Plan Review Details - Permit 10030118
Plan Review Stops For Permit 10030118
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-22 Cont ID  
Sent By shill Date 2010-03-22 Time 14:03 Rev Time 0.00
Received By shill Date 2010-03-22 Time 14:03 Sent To  
Notes
2010-03-22 14:04:18****PROVISO****
 ****PROVIDE AT INSPECTION****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE CANOPY FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 2. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 3. FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE
 FABRIC MEETS THE REQUIREMENT OF NFPA701.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 15:45 Rev Time 0.00
Received By shill Date 2010-03-16 Time 15:44 Sent To  
Notes
2010-03-16 15:52:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE CANOPY FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 2. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 3. FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE
 FABRIC MEETS THE REQUIREMENT OF NFPA701.
  
 4. FBC3501, PLAN STATES THAT IT HAS BEEN DESIGNED TO 75
 MPH WITH FABRIC ATTACHED. THE STRUCTURE IS TO BE
 DESIGNED TO 90MPH.
  
 5. FBC3501, PLAN STATES THAT THE OWNER IS TO REMOVE
 FABRIC WHEN WINDS OF 90 MPH ARE ANTICIPATED. THIS IS
 REQUIRED WHEN WINDS OF 75MPH ARE ANTICIPATED. PLEASE
 REVISE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 15:52 Rev Time 0.00
Received By shill Date 2010-03-03 Time 09:37 Sent To  
Notes
2010-03-04 09:38:45IN ZONING BOX

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2010-03-09 Cont ID  
Sent By rkussner Date 2010-03-09 Time 12:17 Rev Time 0.00
Received By rkussner Date 2010-03-09 Time 12:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-03-08 Cont ID  
Sent By jroach Date 2010-03-08 Time 21:19 Rev Time 0.00
Received By jroach Date 2010-03-08 Time 21:19 Sent To L
Notes
***NONE***