Plan Review Details - Permit 10020496
Plan Review Stops For Permit 10020496
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-11 Cont ID  
Sent By jwitmer Date 2010-03-11 Time 10:17 Rev Time 1.55
Received By jwitmer Date 2010-03-11 Time 10:17 Sent To  
Notes
2010-03-11 12:14:22BUILDING PLAN REVIEW
 PERMIT: 10020496
 ADD: 1885 OKEECHOBEE RD SUITE 1881
 CONT: SETH A FORD
 TEL: (561)718-7560
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DESIGN PROFESSIONAL:
 MCR PROFESSIONAL ENGINEERING, INC.
 MICHAEL BABER P.E.
 OFFICE: (561)863-3393
  
  
 1ST REVIEW
 ACTION: DENIED
  
  
 NOTE!!!! THIS COMMENT IS TO MAKE THE DESIGN
 PROFESSIONAL AND TENANT AWARE OF EXISTING CODE
 COMPLIANCE ISSUES OF THE EXISTING TENANT CONFIGURATION.
 AT THIS TIME IT IS NOT CERTAIN THAT THE PROPOSED MEANS
 OF EGRESS REFLECT THE ORIGINAL PLANS, AND IF THEY WERE,
 THEY WERE ISSUED IN ERROR, OR IF WORK WAS COMPLETED
 SINCE THE ISSUED C. O. AND NOT HAVING THE BENEFIT OF
 PERMIT.
  
 ISSUE ONE IS THE OFFICE AREA IS OVER 8,800 SQ FT AND A
 OCCUPANT LOAD OF 89 OCCUPANTS.
 FBC-B TABLE 1019.2 WILL ONLY ALLOW AN OCCUPANT LOAD OF
 49 WITH A SINGLE EXIT. TWO EXITS ARE REQUIRED AND NOT
 TRAVELING THROUGH A HIGHER HAZARD OCCUPANCY, STORAGE
 (FBC-B1014.2.1). THE EXITS THAT LEAD INTO THE WAREHOUSE
 WOULD NEED TO BE A 2 HR EXIT PASSAGEWAY FROM THE OFFICE
 OCCUPANCY TO THE WAREHOUSE EXIT.
  
 ISSUE TWO IS THERE IS WITHIN THE FENCED IN AREA OF THE
 WAREHOUSE THERE IS TWO MEANS OF EGRESS WITHIN THIS AREA
 BUT HEY ARE NOT SEPARATED BY 1/3RD THE DISTANCE
 (1015.1.2 EXCEPTION 2), THE SECOND ISSUE WITHIN THE
 FENCED IN AREA WOULD BE THE COMMON PATH OF TRAVEL HAS
 ALSO BEEN EXCEEDED, SPRINKLERED BUILDING WITH A STORAGE
 OCCUPANCY ALLOW FOR 100 FT. COMMON PATH OF TRAVEL
 1014.3 EXCEPTION 1).
  
 THE THIRD AREA OF CONCERN IS THE STORAGE AREA NOT
 FENCED IN, COMMON PATH OF TRAVEL HAS BEEN EXCEEDED,
 FBC-B 1014.3 EXCEPTION 1. THE OTHER ISSUE IS HOW ONE
 DETERMINES IF THE STORAGE AREA IS ONE LARGE ONE OR A
 OPEN AREA AND A SECOND FENCED IN AREA UNDER LOCK AND
 KEY. WHEN THE AREA IS CONSIDERED ONE LARGE AREA THERE
 ARE TWO EXITS BUT YOU WOULD NEED TO TRAVEL THROUGH A
 LOCKED AREA, THE TOTAL OCCUPANT LOAD OF THIS SPACE
 WOULD BE 64 REQUIRING TWO DOORS. THE DESIGN TEAM CAN
 ALLOW THE OCCUPANTS OF THE WAREHOUSE TO TRAVEL THROUGH
 THE BUSINESS OCCUPANCY TO AN EXIT. BUT THE DOORS THAT
 LEAD FROM THE OFFICE TO WARE HOUSE WOULD HAVE TO BE
 REVIEWED FOR SWING IN THE DIRECTION OF TRAVEL,
 (1008.1.2).
  
 COMMENT# 1 UNDER THE CURRENT PLAN REVIEW:
  
 1) THE COVERSHEET CODE DATA INDICATES WARE HOUSE
 OCCUPANCY AS F-1 AND A OCCUPANT SQ FT OF 500 SQ FT PER
 PERSON. PLEASE PROVIDE THE TYPE OF MANUFACTURING, FBC-B
 306.2 FACTORY-
 INDUSTRIAL F-1 MODERATE HAZARD.
  
 2) THE OTHER ISSUE IS WITH THE F-1 OCCUPANCY, TABLE
 1004.1.1 INDICATES THE OCCUPANCY PER SQ FT WOULD BE 100
 SQ FT / PERSON. PLEASE CORRECT. FOR STORAGE/ SHIPPING
 IT WOULD BE 300 GROSS.
  
 3) PLANS DO NOT PROVIDE A DOOR LEGEND PLEASE PROVIDE TO
 INDICATE CODE COMPLIANCE WITH FBC-B 715 OPENING
 PROTECTIVE???S AND TABLE 715.4.NOTE PLANS INDICATE A
 NEW FIRE RATED DOOR AND JAMB BUT NO OPENING PROTECTION
 INFORMATION.
  
 4) PLANS INDICATE A NEW MEN???S AND LADIES RESTROOM BUT
 NO HANDICAPPED FACILITIES.
 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS.
 (1) GENERAL. ALTERATIONS TO EXISTING BUILDINGS AND
 FACILITIES SHALL COMPLY WITH THE FOLLOWING:
 (A) NO ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES
 OR HAS THE EFFECT OF DECREASING ACCESSIBILITY OR
 USABILITY OF A BUILDING OR FACILITY BELOW THE
 REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME OF
 ALTERATION.
 11-4.1.3. (11) TOILET FACILITIES. IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22.
 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED,
 THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE
 STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING
 WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES
 (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING
 DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D)
 AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16. IF WATER
 CLOSETS ARE NOT IN STALLS, THEN AT LEAST ONE SHALL
 COMPLY WITH SECTION 11-4.16.
  
 5) THE EMPLOYEE LOUNGE INDICATES THE USE OF A SINK,
 PLEASE PROVIDE DETAILS INDICATING COMPLIANCE WITH:
  
 SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED
 WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 6) PLANS WILL ALSO NEED TO PROVIDE COMPLIANCE WITH:
 INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED
 IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR FINISH
 MATERIALS SHALL BE GROUPED IN THE FOLLOWING CLASSES IN
 ACCORDANCE WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED
 INDEXES.
  
 PLEASE INCLUDE A LIFE SAFETY PLAN PROVIDING OCCUPANCY
 LOADS, EGRESS REQUIREMENTS, EXIT ACCESS, EXIT, EXIT
 DISCHARGE, EMERGENCY LIGHTING AND EXITS DIRECTIONAL???S
 AND EXIT SIGNAGE AS WELL AS LOCATION OF FIRE
 EXTINGUISHERS. WPB ADMINISTRATIVE CODE 106.3.5.1.1(7) &
 FBC-B 906.1.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-03-01 Cont ID  
Sent By dpalmer Date 2010-03-01 Time 16:58 Rev Time 0.00
Received By dpalmer Date 2010-03-01 Time 16:58 Sent To  
Notes
2010-03-01 16:58:16** DENIED **
  
  
 1) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF
 WORK SHOWN ON PLANS IS LOW.
 PLEASE KNOW THAT PER FBC 108.3 THE APPLIED SCOPE OF
 WORK IS TO INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST EVEN IF ANY OF THESE THINGS ARE OWNER
 SUPPLIED.
  
 2) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR NEW
 AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULES.
 408.4,310.16,240.4, 220, 210 ETC
 THE CIRCUITING ON PANEL SCHEDULES ARE NOT PERMITTED TO
 BE GENERIC. * LIGHTING AND RECEPTACLES * IS NOT
 ACCEPTABLE. PLEASE SEE CODE COMMENTARY IN THE NEC UNDER
 408.4.
  
 3) NOTE: PLEASE PLACE NOTE ON PLANS FOR COMPUTER ROOM.
 * NO NEC 645 WIRING METHODS PERMITTED* OR WORDS TO THAT
 AFFECT.
 THIS IS NOT AN IT ROOM BY DEFINITION BASED ON THE PLANS
 SUBMITTED THEREFORE WIRING METHODS WHICH ARE LESS
 STRINGENT IN 645 ARE NOT ALLOWED.
  
 4) NOTE: PLEASE SEE FBC 13-415.AB.1.1, .1.2 AND .1.3
 FOR NEW LIGHTING CONTROLS. ANY NEW SEPARATE SPACES AND
 NEW CONTROLS SHALL MEET MINIMUM PRESCRIPTIVE
 REQUIREMENTS.
  
 5) NOTE: PLANS INDICATE POWER FOR NEW EXHAUST FANS IN
 BATHROOMS HOWEVER NO CONTROL LOCATIONS SHOWN.
 PLEASE SEE MECHANICAL COMMENTS FOR FLORIDA MECHANICAL
 CODE WHICH REQUIRES CONTROLS.
  
 6) NOTE: PLEASE SEE 240.21, 408.36 AS A MAIN IS
 REQUIRED ON THE SECONDARY SIDE OF THE TRANSFORMER. ALL
 TAPPED CONDUCTORS SHALL TERMINATE IN OVER CURRENT
 PROTECTION.
 THIS IS A LIFE SAFETY AND FIRE HAZARD AND WILL BE
 REQUIRED TO BE CORRECTED.
  
 7) NOTE: LOADS ON SERVICE AND PANELS ARE TO BE
 COMPLETED. PANELS DO NOT INDICATE LOADS.
 220, 220.14,220.12, 220.42, .43, ETC
 PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125%.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW BEING INSTALLED IN ADDITION TO
 EXISTING IN NEW AREAS.
 13-415.AB.5
  
 6) NOTE: HOW IS PANEL LA FED? THERE IS NO OCP SHOWN IN
 PANEL L FOR SUB PANEL.
 SEE NOTE #6 ABOVE.
  
 7) NOTE: COVER SHEET INDICATES SOME CODES FROM THE 2004
 FBC. PLEAS EBE SURE THE PLANS INDICATE THE FOLLOWING
 FOR THIS REVIEWER FOR RELEVANT DESIGN.
  
  
 2007 FBC W/ 2009 SUPPLEMENTS
 2006 NFPA-101
 2008 NFPA-70
 2002 NFPA-728) NOTE: NO FIRE ALARM DEVICES, SYSTEMS
 SHOWN. PLEASE SEE FBC 11-4.28.1,.2 AND .3 FOR MINIMUM
 LOCATIONS, LEVELS AND HEIGHTS FOR ADA COMPLIANCE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-08 Cont ID  
Sent By mcarsill Date 2010-03-08 Time 10:06 Rev Time 0.00
Received By mcarsill Date 2010-03-08 Time 09:59 Sent To  
Notes
2010-03-08 10:06:361885 OKEECHOBEE ROAD
 ARMOR SCREEN CORPORATION
 PERMIT # 10020496
  
 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 3. NO FIRE ALARM DEVICES SHOWN IN EXISTING WORK AREA,
 EMPLOYEE LOUNGE, AND NEW CONFERENCE ROOM.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 ALARM REMODELING PLANNED.
  
 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 6. PLEASE INDICATE EXISTING HARDWARE AND LOCKING
 DEVICES PRESENT ON EXISTING EXIT DOORS.
  
 7. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND
 CEILINGS SHALL COMPLY WITH THE FLORIDA BUILDING AND
 FLORIDA FIRE PREVENTION CODE.
  
 8. MORE DETAILS REQUIRED FOR NEW COMPUTER ROOM.
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-15 Cont ID  
Sent By jwitmer Date 2010-03-15 Time 09:36 Rev Time 0.00
Received By jwitmer Date 2010-02-24 Time 10:56 Sent To  
Notes
2010-02-24 11:14:30C-3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-03-04 Cont ID  
Sent By rregueir Date 2010-03-04 Time 20:28 Rev Time 0.00
Received By rregueir Date 2010-03-04 Time 20:22 Sent To  
Notes
2010-03-04 20:28:42REVIEW #:
 ACTION:
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE VENTILATION CALCULATIONS FOR ALL
 RECONFIGURED SPACES IN ACCORDANCE WITH FBC-EB 709.1 AND
 FBC-M SECTION 403, INCLUDING NEW OFFICES AND EMPLOYEE
 LOUNGE.
  
 2. PROVIDE SIZE OF RETURN AIR TRANSFER DUCTS IN
 ACCORDANCE WITH FBC-M 601.4.
  
 3. PROVIDE EXHAUST FAN SCHEDULE SHOWING EXHAUST RATE
 CFM TO DEMONSTRATE COMPLIANCE WITH FBC-M SECTION 403.
  
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-03-04 Cont ID  
Sent By kstevens Date 2010-03-04 Time 08:28 Rev Time 0.00
Received By kstevens Date 2010-03-04 Time 08:28 Sent To  
Notes
2010-03-04 08:59:09DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS ENGINEERS SHALL LEGIBLY INDICATE THEIR
 ADDRESS IN THEIR TITLE BLOCK ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025.
  
 2. SHT 1 11-4.23.5 URINALS. IF URINALS ARE PROVIDED,
 THEN AT LEAST ONE SHALL COMPLY WITH SECTION 11-4.18.
 SHOW COMPLIANCE WITH THE FOLLOWING:
 11-4.18.2 HEIGHT. URINALS SHALL BE STALL-TYPE OR
 WALL-HUNG WITH AN ELONGATED RIM AT A MAXIMUM OF 17
 INCHES (430 MM) ABOVE THE FINISH FLOOR.
  
 11-4.18.3 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE 30
 INCHES BY 48 INCHES (760 MM BY 1220 MM) SHALL BE
 PROVIDED IN FRONT OF URINALS TO ALLOW FORWARD APPROACH.
 THIS CLEAR SPACE SHALL ADJOIN OR OVERLAP AN ACCESSIBLE
 ROUTE AND SHALL COMPLY WITH SECTION 11-4.2.4. URINAL
 SHIELDS THAT DO NOT EXTEND BEYOND THE FRONT EDGE OF THE
 URINAL RIM MAY BE PROVIDED WITH 29 INCHES (735 MM)
 CLEARANCE BETWEEN THEM.
  
 11-4.18.4 FLUSH CONTROLS. FLUSH CONTROLS SHALL BE HAND
 OPERATED OR AUTOMATIC, AND SHALL COMPLY WITH SECTION
 11-4.27.4, AND SHALL BE MOUNTED NO MORE THAN 44 INCHES
 (1120 MM) ABOVE THE FINISH FLOOR.
  
 11-4.18.4 FLUSH CONTROLS. FLUSH CONTROLS SHALL BE HAND
 OPERATED OR AUTOMATIC, AND SHALL COMPLY WITH SECTION
 11-4.27.4, AND SHALL BE MOUNTED NO MORE THAN 44 INCHES
 (1120 MM) ABOVE THE FINISH FLOOR.
  
 3. SHT 1 IF TOILET STALLS ARE PROVIDED, THEN AT LEAST
 ONE SHALL BE A STANDARD TOILET STALL COMPLYING WITH
 SECTION 11-4.17. SECTION 11-4.22.4. THE STANDARD
 ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN ACCESSIBLE
 LAVATORY WITHIN IT, THE SIZE OF SUCH LAVATORY TO BE NOT
 LESS THAN 19 INCHES WIDE BY 17 INCHES (483 MM BY 432
 MM) DEEP, NOMINAL SIZE, AND WALL MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 11-4.17. SEE FIGURE
 11-17(E).
  
 4. 11-4.22.6 LAVATORIES AND MIRRORS. IF LAVATORIES AND
 MIRRORS ARE PROVIDED, THEN AT LEAST ONE OF EACH SHALL
 COMPLY WITH SECTION 11-4.19. THERE ARE NO ACCESSIBLE
 LAVS INDICATED IN THE WOMEN'S TOILET ROOM. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 11-4.19 LAVATORIES AND MIRRORS.
  
 11-4.19.1 GENERAL. THE REQUIREMENTS OF SECTION 11-4.19
 SHALL APPLY TO LAVATORY FIXTURES, VANITIES, AND
 BUILT-IN LAVATORIES.
  
 11-4.19.2 HEIGHT AND CLEARANCES. LAVATORIES SHALL BE
 MOUNTED WITH THE RIM OR COUNTER SURFACE NO HIGHER THAN
 34 INCHES (865 MM) ABOVE THE FINISH FLOOR. PROVIDE A
 CLEARANCE OF AT LEAST 29 INCHES (735 MM) ABOVE THE
 FINISH FLOOR TO THE BOTTOM OF THE APRON. KNEE AND TOE
 CLEARANCE SHALL COMPLY WITH FIGURE 31.
  
 11-4.19.3 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE 30
 INCHES BY 48 INCHES (760 MM BY 1219 MM) COMPLYING WITH
 SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A
 LAVATORY TO ALLOW FORWARD APPROACH. SUCH CLEAR FLOOR
 SPACE SHALL ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH
 THE LAVATORY (SEE FIGURE 32).
  
 11-4.19.4 EXPOSED PIPES AND SURFACES. HOT WATER AND
 DRAIN PIPES UNDER LAVATORIES SHALL BE INSULATED OR
 OTHERWISE CONFIGURED TO PROTECT AGAINST CONTACT. THERE
 SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER
 LAVATORIES.
  
 11-4.19.5 FAUCETS. FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, AND
 ELECTRONICALLY CONTROLLED MECHANISMS ARE EXAMPLES OF
 ACCEPTABLE DESIGNS. IF SELF-CLOSING VALVES ARE USED THE
 FAUCET SHALL REMAIN OPEN FOR AT LEAST 10 SECONDS.
  
 5. SHT 2 THE EMPLOYEE LOUNGE SINK SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH THE FOLLOWING:
 11-4.24 SINKS.
  
 11-4.24.1 GENERAL. SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.24.
  
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34 INCHES (865 MM) ABOVE
 THE FINISH FLOOR.
  
 11-4.24.3 KNEE CLEARANCE. KNEE CLEARANCE THAT IS AT
 LEAST 27 INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE,
 AND 19 INCHES (485 MM) DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS.
  
 11-4.24.4 DEPTH. EACH SINK SHALL BE A MAXIMUM OF 61/2
 INCHES (165 MM) DEEP.
  
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK (SEE FIGURE 32). - NOTE: CABINET DOORS ARE NOT
 ALLOWED IN THE CLEAR FLOOR SPACE.
  
 11-4.24.6 EXPOSED PIPES AND SURFACES. HOT WATER AND
 DRAIN PIPES EXPOSED UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT AGAINST CONTACT.
 THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
  
 11-4.24.7 FAUCETS. FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE
 DESIGNS.
  
 6. SHT 4, A SANITARY ISOMETRIC RISER DIAGRAM IS
 REQUIRED SHOWING ALL PIPE SIZES, TRAPS & VENTS.
 SECTIONS 106.3.5.1.3(4)(6)(13), 701.1, 901.1 & 1001.1
  
 7. SHT 4, A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED
 SHOWING ALL PIPE SIZES, VALVES & (WHERE REQUIRED BY
 SECTION 604.9), WATER HAMMER ARRESTORS. SECTIONS
 106.3.5.1.3(3)(10)(13) & 601.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-03-09 Cont ID  
Sent By kdfreema Date 2010-03-09 Time 13:21 Rev Time 0.00
Received By kdfreema Date 2010-03-09 Time 13:21 Sent To  
Notes
***NONE***