Plan Review Details - Permit 10020360
Plan Review Stops For Permit 10020360
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-01 Cont ID  
Sent By rmcdouga Date 2010-03-01 Time 10:35 Rev Time 0.00
Received By rmcdouga Date 2010-03-01 Time 10:04 Sent To  
Notes
2010-03-01 10:35:28DENIED BY BUILDING
  
 1) THE CONTRACTOR WILL NEED TO BE SPECIFIED BEFORE THE
 PERMIT CAN BE ISSUED.
  
 2) THE VALUE OF THE WORK SPECIFIED IS TOO LOW. PLEASE
 INDICATE THE CORRECT VALUE.
  
 3) THE PLAN REVIEW FEES HAVE NOT BEEN PAID.
  
 4) FBC 11-4.7.7 REQUIRES CURB RAMPS TO HAVE DETECTABLE
 WARNINGS EXTENDING THE FULL WIDTH AND DEPTH OF THE CURB
 RAMP. SHOW COMPLIANCE. SEE MARK-UP ON SHEET A1-1.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-23 Cont ID  
Sent By dpalmer Date 2010-02-23 Time 11:23 Rev Time 0.00
Received By dpalmer Date 2010-02-23 Time 11:20 Sent To  
Notes
2010-02-23 11:22:36ALL ELEVATOR DISCONNECTS HAVE INCORRECT OVER CURRENT
 PROTECTION. MAXIMUM OF 175%.
  
 APPLIED VALUE IS TOO LOW FOR APPLIED SCOPE OF WORK.
  
 CONTRACTOR AS APPLIED IS NOT LICENSED FOR SCOPE OF
 WORK.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2010-02-24 Cont ID  
Sent By efabian Date 2010-02-24 Time 15:22 Rev Time 2.00
Received By efabian Date 2010-02-24 Time 15:22 Sent To  
Notes
2010-02-24 15:27:361. MINIMUM CLEARANCE OF 5 FEET BETWEEN PLANTING OF
 TREES AND UTILITIES PIPELINE NOT ACHIEVED AND
  
 2. SHOW PIPE SEGMENTS IN LINEAR FEET DIMENSIONS BETWEEN
 SEGMENT CONNECTIONS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-09 Cont ID  
Sent By rbrown Date 2010-03-09 Time 10:57 Rev Time 0.00
Received By rbrown Date 2010-03-09 Time 10:55 Sent To  
Notes
2010-03-09 10:57:44DIGITAL PLAN REVIEW TEST
 CITY CENTER
  
 1. INCREASE DOOR WIDTH AS PER NFPA 101, SECTION 7.2.1.
  
 2. FIRE HOSE VALVE APPEARS TO BE LOCATED IN TRAVEL PATH
 OF STAIRS. PLEASE SEE NFPA 14, THE STANDARD OF
 STANDPIPE SYSTEMS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-02-23 Cont ID  
Sent By rregueir Date 2010-02-23 Time 08:21 Rev Time 0.00
Received By rregueir Date 2010-02-23 Time 08:14 Sent To  
Notes
2010-02-23 08:21:55REVIEW #: 1ST - DIGITAL PLANS
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1-1.2: FIRE DAMPER IS REQUIRED IN THE 10X10
 SUPP;Y DUCT PENETRATING MEZZANINE LEVEL WALL IN
 ACCORDANCE WITH FBC-M 607.5.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-03-23 Cont ID  
Sent By lwagner Date 2010-03-23 Time 10:15 Rev Time 0.00
Received By lwagner Date 2010-03-23 Time 10:15 Sent To  
Notes
2010-03-23 10:21:35WATER PIPE FOR TOILET ROOMS #105 & 106 IS REQUIRED TO
 BE 2" FBC PLUMBING 2007 TABLE 603.1
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-03-18 Cont ID  
Sent By kdfreema Date 2010-03-18 Time 09:40 Rev Time 0.00
Received By kdfreema Date 2010-03-18 Time 09:40 Sent To  
Notes
2010-03-18 09:46:07***PROVISO***
  
 PLEASE ENSURE THAT ALL PLANS ARE FOLLOWED DURING
 CONSTRUCTION. ANY CHANGED WILL NEED TO BE RESUBMITTED
 FOR REVIEW.