 |
Plan Review Details - Permit 10010404
Plan Review Stops For Permit 10010404 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2010-03-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-24 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-24 |
Time |
16:21 |
Sent To |
|
|
Notes |
2010-03-24 16:22:03 | PROVISO - PROVIDE REVISED ENGINEERING AT INSPECTION | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2010-03-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-16 |
Time |
08:19 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-16 |
Time |
08:19 |
Sent To |
|
|
Notes |
2010-03-16 08:22:46 | CORRECTIONS | | (COURTESY REVIEW, CONTRACTOR REQUEST) | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | FROM PROVISO LIST, NOT ADDRESSED: | | | | 1. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT | | FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER | | (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO | | HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT | | WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE | | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT | | BE NOTARIZED. | | | | 2. TWO SIGNED, SEALED IDENTICAL SETS OF DOCUMENTS | | REQUIRED FOR PERMIT ISSUANCE. ONE SET IS NOT SEALED, | | THE OTHER HAS A PHOTOCOPY SIGNATURE. THIS SET HAS BEEN | | RETAINED. SEE FS471, OR CONTACT FBPE FOR MORE | | INFORMATION. IF THEY DETERMINE THAT A PHOTOCOPY IS | | ACCEPTABLE, CONTRARY TO PREVIOUS DISCUSSIONS AND | | FLORIDA STATUTE, PLEASE ADVISE. | | | | NEW COMMENT: | | | | 3. INSTALLATION PROPOSED EXCEEDS THE SIZE OF | | ENGINEERING (ENGINEERING SHOWS A 2'3" PROJECTION, | | INSTALLATION PROPOSED IS 4'). AS THE PLANS ARE TO BE | | REVISED BY THE ENGINEER, PLEASE ADDRESS ITEMS 1 AND 2 | | AT THIS TIME. PLANS ARE TO BE SIGNED, SEALED, DATED | | ORIGINALS. PLEASE DO NOT SUBMIT UNSEALED PHOTOCOPIES OR | | PHOTOCOPY SIGNATURES UNLESS SUPPORTED FBPE. | | | | 3RD REVIEW COMMENT: | | | | CONTRACTOR STATED THAT THE 4' PROJECTION IS INCLUDED IN | | THE ENGINEERING. PLEASE SEE NOTES, "HEIGHT SHALL BE | | EQUAL TO OR LARGER THAN PROJECTION". PLEASE REVISE. | | | | 4. PLEASE PROVIDE TWO COLLATED IDENTICAL SETS OF PLANS | | FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE MARKED "VOID" | | TO AVOID CONFUSION AND DELAYS. | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2010-03-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-03-08 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-03-08 |
Time |
13:55 |
Sent To |
|
|
Notes |
2010-03-08 14:02:42 | CORRECTIONS | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | FROM PROVISO LIST, NOT ADDRESSED: | | | | 1. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT | | FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER | | (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO | | HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT | | WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE | | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT | | BE NOTARIZED. | | | | 2. TWO SIGNED, SEALED IDENTICAL SETS OF DOCUMENTS | | REQUIRED FOR PERMIT ISSUANCE. ONE SET IS NOT SEALED, | | THE OTHER HAS A PHOTOCOPY SIGNATURE. THIS SET HAS BEEN | | RETAINED. SEE FS471, OR CONTACT FBPE FOR MORE | | INFORMATION. IF THEY DETERMINE THAT A PHOTOCOPY IS | | ACCEPTABLE, CONTRARY TO PREVIOUS DISCUSSIONS AND | | FLORIDA STATUTE, PLEASE ADVISE. | | | | NEW COMMENT: | | | | 3. INSTALLATION PROPOSED EXCEEDS THE SIZE OF | | ENGINEERING (ENGINEERING SHOWS A 2'3" PROJECTION, | | INSTALLATION PROPOSED IS 4'). AS THE PLANS ARE TO BE | | REVISED BY THE ENGINEER, PLEASE ADDRESS ITEMS 1 AND 2 | | AT THIS TIME. PLANS ARE TO BE SIGNED, SEALED, DATED | | ORIGINALS. PLEASE DO NOT SUBMIT UNSEALED PHOTOCOPIES OR | | PHOTOCOPY SIGNATURES UNLESS SUPPORTED FBPE. | | | | 4. PLEASE PROVIDE TWO COLLATED IDENTICAL SETS OF PLANS | | FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE MARKED "VOID" | | TO AVOID CONFUSION AND DELAYS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2010-02-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-02-08 |
Time |
09:18 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-02-08 |
Time |
09:18 |
Sent To |
|
|
Notes |
2010-02-08 09:22:18 | ****PROVISO**** | | ****REVISION REQUIRED**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT | | FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER | | (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO | | HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT | | WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE | | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT | | BE NOTARIZED. | | | | 2. TWO SIGNED, SEALED IDENTICAL SETS OF DOCUMENTS | | REQUIRED FOR PERMIT ISSUANCE. ONE SET IS NOT SEALED, | | THE OTHER HAS A PHOTOCOPY SIGNATURE. THIS SET HAS BEEN | | RETAINED. SEE FS471, OR CONTACT FBPE FOR MORE | | INFORMATION. IF THEY DETERMINE THAT A PHOTOCOPY IS | | ACCEPTABLE, CONTRARY TO PREVIOUS DISCUSSIONS AND | | FLORIDA STATUTE, PLEASE ADVISE. | | | | CONTRACTOR IS ENCOURAGED TO ADDRESS PROVISOS WHEN | | RESUBMITTING FOR ZONING COMMENTS IN ORDER TO AVOID | | REVISION FEES. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2010-02-16 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2010-02-11 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2010-02-11 |
Time |
15:05 |
Sent To |
|
|
Notes |
2010-02-16 15:06:30 | IN ZONING BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2010-02-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-02-08 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-01-21 |
Time |
11:07 |
Sent To |
|
|
Notes |
2010-01-25 11:08:04 | IN ZONING BOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2010-03-05 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2010-03-05 |
Time |
08:57 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2010-03-05 |
Time |
08:57 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2010-02-01 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2010-02-01 |
Time |
15:33 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2010-02-01 |
Time |
15:33 |
Sent To |
B |
|
Notes |
2010-02-01 15:40:33 | FAILED | | | | 1) THE BROADWAY MIXED USE DISTRICT REQUIRES AWNINGS TO | | PROJECT A MINIMUM OF 4 FEET FROM THE BUILDING FACADE. | | THE ZONING VARIANCE APPROVAL LETTER INCLUDED WITH THE | | APPLICATION INCLUDED A CONDITION AND DRAWINGS FOR A 4 | | FOOT PROJECTION. THE DRAWING SIGNED AND SEALED BY THE | | STRUCTURAL ENGINEER CALLS OUT A 2 FEET 3 INCH AWNING | | PROJECTION. | | | | PLEASE NOTE THAT THE AWNING PROJECTS OVER THE BROADWAY | | RIGHT-OF-WAY AND MAY REQUIRE A FDOT PERMIT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |