Plan Review Details - Permit 10020403
Plan Review Stops For Permit 10020403
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-02-22 Cont ID  
Sent By jgomez Date 2010-02-22 Time 11:52 Rev Time 0.00
Received By jgomez Date 2010-02-22 Time 11:11 Sent To PC
Notes
2010-02-22 11:56:19REROOF REVISION CHECKLIST:
  
 1- PRODUCT APPROVAL FL1654-R6 SUBMITTED IS MISSING THE
 TECHNICAL INFORMATION SHOWING SPECIFIC APPROVED
 ASSEMBLY TO BE INSTALLED. PROVIDE INFORMATION SHOWING
 SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 2007 FLORIDA RESIDENTIAL CODE.
 ***NOTE: IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301, THEN NEED TO PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL NOTE #6 OF THE PRODUCT APPROVAL SUBMITTED.
 ALSO, CHECK GENERAL NOTE #7 FOR BONDED SYSTEMS. NAIL
 ENHANCING IS NOT ALLOWED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-22 Cont ID  
Sent By jgomez Date 2010-02-22 Time 11:12 Rev Time 0.00
Received By jgomez Date 2010-02-22 Time 11:12 Sent To  
Notes
***NONE***