Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-03-15 Cont ID  
Sent By hmoser Date 2010-03-15 Time 09:09 Rev Time 0.00
Received By hmoser Date 2010-03-15 Time 09:08 Sent To  
Notes
2010-03-15 09:11:02PASS PROVISO
 REFER TO SECTION 401.5 FBC (M)
 PLAN REVIEW BY HAEOLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-01-27 Cont ID  
Sent By rregueir Date 2010-01-27 Time 10:57 Rev Time 0.00
Received By rregueir Date 2010-01-26 Time 20:46 Sent To  
Notes
2010-01-27 10:57:21**PROVISOS**
  
 1. SUPPLY DUCT PENETRATION OF SHAFT SHALL BE PROTECTED
 WITH FIRE DAMPER IN ACCORDANCE WITH FBC-M 607.5.
  
 2. GREASE DUCT SHALL BE CONTINUOUSLY COVERED BY FIRE
 WRAP SYSTEM FROM POINT OF SHAFT PENETRATION TO OUTLET
 TERMINAL IN ACCORDANCE WITH FBC-M 506.3.10.
  
 3. HORIZONTAL GREASE DUCT SHALL BE PROVIDED WITH
 CLEANOUT(S) IN ACCORDANCE WITH FBC-M 506.3.9.
  
 4. SHOW HOW ANGLE SUPPORTS ARE TO BE ATTACHED TO GREASE
 DUCT IN ACCORDANCE WITH FBC-M 506.3.3. ALSO, PROVIDE
 DETAIL FOR SUPPRTS ON VERTICAL SUPPLY DUCT IN
 ACCORDANCE WITH FBC-M 603.3.
  
 5. PROVIDE SUPPLY AND EXHAUST FAN MANUFACTURER'S WIND
 RESISTANCE DATA IN ACCORDANCE WITH FBC-M 301.12.
  
 SUBMIT REVISED PLANS ADDRESSING ALL OF THE ABOVE ISSUES
 PRIOR TO INSPECTION.
  
 SEPARATE FIRE SUPPRESSION PERMIT REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]