Plan Review Stops For Permit 10030238 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2010-04-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-04-14 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-04-14 |
Time |
15:15 |
Sent To |
|
|
Notes |
2010-04-14 15:16:13 | REVIEW DOES NOT INCLUDE ELECTRIC - PLANS & PERMIT | | APPLICATION REQUIRED | | PERMIT REQUIRED PRIOR TO COMMENCEMENT OF ANY ELECTRIC | | WORK |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2010-03-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-30 |
Time |
17:45 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-30 |
Time |
17:45 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2010-03-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-29 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-29 |
Time |
12:13 |
Sent To |
|
|
Notes |
2010-03-29 13:06:46 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. SEE FIRE COMMENTS. PLEASE CLARIFY LEVEL OF | | ALTERATION FBC EB401.4. SEE ALSO FBC EB704.2.4, FBC | | 804.2.2. | | | | 2. USE OF DINING AREA 3 NOT CLEAR. SEE FBC TABLE | | 1004.1.1, ASSEMBLY STANDING SPACE IS 5 SF NET. PLEASE | | CLARIFY USE OF SPACE AND OCCUPANT LOAD. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-03-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-16 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-16 |
Time |
13:12 |
Sent To |
|
|
Notes |
2010-03-16 13:33:23 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. PLEASE REVISE PLAN TO INCLUDE OCCUPANT LOAD BASED ON | | NEW SEATING PLAN FBC1004. | | | | 2. SHOW LIFE SAFETY INFORMATION; EXIT ACCESS TRAVEL | | DISTANCE, REQUIRED WIDTH FOR EXITS BASED ON NEW | | OCCUPANT LOAD, FBC 10. | | | | 3. PROVIDE A DETAIL FOR ACCESSIBLE SEATING AND SHOW | | COMPLIANCE WITH FBC11-5.1 (5%), FBC11-4.32. NO | | DIMENSIONS PROVIDED ON THE PLAN. FOR FIXED SEATING, SEE | | FBC11-4.32 AND SHOW CLEAR FLOOR SPACE, AISLE WIDTH, | | KNEE CLEARANCE, HEIGHT. | | | | 4. FBC11-5.2, A "HANDICAP BAR" IS SHOWN ON THE PLAN, | | FBC11-4.32.4, BAR IS SHOWN AT 36", MAX 34" PERMITTED. | | PLEASE REVISE. | | | | 5. BOND BREAK REQUIRED FOR STUCCO OVER WOOD SHEATHING | | FBC1404.2.1. | | | | 6. PLAN IS NOT CLEAR. IS THE "VESTIBULE" (ENTRY TOWER) | | EXISTING INTERIOR SPACE? PLAN STATES THAT THE ENTRY IS | | TO RECEIVE A "NEW CEMENTITIOUS FINISH" OVER EXISTING | | PLYWOOD. PLAN ALSO STATES "PROVIDE STUCCO FINISH ON | | HIGH RIB LATH OVER NEW SOFFIT" BUT NO DETAIL/WIND | | DESIGN CRITERIA PROVIDED FOR THE "NEW SOFFIT," FBC1609, | | FBC*106. EXISTING CONDITIONS NOT CLEAR. FBC*106. | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2010-03-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-15 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-15 |
Time |
08:31 |
Sent To |
|
|
Notes |
2010-03-15 08:31:38 | PER BT/LM, ELECTRIC PLANS TO BE SUBMITTED WITH ELECTRIC | | PERMIT APPLICATION | | ELECTRIC PERMIT REQUIRED PRIOR TO ANY ELECTRIC WORK | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2010-03-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2010-03-10 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2010-03-10 |
Time |
12:27 |
Sent To |
|
|
Notes |
2010-03-10 12:27:27 | ** DENIED ** | | | | | | 1) NOTE: PERMIT APPLICATION STATES RELOCATION OF LIGHTS | | HOWEVER NO PLANS SHOWING PROPOSED ELECTRICAL WORK WAS | | SUBMITTED. PLEASE SUBMIT. | | | | PLEASE SUBMIT COMPLETED PLANS. PLEASE CALL IF THERE ARE | | ANY QUESTIONS OR IF COMMENTS ARE NOT TYPED IN A CLEAR | | MANNER. | | | | DEWEY PALMER | | ELECTRICAL PLANS EXAMINER II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | HOURS: MONDAY THROUGH THURSDAY 8AM TO 5PM. | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2010-04-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2010-04-14 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2010-04-14 |
Time |
13:43 |
Sent To |
|
|
Notes |
2010-04-14 14:03:05 | *****APPROVED***** | | | | THE COMMENTS FROM THE PREVIOUS PLAN REVEWS HAVE BEEN | | ADDRESSED; PLAN SHEET A-101 STAMPED, INITIALED, AND | | DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2010-03-31 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-31 |
Time |
08:20 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-04-05 |
Time |
08:20 |
Sent To |
|
|
Notes |
2010-04-05 08:21:45 | PER CHIEF CARSILLO, PLEASE SEE PREVIOUS COMMENTS (NOT | | ADDRESSED). MC CALLED CONTRACTOR TO DISCUSS. | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2010-03-26 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2010-03-26 |
Time |
18:19 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2010-03-26 |
Time |
14:47 |
Sent To |
|
|
Notes |
2010-03-26 14:54:40 | *****DENIED***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED HOWEVER, BASED ON THE NEW INFORMATION | | SUBMITTED, ADDRESS THE FOLLOWING COMMENTS AS REFERENCED | | IN NFPA 101, LIFE SAFETY CODE, FLORIDA 2007 EDITION: | | | | 1. PLEASE EXPLAIN THE INCREASE IN OCCUPANT LOAD FIRST | | SUBMITTED AT 218 IS NOW LISTED AS 336 PERSONS. BE | | ADVISED THAT: IN BOTH NEW ASSEMBLY OCCUPANCIES (CHAPTER | | 12 - 12.3.4.1) AND EXISTING ASSEMBLY OCCUPANCIES | | (CHAPTER 13 - 13.3.4.1) WITH OCCUPANT LOADS MORE THAN | | 300, THE OCCUPANCY SHALL BE PROVIDED WITH AN APPROVED | | FIRE ALARM SYSTEM, UNLESS OTHERWISE PERMITTED BY | | CERTAIN CRITERIA. | | | | 2. THE RESUBMITTED PLAN NOW REFERS TO DINING AREA 3 AS | | LOUNGE/DANCE 70 SEATS (LOAD 115 PERSONS) SHOWING A DJ | | BOOTH IN THE SOUTH CORNER OF THE ROOM. BE ADVISED THAT: | | WHERE THE OCCUPANT LOAD EXCEEDS 100 (NEW ASSEMBLY, | | CHAPTER 12 - 12.3.5.1) OR WHERE THE OCCUPANT LOAD | | EXCEEDS 300 (EXISTING ASSEMBLY - 13.3.5.1), THE | | FOLLOWING ASSEMBLY OCCUPANTS SHALL BE PROTECTED | | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC | | SPRINKLER SYSTEM: (1) DANCE HALLS (2) DISCOTHEQUES (3) | | NIGHTCLUBS OR SIMILAR USAGE (4) ASSEMBLY OCCUPANCIES | | WITH FESTIVAL SEATING | | | | 3. ASSEMBLY OCCUPANCIES SHALL BE PROVIDED WITH A | | MINIMUM OF ONE TRAINED CROWD MANAGER OR CROWD MANAGER | | SUPERVISOR. WHERE THE OCCUPANT LOAD EXCEED 250, | | ADDITIONAL TRAINED CROWD MANAGERS OR CROWD MANAGER | | SUPERVISORS SHALL BE PROVIDED AT A RATIO OF 1 FOR EVERY | | 250 OCCUPANTS, UNLESS OTHERWISE PERMITTED AS PER | | 12.7.6.1 OF NFPA 101 - LIFE SAFETY CODE. THE CROWD | | MANAGER SHALL RECEIVE APPROVED TRAINNG IN CROWD CONTROL | | MANAGEMENT TECHNIQUES. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | OR | | | | BATTALION CHIEF MIKE CARSILLO | | FIRE MARSHAL - FIRE PREVENTION BUREAU | | 561-804-4709 | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2010-03-16 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2010-03-16 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2010-03-16 |
Time |
10:14 |
Sent To |
|
|
Notes |
2010-03-16 10:55:28 | *****DENIED***** | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | OF EACH SUBMITTED PLAN SHEET AS PER WEST PALM BEACH | | AMENDMENT 106.1.3 AND FLORIDA ADMINISTRATIVE CODE | | 61G1-16.004(3). | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS TO COMPLY WITH NFPA 241 - 2004 | | EDITION. | | | | 3. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE | | WHICH IS BASED ON NFPA 101, LIFE SAFETY CODE, 2006 | | EDITION AND NFPA 1, UNIFORM FIRE PREVENTION CODE, 2006 | | EDITION SHALL BE REFERENCED. | | | | 4. PLAN DOES NOT INDICATE IF THE BUILDING HAS A FIRE | | ALARM AND/OR FIRE SPRINKLER SYSTEM. PLEASE INDICATE IF | | THE SCOPE OF WORK HAS CAUSE FOR THIS/THESE SYSTEM(S) TO | | BE REMODELED. | | | | 5. SHOW THE LOCATION OF ALL EXIT LIGHTS, EMERGENCY | | LIGHTS, AND FIRE EXTINGUISHERS APPLICABLE TO THIS | | BUILDING. | | | | 6. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW | | WALL/PARTITION IN TERMS OF CLASS A, CLASS B, OR CLASS | | C. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2010-04-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-04-12 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-04-12 |
Time |
15:39 |
Sent To |
|
|
Notes |
2010-04-13 15:39:52 | ************EXPEDITED*************** | 2010-04-12 15:40:08 | SENT TO B-13. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2010-03-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-30 |
Time |
17:46 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-30 |
Time |
17:46 |
Sent To |
|
|
Notes |
2010-03-30 17:46:26 | ROUTED TO FIRE | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-03-25 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-03-25 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2010-03-25 |
Time |
16:21 |
Sent To |
|
|
Notes |
2010-03-25 16:23:13 | ****************EXPEDITED**************** | | 2ND RUN | | B--9 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-03-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-16 |
Time |
13:41 |
Rev Time |
|
Received By |
shill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2010-03-09 16:06:32 | C--20 | | *********************EXPEDITED************************ |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
N |
Date |
2010-03-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-30 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-30 |
Time |
09:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2010-03-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-16 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-16 |
Time |
13:39 |
Sent To |
|
|
Notes |
2010-03-16 13:40:58 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. PLEASE CLARIFY THAT "VESTIBULE" IS EXISTING ENCLOSED | | UNDER AIR SPACE. IF IT IS NOT, PLEASE PROVIDE EXISTING | | SQUARE FOOT AREA AND PROPOSED NEW. | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2010-03-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-30 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-30 |
Time |
09:27 |
Sent To |
|
|
Notes |
2010-03-30 09:27:53 | N PER H MOSER | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2010-03-11 |
|
|
Cont ID |
|
Sent By |
kdfreema |
Date |
2010-03-11 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
kdfreema |
Date |
2010-03-11 |
Time |
13:26 |
Sent To |
|
|
Notes |
|
|