Plan Review Details - Permit 10020554
Plan Review Stops For Permit 10020554
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-03-01 Cont ID  
Sent By mgonzale Date 2010-02-25 Time 11:55 Rev Time 0.00
Received By shill Date 2010-03-01 Time 09:53 Sent To  
Notes
2010-03-01 10:11:04PROVISO - PROVIDE ORIGINAL STRUCTURAL ENGINEERING
  
2010-02-25 11:55:09 
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2010-02-25 Cont ID  
Sent By mgonzale Date 2010-02-25 Time   Rev Time 2.00
Received By mgonzale Date 2010-02-25 Time   Sent To B
Notes
2010-02-25 16:21:36PASSED WITH PROVISOS 02/25/2010:
  
 1. EOR HAS REVISED PLAN RELATED TO SOIL DENSITY.
 2. PIPE MATERIAL FOR STORM WORK IN THE BUILDING HAS
 BEEN IDENTFIED AS PVC.
 3. SHOP DRAWINGS HAVE BEEN PROVIDED.
 (MANHOLE COVER AND FRAME MUST BE HINGE DESIGN AS SHOWN
 ON CWPB DETAIL ST-2)
 (SEE DETAIL ATTACHED)
 4. CWPB STANDARD DETAILS HAVE BEEN ATTACHED ALONG WITH
 GENERAL NOTES.
 5. EOR HAS INCLUDED CWPB DETAIL GS-2 IN AN EFFORT TO
 ILLUSTRATE PIPE TO MANHOLE CONNECTION.
 6. 15" RCP STORM PIPE IN CONFLICT HAS ALSO BEEN SHOWN
 AND ELEVATION OF NEW 24" PVC PIPE WAS CHANGE TO AVOID
 CONFLICT.
  
 MANUEL JULIAN GONZALEZ
 ESD ENGINEERING REVIEW
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2010-02-25 Cont ID  
Sent By mgonzale Date 2010-02-25 Time   Rev Time 3.00
Received By mgonzale Date 2010-02-25 Time   Sent To B
Notes
2010-02-25 11:56:21SHEET C-9:
  
 1.NOTE 3 DENSITY SPECIFICATION FOR T-180 IS 98%
 2.PIPE MATERIAL NOT APPROVED FOR PROPOSED USE. PER FBC
 PLUMBING CODE, SECTION 1102.
 3.SHOP DRAWING, MATERIAL SUBMITTALS, AND SPECIFICATIONS
 REQUIRED.
 4.PROVIDE STRUCTURE CONNECTION DETAIL FOR PIPE, RWL,
 AREA DRAINS, AND CONDENSATE LINES.
  
 MANUEL JULIAN GONZALEZ
 ESD ENGINEERING REVIEW
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-01 Cont ID  
Sent By shill Date 2010-03-01 Time 10:10 Rev Time 0.00
Received By shill Date 2010-02-24 Time 16:23 Sent To  
Notes
2010-02-24 16:24:10TO MANNY GONZALEZ DESK
  