZE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-03-31 Cont ID  
Sent By jgomez Date 2010-03-31 Time 17:23 Rev Time 0.00
Received By jgomez Date 2010-03-31 Time 17:23 Sent To  
Notes
2010-03-31 17:26:12RESIDENTIAL (R3) PLUMBING REVIEW.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE SANITARY ISOMETRIC RISER DIAGRAM AS REQUIRED
 BY SEC. 106.3.5.4(9) OF CITY AMENDMENTS TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 2 Status P Date 2010-05-19 Cont ID  
Sent By astelly Date 2010-05-19 Time 16:20 Rev Time 0.00
Received By astelly Date 2010-05-19 Time 16:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-04-07 Cont ID  
Sent By astelly Date 2010-04-07 Time 11:50 Rev Time 0.00
Received By astelly Date 2010-04-07 Time 11:50 Sent To  
Notes
2010-04-07 12:17:05AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PURSUANT TO SEC. 94-74 (A)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, THE PROPERTY MUST MEET THE
 FOLLOWING CONDITIONS:
  
 MINIMUM LOT DIMENSIONS FOR SINGLE-FAMILY USE WITH
 ACCESSORY APARTMENT.
 A.
 LOT AREA: 6,000 FEET;
 B.
 LOT WIDTH: 60 FEET;
 THE APPLICANT MAY APPLY TO THE ZONING BOARD OF APPEALS
 FOR A VARIANCE REGARDING THE MINIMUM LOT WIDTH.
  
 THE AREA OF THE PROPOSED CONCRETE PATIO AHOWN ON THE
 SITE PLAN DOES NOT MATCH THE AREA SHOWN ON THE SURVEY.
  
  
  