Plan Review Details - Permit 10020513
Plan Review Stops For Permit 10020513
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-05-10 Cont ID  
Sent By jgomez Date 2010-05-10 Time 10:29 Rev Time 0.00
Received By jgomez Date 2010-05-10 Time 09:50 Sent To Z
Notes
2010-05-10 10:30:11BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS
 UNDER A SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-04-21 Cont ID  
Sent By jgomez Date 2010-04-21 Time 16:44 Rev Time 0.00
Received By jgomez Date 2010-04-21 Time 16:44 Sent To  
Notes
2010-04-21 16:52:02BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS
 UNDER A SEPARATE PERMIT.
 2- REVISE ENERGY CALCULATIONS: PLANS CALL FOR UNVENTED
 ATTIC, WHILE ENERGY CALCULATIONS CALL FOR VENTED ATTIC.
 INFORMATION NEED TO MATCH.
 3- REVISE TRUSS DRAWING T-1.
 A) BEARING END CALLS FOR W=8". THIS IS A 2X4 WOOD
 FRAMED WALL. SEE PLANS AND REVISE AS REQUIRED.
 B) PROVIDE 2 COMPLETE COPIES SIGNED AND SEALED BY THE
 ENGINEER. ONLY ONE WAS SIGNED AND SEALED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-10 Cont ID  
Sent By jgomez Date 2010-03-10 Time 13:41 Rev Time 0.00
Received By jgomez Date 2010-03-10 Time 13:40 Sent To PC
Notes
2010-03-10 14:07:21RESIDENTIAL (R3) ADDITION/RENOVATION BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- REVISE ENERGY CALCULATIONS:
 A) NEED TO PROVIDE REVISED FORM FOR 2007 CODE. ONE
 SUBMITTED IS FOR 2004 CODE. NOTE: THERE IS NOT FORM C
 ON 2009 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE.
  
 B) CORRECT THE CLIMATE ZONE. THIS IS NOT ZONE 7.
  
 C) COORDINATE WALL TYPE AND INSULATION, CEILING TYPE
 AND INSULATION WITH INFORMATION SHOWN ON PLANS.
  
 D) CLARIFY EXISTING COOLING SEER VALUE. CHECK PLANS AND
 EXISTING UNIT.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) SLIDING GLASS DOORS. NOA 07-0808.09 IS CLOSED
 ACCORDING TO THE MIAMI-DADE WEBSITE. NEED TO PROVIDE
 CURRENT NOA.
  
 B) ROOF SHINGLES. NOA 08-0414.01 IS SUPERSEDED
 ACCORDING TO THE MIAMI-DADE WEBSITE. NEED TO PROVIDE
 CURRENT NOA.
  
 C) STORM SHUTTERS. AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE AND CLEARLY MARK ON SHUTTERS DRAWING SPECIFIC
 MOUNTING CONDITIONS AND FASTENER TYPE AND SPACING.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE THESE
 PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 4- PLANS NEED TO PROVIDE SPECIFICATIONS AND DETAILS
 SHOWING HOW PROVIDING GARAGE SEPARATION AS REQUIRED BY
 SEC. 309.2 OF 2007 FLORIDA RESIDENTIAL CODE. CEILING
 AND WALLS NEED TO PROVIDE SUCH SEPARATION.
  
 5- ESP LOW INSULATION:
 A) ACCORDING TO THE NOTES AND WARNINGS ON INFORMATION
 SUBMITTED NEED TO PROVIDE A PROPER THERMAL BARRIER IT
 CAN'T BE EXPOSED.
  
 B) PROVIDE INFORMATION SHOWING HOW PROVIDING THE
 R-VALUE REQUIRED BY THE ENERGY CALCULATIONS.
  
 6- TRUSS PACKAGE IS MISSING THE TRUSS T-1 DRAWING.
 ALSO, TRUSS LAYOUT AND INDIVIDUAL TRUSS DRAWINGS SHEETS
 NEED TO HAVE ORIGINAL SEAL AND SIGNATURE OF THE TRUSS
 ENGINEER. AND, PROVIDE TRUSS ENGINEER COMPLETE
 INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 7- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 **NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 8- SHEET A-1:
 A) SPECIFY SAFETY GLASS FOR MASTER BATHROOM WINDOW AS
 REQUIRED BY SEC. R308.4(5) OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 B) ENGINEERING CRITERIA INFORMATION: CLARIFY WHAT'S
 BUILDING CATEGORY IIIB AND SPECIFY WHAT SECTION OF THE
 CODE IS THIS TAKEN FROM.
  
 9- OWES $1179.85 PERMIT FEE BALANCE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-03-08 Cont ID  
Sent By btrobaug Date 2010-03-08 Time 11:59 Rev Time 0.00
Received By btrobaug Date 2010-03-08 Time 11:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-05-05 Cont ID  
Sent By shill Date 2010-05-05 Time 08:28 Rev Time 0.00
Received By shill Date 2010-05-05 Time 08:28 Sent To  
Notes
2010-05-05 08:29:22TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-12 Cont ID  
Sent By jgomez Date 2010-04-12 Time 13:12 Rev Time 0.00
Received By jgomez Date 2010-04-12 Time 13:04 Sent To  
Notes
2010-04-12 13:12:26SENT TO R-1.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-10 Cont ID  
Sent By jgomez Date 2010-03-10 Time 14:07 Rev Time 0.00
Received By jgomez Date 2010-02-24 Time 10:52 Sent To  
Notes
2010-02-24 10:53:03R-1

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-03-10 Cont ID  
Sent By jgomez Date 2010-03-10 Time 13:39 Rev Time 0.00
Received By jgomez Date 2010-03-10 Time 13:38 Sent To  
Notes
2010-03-10 13:40:06RENOVATION EXISTING LIVING SPACE TO BE USED AS MASTER
 BEDROOM AND CARPORT CONVERTED TO GARAGE.

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2010-05-12 Cont ID  
Sent By rkussner Date 2010-05-12 Time 16:04 Rev Time 0.00
Received By rkussner Date 2010-05-12 Time 16:03 Sent To  
Notes
2010-05-12 16:06:43***LANDSCAPE REVIEW APPROVED WITH PROVISO***
  
  
 MUST APPLY FOR SEPARATE LANDSCAPE AND IRRIGATION
 PERMITS, GET THEM APPROVED AND SUCCESSFULLY INSPECTED
 PRIOR TO C/O.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-04-29 Cont ID  
Sent By rkussner Date 2010-04-29 Time 14:27 Rev Time 0.00
Received By rkussner Date 2010-04-29 Time 14:27 Sent To  
Notes
2010-04-29 14:29:39***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. REPEAT COMMENT: PROVIDE THE SPACING FOR ALL PROPOSED
 PLANT MATERIAL.
  
 2. REPEAT COMMENT: PLEASE PROVIDE THE TABULATION
 NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE
 XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS,
 INCLUDING THE XERISCAPE DESIGN OPTIONS. THIS DOES NOT
 APPEAR TO MEET THE MINIMUM SHADE TREE REQUIREMENT.
  
 3. REPEAT COMMENT: PLEASE SHOW ALL UTILITES, OVERHEAD
 LINES, EASEMENTS AND ANYTHING ELSE THAT MAY INTERFERE
 WITH THE PROPOSED LANDSCAPING ON THE LANDSCAPE PLAN.
  
 4. REPEAT COMMENT: ALL EXISTING TREES, SHURBS AND
 GROUND COVER TO REMAIN SHALL BE IDENTIFIED.
  
 5. REPEAT COMMENT: LANDSCAPING REQUIRES A SEPARATE
 PERMIT. PLEASE SUBMIT TWO COPIES OF THE AMENDED
 LANDSCAPE PLAN AND A COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN
 DOWN INTO UNIT COST.
  
 6. REPEAT COMMENT: A SEPARATE IRRIGATION PERMIT IS
 REQUIRED.
  
 7. REPEAT COMMENT: IF ANY TREES WILL BE REMOVED, A TREE
 ALTERATION PERMIT WILL BE REQUIRED. THE APPLICATIONS
 ARE AVAILABLE AT THE FRONT DESK OF THE PLANNING AND
 ZONING DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-03-05 Cont ID  
Sent By rkussner Date 2010-03-05 Time 17:09 Rev Time 0.00
Received By rkussner Date 2010-03-05 Time 17:09 Sent To  
Notes
2010-03-05 17:29:21***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PROVIDE THE SPACING FOR ALL PROPOSED PLANT MATERIAL.
  
 2. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS. THIS DOES NOT APPEAR TO MEET
 THE MINIMUM SHADE TREE REQUIREMENT.
  
 3. PLEASE SHOW ALL UTILITES, OVERHEAD LINES, EASEMENTS
 AND ANYTHING ELSE THAT MAY INTERFERE WITH THE PROPOSED
 LANDSCAPING ON THE LANDSCAPE PLAN.
  
 4. ALL EXISTING TREES, SHURBS AND GROUND COVER TO
 REMAIN SHALL BE IDENTIFIED.
  
 5. LANDSCAPING REQUIRES A SEPARATE PERMIT. PLEASE
 SUBMIT TWO COPIES OF THE AMENDED LANDSCAPE PLAN AND A
 COST ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL
 LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO UNIT
 COST.
  
 6. A SEPARATE IRRIGATION PERMIT IS REQUIRED.
  
 7. IF ANY TREES WILL BE REMOVED, A TREE ALTERATION
 PERMIT WILL BE REQUIRED. THE APPLICATIONS ARE AVAILABLE
 AT THE FRONT DESK OF THE PLANNING AND ZONING
 DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-03-02 Cont ID  
Sent By kstevens Date 2010-03-02 Time 11:41 Rev Time 0.00
Received By kstevens Date 2010-03-02 Time 11:41 Sent To  
Notes
2010-03-02 11:41:53PLUMBING PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2010-04-28 Cont ID  
Sent By lfranco Date 2010-04-28 Time 19:33 Rev Time 0.00
Received By lfranco Date 2010-04-28 Time 19:33 Sent To L
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-03-05 Cont ID  
Sent By lfranco Date 2010-03-05 Time 15:14 Rev Time 0.00
Received By lfranco Date 2010-03-05 Time 15:08 Sent To L
Notes
2010-03-05 15:50:46PLANNING AND ZONING: **** FAILED ****
  
 1. PROVIDE COMMENTS IN WRITING.
  
 2. THE SURVEY SHOWS SOME PROPOSED WORK, BUT NOT ALL.
 FOR EXAMPLE, THE DIMENSIONS OF THE "NEW MASTER BEDROOM
 AND BATHROOM" SEEM TO BE INCLUDED WITH A SETBACK OF
 4.81', YET THE PROPOSED "NEW GARAGE" IS NOT SHOWN.
 PROVIDE AN EXISTING (AS-BUILT) SURVEY ONLY OR SHOW ALL
 PROPOSED IMPROVEMENTS WITH SETBACK DIMENSIONS.
  
 3. PURSUANT TO SECTION SEC. 94-72 OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS ("ZLDR"). THE MINIMUM
 SETBACKS FOR PRINCIPAL BUILDING IN A SINGLE-FAMILY LOW
 DENSITY ("SF7") RESIDENTIAL DISTRICT IS AS FOLLOWS:
  
 (2)
 A. FRONT: 25 FEET;
 B. CORNER: 12.5 FEET;
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL
  
 THE PROPOSED SIDE SETBACK DOES NOT MEET THE MINIMUM
 REQUIREMENT. PROVIDE THE REAR SETBACK DIMENSION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  