Plan Review Details - Permit 10030158
Plan Review Stops For Permit 10030158
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2010-03-05 Cont ID  
Sent By jnguyen Date 2010-03-05 Time 09:35 Rev Time  
Received By jwitmer Date 2010-03-05 Time 08:45 Sent To  
Notes
2010-03-05 09:31:50THIS PERMIT WAS FOR THE CONSTRUCTION OF A BOARDWALK IN
 THE SOUTH COVE NATURAL AREA (NO EXISTING PARCEL
 BOUNDARY WITH A PCN#). I HAVE EXAMINED THE SITE PLANS &
 DECIDED TO ISSUE IT THE UNOFFICIAL ADDRESS OF 690 S
 FLAGLER DR UNDER THE CITY OF WEST PALM BEACH PCN#
 74434328090160010. I CALLED ERIC ANDERSON & LEFT HIM A
 MESSAGE TO INFORM HIM OF THE ADDRESS. IN COMMUNITYPLUS
 UNDER PCN# 74434328090160010, I HAVE MOVED THIS PERMIT
 RECORD FROM SEQUENTIAL UNIT RECORD 0116 - 145 @ TRINITY
 PL TO SEQUENTIAL UNIT RECORD 0117 - 690 @ S FLAGLER DR.
 PLEASE IMPLEMENT THIS CORRECTION ON THE ORIGINAL PERMIT
 APPLICATION BECAUSE I WAS ONLY PROVIDED WITH A COPY.
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 MIS DEPARTMENT
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-05-26 Cont ID  
Sent By jwitmer Date 2010-05-10 Time 10:48 Rev Time 0.77
Received By jwitmer Date 2010-05-10 Time 10:48 Sent To  
Notes
2010-05-10 10:51:51BUILDING PLAN REVIEW
 PERMIT: 10030158
 ADD: 690 S FLAGLER DR
 CONT: TO BE DETERMINED
 CONTACT: ERIC ANDERSON/ ENVIRONMENTAL ANALYST
 TEL: (561)233-2514
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DESIGNER OF RECORD
 JASON HANCHUK P.E.
 PHONE: NOT PROVIDED!
  
 1) AT THIS TIME NO CONTRACTOR HAS SIGNED ON, WILL NEED
 TO VERIFY LICENSURE BEFORE ISSUANCE OF PERMIT!
  
 BUILDING PROVISO: SHEET B9 RAMP AND STEP DETAIL. TO
 PROVIDE EDGE PROTECTION PER FLORIDA D.O.T. STANDARDS
 FOR PEDESTRIAN WALKWAYS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-29 Cont ID  
Sent By jwitmer Date 2010-03-29 Time 13:32 Rev Time 4.40
Received By jwitmer Date 2010-03-29 Time 08:55 Sent To  
Notes
2010-03-29 13:32:32 
 BUILDING PLAN REVIEW
 PERMIT: 10030158
 ADD: 690 S FLAGLER DR
 CONT: TO BE DETERMINED
 CONTACT: ERIC ANDERSON/ ENVIRONMENTAL ANALYST
 TEL: (561)233-2514
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DESIGNER OF RECORD
 JASON HANCHUK P.E.
 PHONE: NOT PROVIDED!
  
 1ST REVIEW
 ACTION: DENIED
  
  
  
  
 1) PLEASE PROVIDE 2 SETS OF DOCUMENTS THAT ARE TO BE
 PERMITTED. ONE SET OF CONSTRUCTION DOCUMENTS SO
 REVIEWED DOCUMENTS SHALL BE RETAINED BY THE BUILDING
 OFFICIAL. THE OTHER SET SHALL BE RETURNED TO THE
 APPLICANT, AND SHALL BE KEPT AT THE SITE OF WORK AND
 SHALL BE OPEN TO INSPECTION BY THE BUILDING OFFICIAL OR
 A DULY AUTHORIZED REPRESENTATIVE. WEST PALM BEACH
 CONSTRUCTION SERVICES ADMINISTRATIVE CODE 106.3.1. THE
 DEPARTMENT OF THE ARMY ALSO REQUEST ONE SET OF
 DOCUMENTS TO BE AVAILABLE AT THE CONSTRUCTION SITE.
  
 2) MISSING DESIGN CRITERIA: 110.2* W. P. B.
 ADMINISTRATIVE CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 A-5 OCCUPANCY. ASSEMBLY USES INTENDED FOR PARTICIPATION
 IN OR VIEWING OUTDOOR ACTIVITIES.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5,
 TABLE 503.
 D) THE OCCUPANT LOAD, SEE 1004.
  
 3) MISSING INFORMATION: DESIGN CRITERIA LIVE LOADS
 DESIGNED TO TABLE 1607.1.(40).
  
 4) MISSING WIND DESIGN CRITERIA: 1604.4 EVERY STRUCTURE
 SHALL BE DESIGNED TO RESIST THE OVERTURNING EFFECTS
 CAUSED BY LATERAL FORCES SPECIFIED IN THIS CHAPTER. SEE
 SECTION 1609 FOR WIND AND SECTION 1610 FOR LATERAL SOIL
 LOADS.
  
  
  
 1603.1.4 WIND DESIGN DATA. THE FOLLOWING INFORMATION
 RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF THE
 LATERAL-FORCE-RESISTING SYSTEM OF THE BUILDING:
 4.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 4.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 4.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 4.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 5) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 ARE IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6.
  
 1802.2.4 PILE AND PIER FOUNDATIONS. PILE AND PIER
 FOUNDATIONS SHALL BE DESIGNED AND INSTALLED ON THE
 BASIS OF A FOUNDATION INVESTIGATION AND REPORT AS
 SPECIFIED IN SECTIONS 1802.4 THROUGH 1802.6 AND SECTION
 1808.2.2.
  
 1808.2.2 GENERAL. PIER AND PILE FOUNDATIONS SHALL BE
 DESIGNED AND INSTALLED ON THE BASIS OF A FOUNDATION
 INVESTIGATION AS DEFINED IN SECTION 1802, UNLESS
 SUFFICIENT DATA UPON WHICH TO BASE THE DESIGN AND
 INSTALLATION IS AVAILABLE.
  
 THE INVESTIGATION AND REPORT PROVISIONS OF SECTION 1802
 SHALL BE EXPANDED TO INCLUDE, BUT NOT BE LIMITED TO,
 THE FOLLOWING:
 1. RECOMMENDED PIER OR PILE TYPES AND INSTALLED
 CAPACITIES.
 2. RECOMMENDED CENTER-TO-CENTER SPACING OF PIERS OR
 PILES.
 3. DRIVING CRITERIA.
 4. INSTALLATION PROCEDURES.
 5. FIELD INSPECTION AND REPORTING PROCEDURES (TO
 INCLUDE PROCEDURES FOR VERIFICATION OF THE INSTALLED
 BEARING CAPACITY WHERE REQUIRED).
 6. PIER OR PILE LOAD TEST REQUIREMENTS.
 7. DURABILITY OF PIER OR PILE MATERIALS.
 8. DESIGNATION OF BEARING STRATUM OR STRATA.
 9. REDUCTIONS FOR GROUP ACTION, WHERE NECESSARY.
  
  
 6) SHEET B2 INDICATES THE USE OF IPE WOOD TO BE USED
 FOR DECKING, SIDE RAILS AND TOP RAILS, PLEASE PROVIDE
 TESTING DOCUMENTATION FOR FLAME SPREAD AND SMOKE
 DEVELOPMENT. SEE TABLE 803.5 NON-SPRINKLERED BUILDINGS.
 THIS IS A EXTERIOR USE BUT INCLUDED IN THIS TABLE ARE
 TYPE A-5 OCCUPANCIES ( A-5 OCCUPANCY. ASSEMBLY USES
 INTENDED FOR PARTICIPATION IN OR VIEWING OUTDOOR
 ACTIVITIES). IT APPEARS THIS FINISH SHOULD BE A ???A???
 TYPE RATING.
 803.1. CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED
 0-450.
  
 7) ANOTHER ISSUE WITH B2 IS THE GRATING SIZE OF 1 ??
 INCHES SQUARE. PLEASE REVIEW :
 11-4.5.4 GRATINGS. IF GRATINGS ARE LOCATED IN WALKING
 SURFACES, THEN THEY SHALL HAVE SPACES NO GREATER THAN
 1/2 INCH (13 MM) WIDE IN ONE DIRECTION [SEE FIGURE
 8(G)]. IF GRATINGS HAVE ELONGATED OPENINGS, THEN THEY
 SHALL BE PLACED SO THAT THE LONG DIMENSION IS
 PERPENDICULAR TO THE DOMINANT DIRECTION OF TRAVEL [SEE
 FIGURE 8(H)].
  
 8) SHEET B9 INDICATES ON THE LAND SIDE OF THE PROJECT A
 RAMP. THIS RAMP INDICATES A SLOPE OF 1:20 WHICH
 QUALIFIES NOT NEEDING HANDRAILS BUT THE REQUIREMENT FOR
 EDGE PROTECTION IS STILL REQUIRED. 1010.9 EDGE
 PROTECTION. EDGE PROTECTION COMPLYING WITH SECTION
 1010.9.1 OR 1010.9.2 SHALL BE PROVIDED ON EACH SIDE OF
 RAMP RUNS AND AT EACH SIDE OF RAMP LANDINGS.
  
 9) SHEET B9 & B10 INDICATED A STAIR WITH THREE RISERS
 MEASURING 7 INCHES OR A TOTAL RISE OF 21 INCHES. THE
 PLANS INDICATE AN ELEVEN INCH TREAD PLEASE REVIEW
 1003.5.1 WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT
 EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY A STAIR,
 THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE 13
 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF EACH
 STEP SHALL BE READILY APPARENT.
  
 10) SHEET B9 THE HANDRAIL INDICATED ON THE LEFT SIDE OF
 THE STAIR IS MISSING THE HORIZONTAL EXTENSION PARALLEL
 WITH THE FLOOR OR GROUND SURFACE. 11-4.9.4
  
 11) SHEET B9 THE HANDRAIL TO THE RIGHT SIDE OF THE
 STAIR IS NOT DEPICTED. B10 DETAIL# 1 DOES NOT INDICATE
 THE HANDRAIL NOR HANDRAIL EXTENSIONS SHALL COMPLY WITH
 11-4.4(1) PROTRUDING OBJECTS. . PLEASE ALSO PROVIDE THE
 DIMENSION FROM THE BOTTOM OF THE RETURN ON THE HANDRAIL
 TO GRADE.
  
 12) SHEET B10 DETAIL1 THE STEP BOARDWALK TERMINATION
 DETAIL. PLEASE PROVIDE THE ELEVATIONS AT THE BULKHEAD
 AND THE END OF THE TRANSITION WHERE THE 1: 20 SLOPE
 ENDS, ALSO PROVIDE THE DISTANCE BETWEEN THE TWO POINTS
 SO THIS AREA CAN BE REVIEWED TO DETERMINE IF THIS IS TO
 BE CONSIDERED A RAMP WITH HANDRAIL REQUIREMENTS.
 11-4.8.
  
 13) SHEET B7 DETAIL# 1 INDICATES THE USE OF GALVANIZED
 ROOFING PANELS AND NOA, NOTICE OF ACCEPTANCE REPORT
 WHICH IS A MIAMI-DADE REPORT. NO SUCH REPORT WAS
 SUBMITTED AT THIS TIME, THE PLANS ALSO DO NOT PROVIDE
 WIND PRESSURES FOR THIS STRUCTURE. RULE 9B-72(31)(D).
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2010-03-25 Cont ID  
Sent By dlauderm Date 2010-03-25 Time 14:19 Rev Time 10.00
Received By dlauderm Date 2010-03-25 Time 14:19 Sent To FIRE
Notes
2010-03-25 14:21:57CSD COMMENTS FOR PERMIT 10030158:
 REVIEWER: DEAN S. LAUDERMILK, PROJECT COORDINATOR
 IF YOU HAVE ANY QUESTIONS CONTACT ME AT: DIRECT DIAL:
 494-1083, FAX: 494-1116, EMAIL: [email protected]
 PLAN FOR BOARDWALK IS PASSED WITH THE FOLLOWING
 PROVISOS:
 THE COUNTY MAY WISH TO WAIT AND MEET WITH JOAN
 GOLDBERG, PRIOR TO MAKING ANY CHANGES TO THE LAND SIDE
 PLAN. SHE IS ON VACATION AND IS EXPECTED BACK ON APRIL
 5TH. THE FOLLOWING COMMENTS SHOULD BE CONSIDERED AS THE
 PRELIMINARY ESD REVIEW, SOME OF THE OUTSTANDING ISSUES
 INCLUDE (BUT WILL NOT BE LIMITED TO):
 A. THE EXISTING BIKE PATH/PEDESTRIAN WALKWAY, FROM
 OKEECHOBEE BLVD. TO BANYAN IS 16' WIDE. IN PLACES WHERE
 IT NARROWS DOWN TO 12' THERE IS ANOTHER 4' WIDE GRAVEL
 PATH THAT RUNS IN PARALLEL. A DISCUSSION WAS HELD WITH
 ASSISTANT CITY MANAGER ED BALBIS, P.E., TO SEE IF THE
 LOST 7'-10" WIDE SECTION WHERE THE RAMP IS GOING TO BE
 PLACED WILL NEED TO BE PUT BACK, REQUIRING THE
 RELOCATION OF AT LEAST 2 - 14' TALL PEDESTRIAN PATH
 LIGHTS, FOUR TREES, IRRIGATION LINES, ELECTRIC BOXES,
 AND PLANTS. IT SHOULD BE WIDENED, BUT THE FINAL
 DECISION NEEDS TO BE MADE BY JOAN GOLDBERG.
 B. IF THE EXISTING PATH NEEDS TO BE WIDENED IT WILL
 NEED TO MATCH THE EXISTING DESIGN AND USE THE SAME
 MATERIALS (PAVERS). ESD WILL SUPPLY A COPY OF THE PLAN
 FOR THE WALK WAY, IF REQUIRED.
 C. WHEN THE RAMP IS BUILT THE NEW PLANTER BETWEEN THE
 WALKWAY AND THE RAMP WILL NEED TO BE IRRIGATED. THE
 CITY WILL SUPPLY A COPY OF THE IRRIGATION AS-BUILTS
 WHEN WE RECEIVE THEM. THE PLAN WILL NEED TO SHOW THIS
 WORK.
 D. THE NEW RAMP WILL NEED TO MEET THE CITY PAVER
 DESIGN. ESD WILL SUPPLY A COPY OF THE PLAN, IF
 REQUIRED.
 E. THE BOARDWALK WILL NOT HAVE LIGHTS, SO IT WILL BE
 UNSAFE TO USE AT NIGHT. A GATE MAY NEED TO BE SUPPLIED
 TO LOCK DOWN THE BOARDWALK FROM SUNSET TO SUNRISE.
 F. WORK IN THE FLAGLER DRIVE ROW WILL NEED TO EITHER
 STOP OR BE COMPLETED PRIOR TO AND DURING THE EVENTS
 THAT TAKE PLACE IN THE FLAGLER DRIVE AREA. TOWARDS THIS
 END WE OBTAINED A COPY OF THE EVENT SCHEDULE SO THE
 LAND SIDE CONSTRUCTION CAN BE COORDINATED WITH THE
 EVENTS. IT WILL BE SENT TO THE COUNTY VIA EMAIL. THE
 SCHEDULE MAY CHANGE SO KEEP IN CONTACT WITH NICOLE
 MARTIN, EVENT SPECIALIST, COMMUNITY EVENTS DIVISION, AT
 561-822-1527 OR EMAIL HER AT [email protected].
 G. WHERE THE LANDING STARTS THERE IS A 30" RCP STORM
 LINE COMING THRU THE SEAWALL AT AN INVERT ELEVATION OF
 -4.85. EITHER THE LEDGE THAT IS TO BE BUILT TO HOLD THE
 SPARTINA (GRASS) WILL NEED TO BE MOVED OR THE STORM
 LINE WILL NEED TO BE EXTENDED UNDER THE LEDGE TO ALLOW
 THE STORMWATER SYSTEM TO WORK. ANOTHER SUGGESTION BY
 ONE OF OUR ENGINEERS WAS TO BUILD A BOX AROUND THE END
 OF THE LINE IN THE INTRACOASTAL TO ALLOW THE WATER TO
 FLOW OUT OVER THE GRASS. SINCE THE COUNTY PLAN IS NOT
 TO SCALE AND HAS NO MEASUREMENTS SHOWING THE DISTANCES
 BETWEEN THE LEDGES ALONG THE SEAWALL, WE WILL SUPPLY AN
 AS-BUILT (IN AUTO-CAD) FOR THE COUNTY'S USE TO CHECK
 OTHER POSSIBLE CONFLICTS WITH STORM LINES. (SNAP SHOT
 DELETED FROM REVIEW, SEE WORD DOCUMENT EMAILED TO THE
 COUNTY).
 H. DETAIL FROM AS-BUILT SHOWS TIE-IN FROM NEW SEAWALL
 TO EXISTING SEAWALL (BY FDOT) WITH RAILING ON TOP. I
 VISUALLY CHECKED AND IT APPEARS TO BE BUILT THIS WAY.
 THIS WILL AFFECT THE RAILING DESIGN AS SUBMITTED. WILL
 SUPPLY AS-BUILT (IN AUTO-CAD) FOR THE COUNTY'S USE TO
 CHECK OTHER POSSIBLE CONFLICTS. (SNAP SHOT DELETED FROM
 REVIEW, SEE WORD DOCUMENT EMAILED TO THE COUNTY).
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2010-04-29 Cont ID  
Sent By jwitmer Date 2010-04-29 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2010-04-29 Time 08:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-05-18 Cont ID  
Sent By mawillia Date 2010-05-18 Time 12:52 Rev Time 0.00
Received By mawillia Date 2010-05-18 Time 12:42 Sent To  
Notes
2010-05-18 12:52:41*****APPROVED*****
  
 AS WAS PREVIOUSLY DONE ON 03/25/2010, PLAN SHEETS 2,
 B2, AND B9 WERE STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-03-25 Cont ID  
Sent By mawillia Date 2010-03-25 Time 15:43 Rev Time 0.00
Received By mawillia Date 2010-03-25 Time 15:07 Sent To  
Notes
2010-03-25 15:44:35*****APPROVED*****
  
 PLAN SHEETS 2, B2, AND B9 WERE STAMPED, INITIALED, AND
 DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-29 Cont ID  
Sent By jwitmer Date 2010-04-29 Time 08:03 Rev Time 0.00
Received By jwitmer Date 2010-04-29 Time 08:03 Sent To  
Notes
2010-04-29 08:05:20INCOMING TO C-14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-14 Cont ID  
Sent By shill Date 2010-04-14 Time 16:34 Rev Time 0.00
Received By shill Date 2010-03-08 Time 14:37 Sent To  
Notes
2010-03-08 14:39:03TO C-15

Review Stop Z ZONING
Rev No 2 Status P Date 2010-06-21 Cont ID  
Sent By kdfreema Date 2010-06-21 Time 11:20 Rev Time 0.00
Received By kdfreema Date 2010-06-21 Time 11:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-04-13 Cont ID  
Sent By aaponte Date 2010-04-13 Time 16:01 Rev Time 0.00
Received By aaponte Date 2010-04-13 Time 16:01 Sent To  
Notes
2010-04-13 16:07:48WITH THE CONSTRUCTION OF THE ACCESS RAMP, THE SIDEWALK
 GETS REDUCED TO LESS THAN 8 FEET. PLEASE CONTACT JOAN
 GOLDBERG, PROJECT MANAGER FOR THE WATERFRONT PROJECT,
 TO DETERMINE IS THE SIDEWALK NEEDS TO BE WIDEN.
 PROPOSED PROJECT REQUIRES DAC SPECIAL REVIEW. PLEASE
 SUBMIT DAC APPLICATION.