Plan Review Details - Permit 10010404
Plan Review Stops For Permit 10010404
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-03-24 Cont ID  
Sent By shill Date 2010-03-24 Time 16:21 Rev Time 0.00
Received By shill Date 2010-03-24 Time 16:21 Sent To  
Notes
2010-03-24 16:22:03PROVISO - PROVIDE REVISED ENGINEERING AT INSPECTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 08:19 Rev Time 0.00
Received By shill Date 2010-03-16 Time 08:19 Sent To  
Notes
2010-03-16 08:22:46CORRECTIONS
 (COURTESY REVIEW, CONTRACTOR REQUEST)
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PROVISO LIST, NOT ADDRESSED:
  
 1. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 2. TWO SIGNED, SEALED IDENTICAL SETS OF DOCUMENTS
 REQUIRED FOR PERMIT ISSUANCE. ONE SET IS NOT SEALED,
 THE OTHER HAS A PHOTOCOPY SIGNATURE. THIS SET HAS BEEN
 RETAINED. SEE FS471, OR CONTACT FBPE FOR MORE
 INFORMATION. IF THEY DETERMINE THAT A PHOTOCOPY IS
 ACCEPTABLE, CONTRARY TO PREVIOUS DISCUSSIONS AND
 FLORIDA STATUTE, PLEASE ADVISE.
  
 NEW COMMENT:
  
 3. INSTALLATION PROPOSED EXCEEDS THE SIZE OF
 ENGINEERING (ENGINEERING SHOWS A 2'3" PROJECTION,
 INSTALLATION PROPOSED IS 4'). AS THE PLANS ARE TO BE
 REVISED BY THE ENGINEER, PLEASE ADDRESS ITEMS 1 AND 2
 AT THIS TIME. PLANS ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. PLEASE DO NOT SUBMIT UNSEALED PHOTOCOPIES OR
 PHOTOCOPY SIGNATURES UNLESS SUPPORTED FBPE.
  
 3RD REVIEW COMMENT:
  
 CONTRACTOR STATED THAT THE 4' PROJECTION IS INCLUDED IN
 THE ENGINEERING. PLEASE SEE NOTES, "HEIGHT SHALL BE
 EQUAL TO OR LARGER THAN PROJECTION". PLEASE REVISE.
  
 4. PLEASE PROVIDE TWO COLLATED IDENTICAL SETS OF PLANS
 FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE MARKED "VOID"
 TO AVOID CONFUSION AND DELAYS.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-03-08 Cont ID  
Sent By shill Date 2010-03-08 Time 13:55 Rev Time 0.00
Received By shill Date 2010-03-08 Time 13:55 Sent To  
Notes
2010-03-08 14:02:42CORRECTIONS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PROVISO LIST, NOT ADDRESSED:
  
 1. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 2. TWO SIGNED, SEALED IDENTICAL SETS OF DOCUMENTS
 REQUIRED FOR PERMIT ISSUANCE. ONE SET IS NOT SEALED,
 THE OTHER HAS A PHOTOCOPY SIGNATURE. THIS SET HAS BEEN
 RETAINED. SEE FS471, OR CONTACT FBPE FOR MORE
 INFORMATION. IF THEY DETERMINE THAT A PHOTOCOPY IS
 ACCEPTABLE, CONTRARY TO PREVIOUS DISCUSSIONS AND
 FLORIDA STATUTE, PLEASE ADVISE.
  
 NEW COMMENT:
  
 3. INSTALLATION PROPOSED EXCEEDS THE SIZE OF
 ENGINEERING (ENGINEERING SHOWS A 2'3" PROJECTION,
 INSTALLATION PROPOSED IS 4'). AS THE PLANS ARE TO BE
 REVISED BY THE ENGINEER, PLEASE ADDRESS ITEMS 1 AND 2
 AT THIS TIME. PLANS ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. PLEASE DO NOT SUBMIT UNSEALED PHOTOCOPIES OR
 PHOTOCOPY SIGNATURES UNLESS SUPPORTED FBPE.
  
 4. PLEASE PROVIDE TWO COLLATED IDENTICAL SETS OF PLANS
 FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE MARKED "VOID"
 TO AVOID CONFUSION AND DELAYS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-02-08 Cont ID  
Sent By shill Date 2010-02-08 Time 09:18 Rev Time 0.00
Received By shill Date 2010-02-08 Time 09:18 Sent To  
Notes
2010-02-08 09:22:18****PROVISO****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 2. TWO SIGNED, SEALED IDENTICAL SETS OF DOCUMENTS
 REQUIRED FOR PERMIT ISSUANCE. ONE SET IS NOT SEALED,
 THE OTHER HAS A PHOTOCOPY SIGNATURE. THIS SET HAS BEEN
 RETAINED. SEE FS471, OR CONTACT FBPE FOR MORE
 INFORMATION. IF THEY DETERMINE THAT A PHOTOCOPY IS
 ACCEPTABLE, CONTRARY TO PREVIOUS DISCUSSIONS AND
 FLORIDA STATUTE, PLEASE ADVISE.
  
 CONTRACTOR IS ENCOURAGED TO ADDRESS PROVISOS WHEN
 RESUBMITTING FOR ZONING COMMENTS IN ORDER TO AVOID
 REVISION FEES.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-16 Cont ID  
Sent By lmartine Date 2010-02-11 Time 15:05 Rev Time 0.00
Received By lmartine Date 2010-02-11 Time 15:05 Sent To  
Notes
2010-02-16 15:06:30IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-08 Cont ID  
Sent By shill Date 2010-02-08 Time 09:38 Rev Time 0.00
Received By shill Date 2010-01-21 Time 11:07 Sent To  
Notes
2010-01-25 11:08:04IN ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2010-03-05 Cont ID  
Sent By eschneid Date 2010-03-05 Time 08:57 Rev Time 0.50
Received By eschneid Date 2010-03-05 Time 08:57 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-02-01 Cont ID  
Sent By eschneid Date 2010-02-01 Time 15:33 Rev Time 0.25
Received By eschneid Date 2010-02-01 Time 15:33 Sent To B
Notes
2010-02-01 15:40:33FAILED
  
 1) THE BROADWAY MIXED USE DISTRICT REQUIRES AWNINGS TO
 PROJECT A MINIMUM OF 4 FEET FROM THE BUILDING FACADE.
 THE ZONING VARIANCE APPROVAL LETTER INCLUDED WITH THE
 APPLICATION INCLUDED A CONDITION AND DRAWINGS FOR A 4
 FOOT PROJECTION. THE DRAWING SIGNED AND SEALED BY THE
 STRUCTURAL ENGINEER CALLS OUT A 2 FEET 3 INCH AWNING
 PROJECTION.
  
 PLEASE NOTE THAT THE AWNING PROJECTS OVER THE BROADWAY
 RIGHT-OF-WAY AND MAY REQUIRE A FDOT PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.