Plan Review Details - Permit 10010409
Plan Review Stops For Permit 10010409
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-15 Cont ID  
Sent By btrobaug Date 2010-03-15 Time 10:59 Rev Time 0.00
Received By btrobaug Date 2010-03-15 Time 10:51 Sent To ENG
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-02 Cont ID  
Sent By btrobaug Date 2010-02-01 Time 12:32 Rev Time 0.00
Received By btrobaug Date 2010-02-01 Time 12:20 Sent To I
Notes
2010-02-01 12:32:14 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1
  
 1} INDICATE THE SPACING OF THE FENCE FROM THE GENERATOR
 TO SHOW COMPLIANCE WITH 110.26 2008 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2010-03-24 Cont ID  
Sent By efabian Date 2010-03-24 Time 14:35 Rev Time 0.50
Received By efabian Date 2010-03-24 Time 14:34 Sent To Z
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2010-02-02 Cont ID  
Sent By btrobaug Date 2010-02-02 Time 11:38 Rev Time 1.00
Received By dlauderm Date 2010-02-02 Time 10:34 Sent To  
Notes
2010-02-02 10:36:52FAILED.
 SEE J. ROACHES COMMENTS, I WILL NOT REPEAT THEM FOR
 THIS REVIEW.
 1. SUBMIT NEW EASEMENT CONSENT FORM FOR THESE FENCES,
 THE ONE THAT IS ATTACHED IS FOR A FENCE TO SURROUND THE
 WHOLE PROPERTY WITH 6' CHAIN LINK.
 2. SUBMIT UNDER CORRECT ADDRESS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-30 Cont ID  
Sent By shill Date 2010-03-30 Time 10:46 Rev Time 0.00
Received By shill Date 2010-03-30 Time 10:46 Sent To  
Notes
2010-03-30 10:46:10TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-22 Cont ID  
Sent By dpalmer Date 2010-02-22 Time 10:27 Rev Time 0.00
Received By dpalmer Date 2010-02-22 Time 10:27 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-02 Cont ID  
Sent By btrobaug Date 2010-02-02 Time 11:38 Rev Time 0.00
Received By btrobaug Date 2010-01-21 Time 10:41 Sent To  
Notes
2010-02-02 11:39:37TO SMALL PLAN HOLDING BIN UNDER ""J"./WRT.
2010-01-25 10:40:58IN ZONING BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2010-04-05 Cont ID  
Sent By jroach Date 2010-04-05 Time 08:29 Rev Time 0.00
Received By jroach Date 2010-04-05 Time 08:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2010-03-11 Cont ID  
Sent By jroach Date 2010-03-11 Time 16:57 Rev Time 0.00
Received By jroach Date 2010-03-11 Time 16:57 Sent To E
Notes
2010-03-11 17:00:28ZONING PLAN REVIEW
  
 PERMIT NO.: 10010409
 ADDRESS: 1600 NORTH FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: JUNE GAISHIN
 TELEPHONE NO.: 561.784.1444
 SCOPE OF REVIEW: FENCE AROUND GENERATOR, DUMPSTER
 ENCLOSURE, AND COOLING TOWER.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PLANS SHALL NOTE THE PROPOSED HEIGHT OF THE FENCE
 SURROUNDING THE GENERATOR AND COOLING TOWER. FENCE
 SHALL BE AT LEAST EIGHT (8) FEET IN HEIGHT (SOLID FROM
 TOP TO BOTTOM). A 6 FOOT TALL PANEL PLACED 2 FEET OFF
 OF THE GROUND IS NOT SUFFICIENT.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-01-28 Cont ID  
Sent By jroach Date 2010-01-28 Time 16:31 Rev Time 0.00
Received By jroach Date 2010-01-28 Time 16:31 Sent To E
Notes
2010-01-28 16:34:56ZONING PLAN REVIEW
  
 PERMIT NO.: 10010409
 ADDRESS: 1600 NORTH FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: JUNE GAISHIN
 TELEPHONE NO.: 561.784.1444
 SCOPE OF REVIEW: FENCE AROUND GENERATOR, DUMPSTER
 ENCLOSURE, AND COOLING TOWER.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) DIMENSION PROVIDE FOR THE DUMPSTER ENCLOSURE DO NOT
 MEET THE MINIMUM DIMENSION REQUIRED BY THE CITY???S
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 2) SUFFICIENT CLEARANCE SHALL BE PROVIDED AROUND THE
 GENERATOR. THE PLANS PROVIDED ARE UNCLEAR AS TO THE
 EXACT LOCATION OF THE PROPOSED FENCE. CONSIDER USING
 SHEETS SP1 AND RP1 THAT WERE DEVELOPED FOR THE OVERALL
 SITE DEVELOPMENT.
  
 3) PLANS SHALL NOTE THE PROPOSED HEIGHT OF THE FENCE
 SURROUNDING THE GENERATOR AND COOLING TOWER. FENCE
 SHALL BE AT LEAST EIGHT (8) FEET IN HEIGHT.
  
 4) AN EASEMENT CONSENT FORM WAS SUBMITTED FOR 1,666
 LINEAR FEET OF NEW FENCING, WITH JUST ONE ATTACHED
 PLAN, HOWEVER, THE SITE PLANS FOR THE PERMIT ONLY SHOW
 THE FENCING FOR THE GENERATOR, COOLING TOWER, AND
 DUMPSTER ENCLOSURE. PLEASE CLARIFY THE SCOPE OF THE
 PERMIT. IF THE PERIMTER FENCING IS NOT A PART OF THIS
 SCOPE OF THIS PERMIT, PLEASE REMOVE THE EASEMENT
 CONSENT FORM FROM THIS PACKAGE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  