Plan Review Stops For Permit 10030288 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
N |
Date |
2010-05-12 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-05-12 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-05-12 |
Time |
15:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-03-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2010-03-24 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2010-03-24 |
Time |
15:53 |
Sent To |
|
|
Notes |
2010-03-24 16:18:37 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) THE SCOPE OF WORK ON THE PERMIT APPLICATION ONLY | | INDICATES ELECTRICAL WORK. HOWEVER, THE PLANS THAT WERE | | SUBMITTED SHOWS OTHER WORK, SUCH AS INSTALLING METAL | | SHUTTERS AND NEW CONCRETE PARKING. PLEASE CLARIFY AND | | CROSS OUT ALL WORK THAT IS NOT PART OF THIS PERMIT. | | | | 2) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE METAL | | SHUTTERS AND NEW WINDOWS AS REQUIRED BY DCA RULE 9B-72. | | | | 3) THE VALUE OF FOR THE WORK SPECIFIED ON THE | | APPLICATION IS TOO LOW FOR THE SCOPE OF WORK SHOWN ON | | THE PLANS. PLEASE INCREASE THE VALUE TO INCLUDE | | MATERIAL, LABOR COST OVERHEAD AND PROFIT PER CITY | | AMENDMENTS TO FBC 108.3. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2010-05-11 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-05-11 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-05-11 |
Time |
15:29 |
Sent To |
|
|
Notes |
2010-05-11 15:52:15 | ELECTRIC ONLY PERMIT TO CONTRACTOR./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2010-03-16 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-03-16 |
Time |
12:31 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-03-16 |
Time |
12:11 |
Sent To |
I |
|
Notes |
2010-03-16 12:24:41 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | SIZE AND TYPE, GROUNDING DETAILS,AND LOAD CALCULATIONS, | | PER 215.5 NEC, 106.3.5.4 FBC. | | | | 2} AN ELECTRICAL CONTRACTOR MUST APPLY FOR AN | | ELECTRICAL PERMIT PER CHAPTER 489 FS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | | FAX/:561/805-6676 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
N |
Date |
2010-05-12 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-05-12 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-05-12 |
Time |
15:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
F |
Date |
2010-03-29 |
|
|
Cont ID |
|
Sent By |
jpapa |
Date |
2010-03-29 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
jpapa |
Date |
2010-03-29 |
Time |
15:25 |
Sent To |
|
|
Notes |
2010-03-29 15:29:43 | THE WINDOW ON THE SOUTH ELEVATION, IMMEDIATELY ADJACENT | | TO THE DOOR, SHALL MATCH SIZE AND ORIENTATION OF THE | | OTHER SINGLE-HUNG WINDOWS. THE ENTRY DOOR SHALL HAVE A | | PENT ROOF ABOVE PER THE CRA GRANT APPLICATION APPROVED | | SCOPE OF WORK. | | | | FOR MORE INFORMATION, CONTACT FRIEDERIKE MITTNER, CITY | | HISTORIC PRESERVATION PLANNER, AT (561)822-1457. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-05-04 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-05-04 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2010-05-04 |
Time |
14:46 |
Sent To |
|
|
Notes |
2010-05-04 14:46:59 | IN ZONING FOR HISTORICAL ONLY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-03-16 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-03-16 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-03-15 |
Time |
16:30 |
Sent To |
PC |
|
Notes |
2010-05-12 15:16:22 | THIS IS AN ELECTRICAL PERMIT ONLY, BUILDING TO BE | | APPLIED FOR SEPARATELY./WRT. | 2010-03-15 16:32:01 | R4 | | |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
2 |
Status |
N |
Date |
2010-05-12 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-05-12 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-05-12 |
Time |
15:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
F |
Date |
2010-03-26 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2010-03-26 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2010-03-26 |
Time |
16:53 |
Sent To |
|
|
Notes |
2010-03-26 17:14:40 | ***LANDSCAPE REVIEW FAILED*** | | | | PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN | | FORMAT. | | | | 1. THIS IS AN ELECTRICAL PERMIT BUT OTHER ITEMS ARE | | SHOWN ON THIS PLAN WHICH CHANGES THE SCOPE OF WORK. | | SEPARATE PERMITS ARE REQUIRED FOR DEMOLITION | | LANDSCAPING, PAVING AND IRRIGATION. | | | | 2. THE LANDSCAPE PLAN SHALL BE SIGNED AND SEALED BY A | | REGISTERED LANDSCAPE ARCHITECT AND SHALL COMPLY WITH | | THE REQUIREMENTS IN ARTICLE XIV OF THE ZONING AND LAND | | DEVELOPMENT REGULATIONS. IDENTIFY ALL EXISTING AND | | PROPOSED TREES, SHRUBS AND GROUND COVER. | | | | 3. A HEDGE AND A SHADE OR FLOWERING TREE SHALL | | TERMINATE BOTH ENDS OF THE REAR PARKING ROW. THE | | PROPOSED HEDGE ALONG 8TH STREET SHALL BE PLANTED ALONG | | THE FOUNDATION OF THE BUILDING WITH GROUND COVER AND/OR | | SOD BETWEEN THE HEDGE AND THE CITY SIDEWALK. | | | | 4. PROVIDE SOD AND IRRIGATION IN THE RIGHT-OF-WAY, | | ADJACENT TO 8TH STREET. | | | | 5. AN ADDITIONAL PARKING STALL SHOULD BE ADDED IF THERE | | ARE TWO (2) UNITS IN THIS BUILDING | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | KUSSNER @ (561) 822-1462 | | | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2010-05-07 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-05-06 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2010-05-05 |
Time |
15:32 |
Sent To |
E |
|
Notes |
2010-05-07 14:17:30 | HISTORICAL APPROVED SEE PLANS |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2010-03-26 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2010-03-26 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2010-03-26 |
Time |
14:24 |
Sent To |
|
|
Notes |
2010-03-26 14:33:56 | 1. A 5 FEET LANDSCAPE BUFFER SHALL BE PROVIDED AROUND | | THE NEW PARKING AREA. | | 2. PARKING SPACES SHALL BE STRIPED ACCORDING TO CITY | | DETAIL IN SECTION 94-485 OF THE ZONING CODE. | | 3. HISTORIC PRESERVATION REVIEW AND APPROVAL IS | | REQUIRED TO PROCEED WITH PERMIT. | | 4. HEDGE PROPOSED ALONG THE PROPERTY LINE SHALL BE | | RELOCATED AS FOUNDATION PLANTING NEXT TO THE BUILDING. | | 5. IRRIGATION SHALL BE PROVIDED ON GRASSED AREA. |
|
|