Plan Review Details - Permit 10030329
Plan Review Stops For Permit 10030329
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-03-17 Cont ID  
Sent By shill Date 2010-03-17 Time 15:01 Rev Time 0.00
Received By shill Date 2010-03-17 Time 15:01 Sent To  
Notes
2010-03-17 15:11:17***PROVISO***
  
 ***ISSUED AT CONTRACTOR'S RISK****
  
 1. THIS PARCEL IS LOCATED IN EXPOSURE C. REVISE DESIGN
 PRESSURES ACCORDINGLY R301.2.1.4.
  
 2. THE INSTALLATION SCHEDULE "SHUTTER MOUNTING
 CONNECTION TYPE" SHOULD STATE WHICH CONNECTION TYPE IS
 PROPOSED - SEE PAGE 14A (EXAMPLE: WALL MOUNTING DETAIL
 1)
  
 3. PROVIDE REVISED INSTALLATION SCHEDULE AT INSPECTION
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-17 Cont ID  
Sent By shill Date 2010-03-17 Time 15:11 Rev Time 0.00
Received By shill Date 2010-03-15 Time 11:21 Sent To  
Notes
2010-03-15 11:21:57SENT TO MISC. BOX #1.