Plan Review Details - Permit 10030238
Plan Review Stops For Permit 10030238
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-04-14 Cont ID  
Sent By shill Date 2010-04-14 Time 15:15 Rev Time 0.00
Received By shill Date 2010-04-14 Time 15:15 Sent To  
Notes
2010-04-14 15:16:13REVIEW DOES NOT INCLUDE ELECTRIC - PLANS & PERMIT
 APPLICATION REQUIRED
 PERMIT REQUIRED PRIOR TO COMMENCEMENT OF ANY ELECTRIC
 WORK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-03-30 Cont ID  
Sent By shill Date 2010-03-30 Time 17:45 Rev Time 0.00
Received By shill Date 2010-03-30 Time 17:45 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-03-29 Cont ID  
Sent By shill Date 2010-03-29 Time 13:02 Rev Time 0.00
Received By shill Date 2010-03-29 Time 12:13 Sent To  
Notes
2010-03-29 13:06:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE FIRE COMMENTS. PLEASE CLARIFY LEVEL OF
 ALTERATION FBC EB401.4. SEE ALSO FBC EB704.2.4, FBC
 804.2.2.
  
 2. USE OF DINING AREA 3 NOT CLEAR. SEE FBC TABLE
 1004.1.1, ASSEMBLY STANDING SPACE IS 5 SF NET. PLEASE
 CLARIFY USE OF SPACE AND OCCUPANT LOAD.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 13:12 Rev Time 0.00
Received By shill Date 2010-03-16 Time 13:12 Sent To  
Notes
2010-03-16 13:33:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE REVISE PLAN TO INCLUDE OCCUPANT LOAD BASED ON
 NEW SEATING PLAN FBC1004.
  
 2. SHOW LIFE SAFETY INFORMATION; EXIT ACCESS TRAVEL
 DISTANCE, REQUIRED WIDTH FOR EXITS BASED ON NEW
 OCCUPANT LOAD, FBC 10.
  
 3. PROVIDE A DETAIL FOR ACCESSIBLE SEATING AND SHOW
 COMPLIANCE WITH FBC11-5.1 (5%), FBC11-4.32. NO
 DIMENSIONS PROVIDED ON THE PLAN. FOR FIXED SEATING, SEE
 FBC11-4.32 AND SHOW CLEAR FLOOR SPACE, AISLE WIDTH,
 KNEE CLEARANCE, HEIGHT.
  
 4. FBC11-5.2, A "HANDICAP BAR" IS SHOWN ON THE PLAN,
 FBC11-4.32.4, BAR IS SHOWN AT 36", MAX 34" PERMITTED.
 PLEASE REVISE.
  
 5. BOND BREAK REQUIRED FOR STUCCO OVER WOOD SHEATHING
 FBC1404.2.1.
  
 6. PLAN IS NOT CLEAR. IS THE "VESTIBULE" (ENTRY TOWER)
 EXISTING INTERIOR SPACE? PLAN STATES THAT THE ENTRY IS
 TO RECEIVE A "NEW CEMENTITIOUS FINISH" OVER EXISTING
 PLYWOOD. PLAN ALSO STATES "PROVIDE STUCCO FINISH ON
 HIGH RIB LATH OVER NEW SOFFIT" BUT NO DETAIL/WIND
 DESIGN CRITERIA PROVIDED FOR THE "NEW SOFFIT," FBC1609,
 FBC*106. EXISTING CONDITIONS NOT CLEAR. FBC*106.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2010-03-15 Cont ID  
Sent By shill Date 2010-03-15 Time 08:31 Rev Time 0.00
Received By shill Date 2010-03-15 Time 08:31 Sent To  
Notes
2010-03-15 08:31:38PER BT/LM, ELECTRIC PLANS TO BE SUBMITTED WITH ELECTRIC
 PERMIT APPLICATION
 ELECTRIC PERMIT REQUIRED PRIOR TO ANY ELECTRIC WORK
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-03-10 Cont ID  
Sent By dpalmer Date 2010-03-10 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2010-03-10 Time 12:27 Sent To  
Notes
2010-03-10 12:27:27** DENIED **
  
  
 1) NOTE: PERMIT APPLICATION STATES RELOCATION OF LIGHTS
 HOWEVER NO PLANS SHOWING PROPOSED ELECTRICAL WORK WAS
 SUBMITTED. PLEASE SUBMIT.
  
 PLEASE SUBMIT COMPLETED PLANS. PLEASE CALL IF THERE ARE
 ANY QUESTIONS OR IF COMMENTS ARE NOT TYPED IN A CLEAR
 MANNER.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 HOURS: MONDAY THROUGH THURSDAY 8AM TO 5PM.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2010-04-14 Cont ID  
Sent By mawillia Date 2010-04-14 Time 14:03 Rev Time 0.00
Received By mawillia Date 2010-04-14 Time 13:43 Sent To  
Notes
2010-04-14 14:03:05*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVEWS HAVE BEEN
 ADDRESSED; PLAN SHEET A-101 STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2010-03-31 Cont ID  
Sent By shill Date 2010-03-31 Time 08:20 Rev Time 0.00
Received By shill Date 2010-04-05 Time 08:20 Sent To  
Notes
2010-04-05 08:21:45PER CHIEF CARSILLO, PLEASE SEE PREVIOUS COMMENTS (NOT
 ADDRESSED). MC CALLED CONTRACTOR TO DISCUSS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-03-26 Cont ID  
Sent By mawillia Date 2010-03-26 Time 18:19 Rev Time 0.00
Received By mawillia Date 2010-03-26 Time 14:47 Sent To  
Notes
2010-03-26 14:54:40*****DENIED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED HOWEVER, BASED ON THE NEW INFORMATION
 SUBMITTED, ADDRESS THE FOLLOWING COMMENTS AS REFERENCED
 IN NFPA 101, LIFE SAFETY CODE, FLORIDA 2007 EDITION:
  
 1. PLEASE EXPLAIN THE INCREASE IN OCCUPANT LOAD FIRST
 SUBMITTED AT 218 IS NOW LISTED AS 336 PERSONS. BE
 ADVISED THAT: IN BOTH NEW ASSEMBLY OCCUPANCIES (CHAPTER
 12 - 12.3.4.1) AND EXISTING ASSEMBLY OCCUPANCIES
 (CHAPTER 13 - 13.3.4.1) WITH OCCUPANT LOADS MORE THAN
 300, THE OCCUPANCY SHALL BE PROVIDED WITH AN APPROVED
 FIRE ALARM SYSTEM, UNLESS OTHERWISE PERMITTED BY
 CERTAIN CRITERIA.
  
 2. THE RESUBMITTED PLAN NOW REFERS TO DINING AREA 3 AS
 LOUNGE/DANCE 70 SEATS (LOAD 115 PERSONS) SHOWING A DJ
 BOOTH IN THE SOUTH CORNER OF THE ROOM. BE ADVISED THAT:
 WHERE THE OCCUPANT LOAD EXCEEDS 100 (NEW ASSEMBLY,
 CHAPTER 12 - 12.3.5.1) OR WHERE THE OCCUPANT LOAD
 EXCEEDS 300 (EXISTING ASSEMBLY - 13.3.5.1), THE
 FOLLOWING ASSEMBLY OCCUPANTS SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM: (1) DANCE HALLS (2) DISCOTHEQUES (3)
 NIGHTCLUBS OR SIMILAR USAGE (4) ASSEMBLY OCCUPANCIES
 WITH FESTIVAL SEATING
  
 3. ASSEMBLY OCCUPANCIES SHALL BE PROVIDED WITH A
 MINIMUM OF ONE TRAINED CROWD MANAGER OR CROWD MANAGER
 SUPERVISOR. WHERE THE OCCUPANT LOAD EXCEED 250,
 ADDITIONAL TRAINED CROWD MANAGERS OR CROWD MANAGER
 SUPERVISORS SHALL BE PROVIDED AT A RATIO OF 1 FOR EVERY
 250 OCCUPANTS, UNLESS OTHERWISE PERMITTED AS PER
 12.7.6.1 OF NFPA 101 - LIFE SAFETY CODE. THE CROWD
 MANAGER SHALL RECEIVE APPROVED TRAINNG IN CROWD CONTROL
 MANAGEMENT TECHNIQUES.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
 OR
  
 BATTALION CHIEF MIKE CARSILLO
 FIRE MARSHAL - FIRE PREVENTION BUREAU
 561-804-4709
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-16 Cont ID  
Sent By mawillia Date 2010-03-16 Time 10:55 Rev Time 0.00
Received By mawillia Date 2010-03-16 Time 10:14 Sent To  
Notes
2010-03-16 10:55:28*****DENIED*****
  
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET AS PER WEST PALM BEACH
 AMENDMENT 106.1.3 AND FLORIDA ADMINISTRATIVE CODE
 61G1-16.004(3).
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS TO COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 3. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 WHICH IS BASED ON NFPA 101, LIFE SAFETY CODE, 2006
 EDITION AND NFPA 1, UNIFORM FIRE PREVENTION CODE, 2006
 EDITION SHALL BE REFERENCED.
  
 4. PLAN DOES NOT INDICATE IF THE BUILDING HAS A FIRE
 ALARM AND/OR FIRE SPRINKLER SYSTEM. PLEASE INDICATE IF
 THE SCOPE OF WORK HAS CAUSE FOR THIS/THESE SYSTEM(S) TO
 BE REMODELED.
  
 5. SHOW THE LOCATION OF ALL EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHERS APPLICABLE TO THIS
 BUILDING.
  
 6. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALL/PARTITION IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-04-12 Cont ID  
Sent By jgomez Date 2010-04-12 Time 15:39 Rev Time 0.00
Received By jgomez Date 2010-04-12 Time 15:39 Sent To  
Notes
2010-04-13 15:39:52************EXPEDITED***************
2010-04-12 15:40:08SENT TO B-13.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-30 Cont ID  
Sent By shill Date 2010-03-30 Time 17:46 Rev Time 0.00
Received By shill Date 2010-03-30 Time 17:46 Sent To  
Notes
2010-03-30 17:46:26ROUTED TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-25 Cont ID  
Sent By lmartine Date 2010-03-25 Time 16:21 Rev Time 0.00
Received By lmartine Date 2010-03-25 Time 16:21 Sent To  
Notes
2010-03-25 16:23:13****************EXPEDITED****************
 2ND RUN
 B--9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 13:41 Rev Time  
Received By shill Date   Time   Sent To  
Notes
2010-03-09 16:06:32C--20
 *********************EXPEDITED************************

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2010-03-30 Cont ID  
Sent By shill Date 2010-03-30 Time 09:28 Rev Time 0.00
Received By shill Date 2010-03-30 Time 09:28 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 13:39 Rev Time 0.00
Received By shill Date 2010-03-16 Time 13:39 Sent To  
Notes
2010-03-16 13:40:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE CLARIFY THAT "VESTIBULE" IS EXISTING ENCLOSED
 UNDER AIR SPACE. IF IT IS NOT, PLEASE PROVIDE EXISTING
 SQUARE FOOT AREA AND PROPOSED NEW.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-03-30 Cont ID  
Sent By shill Date 2010-03-30 Time 09:27 Rev Time 0.00
Received By shill Date 2010-03-30 Time 09:27 Sent To  
Notes
2010-03-30 09:27:53N PER H MOSER
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-03-11 Cont ID  
Sent By kdfreema Date 2010-03-11 Time 13:26 Rev Time 0.00
Received By kdfreema Date 2010-03-11 Time 13:26 Sent To  
Notes
***NONE***