Plan Review Details - Permit 10020378
Plan Review Stops For Permit 10020378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-05-07 Cont ID  
Sent By rmcdouga Date 2010-05-07 Time 08:55 Rev Time 0.00
Received By rmcdouga Date 2010-05-07 Time 08:55 Sent To  
Notes
2010-05-07 08:57:14PROVISO
  
 SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR WINDOW
 MULLIONS, CUPOLA AND PLASTIC LUMBER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-04 Cont ID  
Sent By rmcdouga Date 2010-03-04 Time 13:03 Rev Time 0.00
Received By rmcdouga Date 2010-03-04 Time 13:03 Sent To  
Notes
2010-03-04 14:12:03DENIED BY BUILDING
  
 1) PROVIDE STRUCTURAL DETAILS FOR THE PATIO ARBOR.
 SPECIFY ALL CONNECTORS AND CONNECTIONS. FBCR 301
  
 2) PROVIDE TWO COPIES OF A RECENT SURVEY.
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS, WINDOWS, MULLIONS, OVERHEAD GARAGE
 DOOR, ROOFING MATERIAL AND CUPOLA AS REQUIRED BY DCA
 RULE 9B-72.
  
 4) ON SHEET S2.0 THERE IS A TYPO SPECIFYING ASCE 7-50
 INSTEAD OF ASCE 7-05. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-26 Cont ID  
Sent By btrobaug Date 2010-04-26 Time 13:03 Rev Time 0.00
Received By btrobaug Date 2010-04-26 Time 12:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-22 Cont ID  
Sent By btrobaug Date 2010-02-22 Time 09:22 Rev Time 0.00
Received By btrobaug Date 2010-02-18 Time 12:43 Sent To  
Notes
2010-02-18 16:17:20 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E1.0 RISER DIAGRAM INDICATES A METER,
 DISCONNECT (FOR PANEL "A") AND PANEL "B", BEING FED
 FROM "A". THE PANEL SCHEDULE IS LABELED PANEL "A". IS
 THE DISCONNECT A COMBINATION DISCONNECT AND PANEL OR IS
 PANEL "B" MISLABELED, CORRELATE SAME. NO FEEDER SHOWN
 TO PANEL "B" FROM PANEL "A" SCHEDULE.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR IS INCORRECT PER
 250.66, MINIMUM SIZE IS #4 CU.
  
 3} THERE IS ONLY ONE SMALL APPLIANCE CIRCUIT SHOWN IN
 THE PANEL SCHEDULE.220.52 SMALL APPLIANCE AND LAUNDRY
 LOADS ??? DWELLING UNIT
 (A) SMALL APPLIANCE CIRCUIT LOAD IN EACH DWELLING UNIT,
 THE LOAD SHALL BE CALCULATED AT 1500 VOLT-AMPERES FOR
 EACH 2-WIRE SMALL-APPLIANCE BRANCH CIRCUIT REQUIRED BY
 210.11(C)(1). WHERE THE LOAD IS SUBDIVIDED THROUGH TWO
 OR MORE FEEDERS, THE CALCULATED LOAD FOR EACH SHALL
 INCLUDE NOT LESS THAN 1500 VOLT-AMPERES FOR EACH 2-WIRE
 SMALL-APPLIANCE BRANCH CIRCUIT. THESE LOADS SHALL BE
 PERMITTED TO BE INCLUDED WITH THE GENERAL LIGHTING LOAD
 AND SUBJECTED TO THE DEMAND FACTORS PROVIDED IN TABLE
 220.42.
  
 4} INDICATE THE LOCATION OF THE METER, MAIN DISCONNECT
 AND PANEL ON THE PLANS.
  
 5} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.INDICATE COMPLIANCE
 ON THE PLANS.
  
 6} PER 210.52 (E)(1) A RECEPTACLE IS REQUIRED AT THE
 FRONT OF THE RESIDENCE.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-26 Cont ID  
Sent By lmartine Date 2010-04-26 Time 09:33 Rev Time 0.00
Received By lmartine Date 2010-04-20 Time 09:31 Sent To  
Notes
2010-04-26 09:40:04MOVED TO R--20
2010-04-26 09:33:52R--15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-04 Cont ID  
Sent By rmcdouga Date 2010-03-04 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2010-02-16 Time 10:54 Sent To  
Notes
2010-02-17 10:55:28R--4

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2010-04-29 Cont ID  
Sent By rkussner Date 2010-04-29 Time 17:10 Rev Time 0.00
Received By rkussner Date 2010-04-29 Time 17:10 Sent To  
Notes
2010-04-29 17:11:52***LANDSCAPE REVIEW NOT REQUIRED WITH THIS PERMIT***
  
 A SEPARATE LANDSCAPE PERMIT IS REQUIRED.
  
 A SEPARATE IRRIGATION PERMIT IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-02-26 Cont ID  
Sent By rkussner Date 2010-02-26 Time 14:30 Rev Time 0.00
Received By rkussner Date 2010-02-26 Time 14:30 Sent To  
Notes
2010-02-26 15:02:49***LANDSCAPE REVIEW FAILED***
  
 1. APPLY FOR A SEPARATE LANDSCAPE PERMIT. SUBMIT TWO
 COPIES OF THE LANDSCAPE PLAN ALONG WITH THE TABULATION
 NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE
 XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS,
 INCLUDING THE XERISCAPE DESIGN OPTIONS.
  
 2. THE PROPOSED TREES AND PLANTING IN THE RIGHT-OF-WAY
 WILL REQUIRE APPROVAL FROM THE CITY ENGINEERING
 DEPARTMENT.
  
 3. PLEASE APPLY FOR AN IRRIGATION AND LIGHTING PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop Z ZONING
Rev No 2 Status P Date 2010-04-29 Cont ID  
Sent By eschneid Date 2010-04-29 Time 16:16 Rev Time 0.75
Received By eschneid Date 2010-04-29 Time 16:16 Sent To  
Notes
2010-04-29 16:45:51PASSED W/PROVISO
  
 1) REPEAT COMMENT: AN EASEMENT RELEASE SHALL BE
 PROVIDED FOR THE PORTION OF THE SUNDECK THAT IS
 PROPOSED WITHIN THE UTILITY EASEMENT ON THE NORTH
 PROPERTY LINE. THE EASEMENT RELEASE IS TO BE PROVIDED
 FROM THE EASEMENT HOLDERS TO THE PROPERTY OWNER, NOT
 FROM THE PROPERTY OWNER TO THE UTILITIES. PLEASE SEND
 THE CITY FORM, WITH THE PLANS, TO FPL, FPU, BELLSOUTH
 AND COMCAST FOR THEIR REVIEW AND APPROVAL. NOTE: THIS
 IS A PROVISO ITEM. THE EASEMENT RELEASE SHALL BE
 PROVIDED PRIOR TO THE FINAL INSPECTIONS FOR THIS WORK.
  
 2) SEPARATE PERMITS ARE REQUIRED FOR THE DRIVEWAY, THE
 FENCE, IRRIGATION, THE DRIVEWAY APPROACH AND THE
 LANDSCAPE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446

Review Stop Z ZONING
Rev No 1 Status F Date 2010-03-01 Cont ID  
Sent By eschneid Date 2010-03-01 Time 11:53 Rev Time 0.75
Received By eschneid Date 2010-03-01 Time 11:53 Sent To  
Notes
2010-03-01 11:55:04FAILED
  
 1) PROVIDE A SURVEY, LESS THEN A YEAR OLD, WHICH SHOWS
 DIMENSIONS TO THE PROPERTY LINE OF ALL EXISTING
 STRUCTURES.
  
 2) PROVIDE THE ROOF OVERHANG DIMENSION ON THE ELEVATION
 DRAWINGS.
  
 3) PROVIDE THE HEIGHT, AS DEFINED BE THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS, FOR THE NEW CUPOLA ON
 THE ELEVATION DRAWINGS.
  
 4) PROVIDE THE SETBACK DIMENSION OF THE SHOWER
 STRUCTURE ON THE SITE PLAN. PLEASE NOTE THAT THIS SHALL
 BE A MINIMUM OF FIVE (5) FEET FROM THE EAST PROPERTY
 LINE.
  
 5) THE ENTRY ARBOR IS NOT PERMITTED WITHIN THE FRONT
 SETBACK (25 FEET).
  
 6) PLEASE PROVIDE THE SETBACK DIMENSION OF THE POOL
 EQUIPMENT. PLEASE NOTE THAT THE POOL EQUIPMENT SHALL
 NOT EXTEND MORE THAN FOUR (4) FEET INTO THE REQUIRED
 SETBACK.
  
 7) AN EASEMENT RELEASE SHALL BE PROVIDED FOR THE
 PORTION OF THE SUNDECK THAT IS PROPOSED WITHIN THE
 UTILITY EASEMENT ON THE NORTH PROPERTY LINE.
  
 8) PROVIDE VERIFICATION ON THE PLANS THAT THE FRONT
 YARD CONTAINS THE LESSER OF 1,000 SQUARE FEET OR 75
 PERCENT LANDSCAPING IN ACCORDANCE WITH SECTION 94-482
 OF THE ZLDR.
  
 9) THE VALUE OF THE CONSTRUCTION ($77,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($63,776) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. THE
 LANDSCAPE IMPROVEMENTS SHALL BE SUBMITTED AS A SEPARATE
 LANDSCAPE PERMIT. THE LANDSCAPE PERMIT SHALL BE
 SUBMITTED PRIOR TO THE APPROVAL OF THIS PERMIT BY THE
 ZONING DIVISION.
  
 10) SEPARATE PERMITS ARE ALSO REQUIRED FOR THE
 DRIVEWAY, THE FENCE, IRRIGATION, THE EXTERIOR LIGHTING
 AND THE POOL.
  
 11) THE TREES SHOWN IN THE RIGHT-OF-WAY AND THE
 DRIVEWAY APPROACH REQUIRE SEPARATE PERMIT APPROVALS
 FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446