Plan Review Details - Permit 10020467
Plan Review Stops For Permit 10020467
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-03-25 Cont ID  
Sent By shill Date 2010-03-25 Time 08:33 Rev Time 0.00
Received By shill Date 2010-03-25 Time 08:33 Sent To  
Notes
2010-03-25 08:39:16PROVISO - SMS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-03-23 Cont ID  
Sent By shill Date 2010-03-23 Time 16:05 Rev Time 0.00
Received By shill Date 2010-03-23 Time 16:05 Sent To  
Notes
2010-03-23 16:22:25****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE NEW PLAN SHOWS 150MPH EXPOSURE B. PLEASE REVISE.
  
 2. PLEASE CLARIFY GIRT SIZING. IF NECESSARY, CIRCLE ON
 THE CHARTS SUBMITTED. THE FIRST SUBMITTAL INCLUDED A
 SHEET WHICH PROVIDED GIRT INFORMATION; THIS WAS NOT
 PROVIDED IN A REVISED FORM FOR EXPOSURE C. HOWEVER, THE
 LOAD WIDTH APPEARS TOO SHORT (ROUNDING DOWN RATHER THAN
 ROUNDING UP) AND THE TYPE OF CHAIR RAIL PROPOSED IS NOT
 CLEAR, ONLY SIZE, BUT NOT ALL SIZES COMPLY. FOR
 INSTANCE, 4'4" LOAD WITDTH, 7'10" SPAN, 2X3. THE NEW
 PLAN DOES NOT SPECIFY WHICH 2X3; SMS IS SPECIFIED ON A
 SHEET FROM THE FIRST SUBMITTAL WHICH SPECIFIES EXPOSURE
 B. PLEASE REVISE THE PLAN TO INCLUDE THE TYPE OF GIRT
 PROPOSED.
  
 4'4" LOAD WIDTH - IT APPEARS THAT THIS SHOULD BE 4'5".
 IT IS NOT CLEAR WHY YOU HAD SPECIFIED A 7'10" SPAN,
 ISN'T THIS AN 8' SPAN? YOU CANNOT DEDUCT FOR THE
 MEMBERS, THIS DIMENSION SHOULD GO FROM STRUCTURE/CENTER
 OF POST TO STRUCTURE/CENTER OF POST. 2X3 SMS REQUIRED,
 BUT "SMS" WAS NOT SPECIFIED ON ANY OF THE REVISED
 SHEETS. IT IS NOT CLEAR HOW SPANS HAVE BEEN DETERMINED.
  
 FOR THE 3'11"/5' LOAD WIDTH/SPAN, 2X2 SPECIFIED. SMS
 NOT SPECIFIED, BUT APPEARS TO BE REQUIRED. PLEASE
 REVISE PLAN TO STATE SPECIFIC SIZE IF ALL DO NOT
 COMPLY.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-09 Cont ID  
Sent By shill Date 2010-03-09 Time 14:38 Rev Time 0.00
Received By shill Date 2010-03-09 Time 14:38 Sent To  
Notes
2010-03-09 14:43:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THIS PARCEL IS IN THE TRANSITION ZONE BETWEEN
 EXPOSURE BAND EXPOSURE C, AND THEREFORE MUST BE
 DESIGNED AS EXPOSURE C UNLESS INTERPOLATED BY AN
 ENGINEER FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE
 CHANGED EFFECTIVE MARCH 1, 2009.
  
 ***THIS IS A COURTESY NOTICE - IN THE FUTURE, PLANS
 WILL NOT BE DENIED BUT WILL BE ISSUED WITH PROVISO THAT
 THE PLANS BE REVISED PRIOR TO FIRST INSPECTION, WITH
 REVISION FEES.**
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-22 Cont ID  
Sent By lmartine Date 2010-03-18 Time 13:52 Rev Time 0.00
Received By lmartine Date 2010-03-18 Time 13:52 Sent To  
Notes
2010-03-22 13:52:57GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-09 Cont ID  
Sent By shill Date 2010-03-09 Time 14:44 Rev Time 0.00
Received By shill Date 2010-02-23 Time 08:44 Sent To  
Notes
2010-02-23 08:45:34TO ZONING IN BOX./WRT.

Review Stop Z ZONING
Rev No 1 Status P Date 2010-03-04 Cont ID  
Sent By lfranco Date 2010-03-04 Time 15:37 Rev Time 0.00
Received By lfranco Date 2010-03-04 Time 15:37 Sent To B
Notes
2010-03-04 15:40:28PLANNING AND ZONING **** PASSED WITH PROVISO, THE
 SCREEN ENCLOSURE IS TO THE REAR EDGE (SOUTH EDGE) OF
 EXISTING HOME. ****
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]