Plan Review Details - Permit 10030180
Plan Review Stops For Permit 10030180
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-04-28 Cont ID  
Sent By dwise Date 2010-04-28 Time 19:32 Rev Time 0.00
Received By dwise Date 2010-04-28 Time 19:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-24 Cont ID  
Sent By jwitmer Date 2010-03-24 Time 13:27 Rev Time 0.66
Received By jwitmer Date 2010-03-24 Time 13:27 Sent To  
Notes
2010-03-24 14:14:07BUILDING PLAN REVIEW
 PERMIT: 10030180
 ADD: 3700 S DIXIE HWY
 CONT: MTC REMODELING, INC
 TEL: (561)719-0725
  
 DESIGNER: WILLIAM WATERS AA
 PHONE: 561-307-5152
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS A3 INDICATE THE INSTALATION OF TWO NEW
 EXTERIOR EXIT DOORS. PLANS FAIL TO PROVIDE THE WIND
 DESIGN CRITERIA FOR THIS LOCATION.1603.1.4 WIND DESIGN
 DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.1 BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 1.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 1.3 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 1.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
  
 1.5 COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. 2007 FBC & 2007 EXISTING BUILDING CODE,
 CHAPTER 7, LEVEL 2 ALTERATIONS AND CHAPTER 9 CHANGE OF
 OCCUPANCY.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5
 TABLE 503.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 E) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
  
 3) SHEET A-3 DOOR# 101& 102. EXISSTING BILDING CODE
 606.4 REPLACEMENT OF WINDOWS AND DOORS. THE REPLACEMENT
 OF GARAGE DOORS, EXTERIOR DOORS, SKYLIGHTS, OPERATIVE
 AND INOPERATIVE WINDOWS SHALL BE DESIGNED AND
 CONSTRUCTED TO COMPLY WITH CHAPTER 16 OF THE FLORIDA
 BUILDING CODE, BUILDING .
 FBC-B 1609.1.2 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, GLAZING IN BUILDINGS SHALL BE IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE DOORS
 AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND 203
 OR AAMA 506 REFERENCED THEREIN AS FOLLOWS:
 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9144 MM) OF
 GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST.
  
 THE PRODUCT APPROVALS SUBMITTED INDICATE THEY DO NOT
 HAVE LARGE MISSILE IMPACT TESTING, STORM SHUTTERS OR
 PANELS HAVING BEEN TESTED FOR LARGE MISSILE IMPACT
 RATINGWOULD BE REQUIRED IF THESE APPROVALS ARE TO BE
 INCLUDED WWITHIN THIS PERMIT.
  
 4) RESTROOMS A-5 INDICATES THE RESTROOM WALLS ARE TO BE
 PAINTED, PLEASE REVIEW FBC-B 1210.2.
  
 5) A-5 FINISH SCHEDULE HAS NO INFORMATION FOR
 COMPLIANCE WITH : 803.1 GENERAL. INTERIOR WALL AND
 CEILING FINISHES SHALL BE CLASSIFIED IN ACCORDANCE WITH
 ASTM E 84. SUCH INTERIOR FINISH MATERIALS SHALL BE
 GROUPED IN THE FOLLOWING CLASSES IN ACCORDANCE WITH
 THEIR FLAME SPREAD AND SMOKE-DEVELOPED INDEXES.
  
 CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450.
  
 CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450.
  
 CLASS C: FLAME SPREAD 76-200; SMOKE-DEVELOPED 0-450.
 TABLE 803.5.
  
 6) A-5 DOOR SCHEDULE DOOR 101 & 102 ARE INDICATED AS 44
 INCHES WIDE. PLEASE REVIEW THE NOA 05-1012.05 SHEET 1
 OF 9 INDICATES THE MAXIMUM DOOR WIDTH OF 36".
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 7) A3 NOTES DEALING WITH ROOM 102 DESERTS IS NOT CLEAR
 IF THIS AREA IS FOR THE PUBLIC AS A SERVICE LINE OR
 WILL THIS BE FOR THE EMPLOYEES ONLY. 11-5.5FOOD SERVICE
 LINES SHALL HAVE A MINIMUM CLEAR WIDTH OF 36 INCHES
 (915 MM), WITH A PREFERRED CLEAR WIDTH OF 42 INCHES
 (1065 MM) TO ALLOW PASSAGE AROUND A PERSON USING A
 WHEELCHAIR. TRAY SLIDES SHALL BE MOUNTED NO HIGHER THAN
 34 INCHES (865 MM) ABOVE THE FLOOR (SEE FIGURE 53). IF
 SELF-SERVICE SHELVES ARE PROVIDED, AT LEAST 50 PERCENT
 OF EACH TYPE MUST BE WITHIN REACH RANGES SPECIFIED IN
 SECTIONS 11-4.2.5 AND 11-4.2.6.
  
 11-5.6 TABLEWARE AND CONDIMENT AREAS. SELF-SERVICE
 SHELVES AND DISPENSING DEVICES FOR TABLEWARE, DISHWARE,
 CONDIMENTS, FOOD AND BEVERAGES SHALL BE INSTALLED TO
 COMPLY WITH SECTION 11-4.2 (SEE FIGURE 54).
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-28 Cont ID  
Sent By dwise Date 2010-04-28 Time 19:32 Rev Time 0.00
Received By dwise Date 2010-04-28 Time 19:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-04-16 Cont ID  
Sent By btrobaug Date 2010-04-16 Time 08:37 Rev Time 0.00
Received By btrobaug Date 2010-04-16 Time 07:11 Sent To I
Notes
2010-04-16 07:45:42THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 (F)(4) NEC . INDICATE
 SAME ON PLANS.
  
 2} THERE IS A CONFLICT IN LOCATION FOR PANEL "A" ON
 SHEETS E-1 & E-2, CLARIFY THE INTENDED LOCATION.106.1.1
 FBC AS AMENDED.
  
 3} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2007 FBC, 2008 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.
 SEE SPECIFICATIONS ON SHEET E-2
  
 4} INDICATE COMPLIANCE WITH CHAPTER 13 OF THE FLORIDA
 BLDG CODE. 13.415. SHOW TIME CLOCK AND OCCUPANCY
 SENSORS LOCATIONS ON THE PLAN. THIS CAN BE DEMONSTRATED
 ON THE PLANS INDICATING THE WATTAGES OF THE LUMINAIRES
 CHOSEN FOR THE PROJECT CONFORM TO THE DENSITY
 REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE SCHEDULE
 TO CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
 5} 210.62 SHOW WINDOWS.
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED
 WITHIN 450 MM (18 IN.) OF THE TOP OF A SHOW WINDOW FOR
 EACH 3.7 LINEAR M (12 LINEAR FT) OR MAJOR FRACTION
 THEREOF OF SHOW WINDOW AREA MEASURED HORIZONTALLY AT
 ITS MAXIMUM WIDTH. INDICATE LOCATION AND ON PANEL
 SCHEDULE.
  
 6} PER 220.14 (G) SHOW WINDOWS. SHOW WINDOWS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER OF THE FOLLOWING:
 (1) THE UNIT LOAD PER OUTLET AS REQUIRED IN OTHER
 PROVISIONS OF THIS SECTION
 (2) AT 200 VOLT-AMPERES PER 300 MM (1 FT) OF SHOW
 WINDOW
  
 7} 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION.
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-04-29 Cont ID  
Sent By mawillia Date 2010-04-29 Time 10:40 Rev Time 0.00
Received By mawillia Date 2010-04-29 Time 09:58 Sent To  
Notes
2010-04-29 10:43:24*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-3, A-4, A-5, AND E-1 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-04-06 Cont ID  
Sent By mcarsill Date 2010-04-06 Time 09:46 Rev Time 0.00
Received By mcarsill Date 2010-04-06 Time 09:11 Sent To  
Notes
2010-04-06 09:45:573700 SOUTH DIXIE HIGHWAY
 10030180
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS REMOVED THE SITE DAILY.
  
 3. EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED.
  
 4. ONLY ONE EMERGENCY LIGHT SHOWN ON PAGE E-2 WHICH IS
 NOT LOCATED NEAR AN EXIT DOOR.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEM.
  
 7. PLEASE INDICATE ON FLOOR PLAN WHERE DISABLED PERSONS
 WILL SIT.
  
 8. OCCUPANT LOAD WILL BE DETERMINED BY THIS OFFICE.
  
 9. ON PAGE A-3 THE TENANT DEMISING WALL APPEARS TO BE
 ONLY ONE HOUR FIRE RATED. PLEASE EXPLAIN RATIONALE.
  
 10. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 11. WRONG BUILDING CODE REFERENCED ON PAGE E-2. SHOULD
 READ 2007 EDITION.
  
 12. GAS INSTALLATIONS SHALL COMPLY WITH NFPA 54, THE
 NATIONAL FUEL GAS CODE.
  
 13. PLEASE ILLUSTRATE ALL PORTABLE AND K FIRE
 EXTINGUISHERS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-21 Cont ID  
Sent By lmartine Date 2010-04-20 Time 09:57 Rev Time 0.00
Received By lmartine Date 2010-04-20 Time 09:57 Sent To  
Notes
2010-04-22 10:48:55PLANS ARE IN DOUG'S OFFICE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-16 Cont ID  
Sent By btrobaug Date 2010-04-16 Time 08:37 Rev Time 0.00
Received By btrobaug Date 2010-03-09 Time 16:06 Sent To  
Notes
2010-04-16 08:39:06TO LARGE HOLDING BIN UNDER "M"./WRT.
2010-03-09 16:14:09C-19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2010-05-03 Cont ID  
Sent By jwitmer Date 2010-05-03 Time 14:21 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-03-24 Cont ID  
Sent By jwitmer Date 2010-03-24 Time 13:28 Rev Time 0.00
Received By jwitmer Date 2010-03-24 Time 13:28 Sent To  
Notes
2010-03-24 13:28:49BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-03-24 Cont ID  
Sent By hmoser Date 2010-03-24 Time 09:37 Rev Time 0.00
Received By hmoser Date 2010-03-23 Time 13:31 Sent To  
Notes
2010-03-24 09:50:36MECHANICAL REVIEW PASS WITH PROVISO
 PLEASE REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM AND
 SECTION 606.4.1 SUPERVISION .
 PLEASE REFER TO SECTION 301.12 WIND RESISTANCE FOR THE
 ERV UNIT .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-03-29 Cont ID  
Sent By lwagner Date 2010-03-29 Time 14:31 Rev Time 0.00
Received By lwagner Date 2010-03-29 Time 13:26 Sent To  
Notes
2010-03-29 14:29:53FBC PLUMBING 2007
 REVIEW #1
 ACTION: PASS PROVISO
  
 1. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 GAS PERMIT REQUIRED
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status N Date 2010-08-02 Cont ID  
Sent By astelly Date 2010-08-02 Time 10:25 Rev Time 0.00
Received By astelly Date 2010-08-02 Time 10:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-04-07 Cont ID  
Sent By astelly Date 2010-04-07 Time 17:27 Rev Time 0.00
Received By astelly Date 2010-04-07 Time 17:27 Sent To  
Notes
***NONE***