Plan Review Details - Permit 10010306
Plan Review Stops For Permit 10010306
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-04-05 Cont ID  
Sent By jwitmer Date 2010-04-05 Time 10:30 Rev Time 2.50
Received By jwitmer Date 2010-04-05 Time 08:00 Sent To  
Notes
2010-04-05 10:48:27BUILDING PLAN REVIEW
 PERMIT: 10010306
 ADD: 1301 SUMMIT BLVD
 CONT: WESLEY CONSTRUCTION CO.
 TEL: (561)310-5834
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 MONDAY APRIL 05/2010
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) FLOOD ZONE CERTIFICATE REQUIRED AFTER SLAB IS
 POURED, MINIMUM SLAB HEIGHT OF 12'-6" NGVD A-7 FLOOD
 ZONE. FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 MARCH 31, 2012.
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS
 NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES
 MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED
 ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW
 FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) ROOFING PERMIT WILL REQUIRE A SEPARATE REVIEW AND
 ASSOCIATED FEES. NOTE, CALCULATIONS FOR WIND PRESSURE,
 EXPOSURE "C" WERE SUBMITTED BY TUMAY CONSULTING
 ENGINEERS, INC FOR THE MWFRS AS WELL AS FOR COMPONENTS
 AND CLADDING PROVIDING THE POSITIVE AND NEGATIVE
 PRESSURES FOR THIS STRUCTURE BUT NO ENHANCED FASTENING
 CALCULATIONS WERE SUBMITTED (RAS 117) FOR THE AMOUNT OF
 FASTENERS REQUIRED PER ROW AND AMOUNT OR ROWS.
 MIAMI-DADE NOA: 08-0227.09
 CERTAIN TEED MODIFIED BITUMEN ROOFING SYSTEMS OVER WOOD
 DECK
 PAGE 38 HIGHLIGHTED
 MAXIMUM DESIGN PRESSURE -60PSF (SEE GENERAL LIMITATION#
 7).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-01-27 Cont ID  
Sent By jwitmer Date 2010-01-27 Time 09:57 Rev Time 2.00
Received By jwitmer Date 2010-01-27 Time 08:00 Sent To  
Notes
2010-01-27 09:58:19BUILDING PLAN REVIEW
 PERMIT: 10010306
 ADD: 1301 SUMMIT BLVD
 CONT: WESLEY CONSTRUCTION CO.
 TEL: (561)310-5834
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 JAN. 27/ 2010
  
 1) SHEET S-1 CARPENTRY NOTE (A) INDICATES COMPLIANCE
 WITH 2319 FBC-BUILDING. THIS CODE SECTION IS FOR THE
 HIGH- VELOCITY HURRICANE ZONES DADE & BROWARD COUNTIES
 ONLY.
  
 2) SHEET S-1 WINDOW BUCK DETAILS WITH OUT REVIEWING THE
 STOREFRONT WINDOW PRODUCT APPROVALS PLEASE BEWARE OF
 SECTION 1714.5.4.2 WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUB-FRAME SYSTEM OR THROUGH THE FLANGE TO THE SECURED
 WOOD BUCK IN ACCORDANCE WITH THE MANUFACTURER'S
 PUBLISHED INSTALLATION INSTRUCTIONS. UNLESS OTHERWISE
 TESTED, BUCKS SHALL EXTEND BEYOND THE INTERIOR FACE OF
 THE WINDOW OR DOOR FRAME SUCH THAT FULL SUPPORT OF THE
 FRAME IS PROVIDED.
  
 3) S-1 THE TERMITE TREATMENT CODE SECTIONS ARE FROM THE
 RESIDENTIAL CODE NOT THE COMMERCIAL BUILDING CODE
 PLEASE ADDRESS CODE SECTIONS 1816.1.(1-8).
  
 4) IN BOTH THE PLYWOOD ROOF SHEAR DIAPHRAGM SCHEDULE AS
 WELL AS THE ROOF ZONING DIAGRAM, BOTH ARE GENERIC
 DETAILS, FOR EXAMPLE THIS IS A FLAT ROOF AS FAR AS
 SLOPE IS CONCERNED. THE PRESSURES FOR THE ROOF ZONING
 DETAIL WOULD BE OK FOR THE ROOF FRAMING MEMBERS
 TRIBUTARY AREA WHEN CONSIDERING PART OF THE MWFRS. WHEN
 REVIEWING FOR THE ROOF ZONES AS PART OF THE COMPONENTS
 AND CLADDING WE WILL BE REVIEWING AT THE TRIBUTARY AREA
 OF EACH FASTENER, 140 MPH/ 0-7 DEGREES, EFFECTIVE WIND
 AREA 10 SQ FT AND A EXPOSURE C.
 THE PARAPET HEIGHT BEING 16???-0??? ABOVE GRADE THIS
 WILL CREATE A ADJUSTMENT FACTOR OF 1.29, THE 1.29
 ADJUSTMENT FACTOR TIMES THE -89PSF= -114.81. THIS IS
 NOT THE WHOLE OF THE EQUATION, TOPOGRAPHICAL FACTORS AT
 FACTORED IN!
 THE MINIMUM NEGATIVE PRESSURE FOR THIS ZONE WOULD BE
 APPROXIMATELY -114.8. PLEASE REVIEW ASCE7-05 CHAPTER 6
 FIGURE 6-3.
 PLEASE REVIEW PRESSURES FOR ALL THREE ROOF ZONES, ZONE
 1, 2 & 3.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 5A) STOREFRONT WINDOWS
 5B) EXTERIOR DOORS
 5C) SKYLIGHTS
 5D) ROOFING ASSEMBLIES
 5E) STORM SHUTTERS IF GLAZED OPENINGS ARE NOT LARGE
 MISSILE RATED
 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) REMAINDER OF PERMIT FEES $1,871.46.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-06 Cont ID  
Sent By btrobaug Date 2010-04-06 Time 16:29 Rev Time 0.00
Received By btrobaug Date 2010-04-06 Time 16:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-08 Cont ID  
Sent By dpalmer Date 2010-02-08 Time 10:02 Rev Time 0.00
Received By dpalmer Date 2010-02-08 Time 10:02 Sent To  
Notes
2010-02-08 10:02:27*DENIED*
  
  
 1) NOTE: PLEASE EXPLAIN THE SUBMITTAL OF METHOD B WHICH
 BE FOR PRESCRIPTIVE FOR SPACE BY SPACE OR SHELL
 BUILDINGS. WHEN USING METHOD B ALL SPACES INCLUDING
 EXTERIOR WOULD REQUIRE ALLOWANCES PER 13-415.AB.5,
 13-415.AB.2.2 FOR EACH SPECIFIC SPACE/AREA. IT IS NOT
 PERMISSIBLE TO USE ONE FORM *B* FOR ALL
 ROOMS/SPACES/AREAS.
 PLEASE SEE METHOD *A* WHEN APPLYING WHOLE BUILDING.
 LIGHTING POWER DENSITIES CAN NOT BE CONFIRMED WITHOUT A
 SPECIFIC FIXTURE LEGEND.
  
 2) NOTE: TITLE BLOCKS TO BE COMPLETE ON PLANS FOR ALL
 INFORMATION AS REQUIRED UNDER FAC 61G15-23.002.
  
 3) NOTE: EXTERIOR LIGHTING IS SHOWN ON A SP SWITCH
 HOWEVER ALSO MENTIONS SOME SORT OF TIMER. PLEASE SEE
 FBC 13-415.AB.1.4.
 MUST BE ONE OF THE TWO FOLLOWING TYPE OF CONTROLS OR
 BOTH. PHOTO-SENSOR TYPE OR ASTRONOMICAL TIME CLOCK WITH
 MINIMUM REQUIRED 10HR BACK UP FOR PROGRAMMING.
  
 4) NOTE: ALL CONTINUOUS LOADS ARE REQUIRED TO BE SHOWN
 AT 125%.
 215.3,230.42
  
 5) NOTE: PLEASE SHOW REQUIRED GROUNDING ELECTRODE
 SYSTEM AT THE DETACHED BUILDING PER 250.32, 250.50
  
 6) NOTE: PLEASE VERIFY THE NAMEPLATE RATING OF THE AHU
 AND THE REQUIRED MINIMUM SIZING. PLEASE SEE MINIMUM
 OVER CURRENT PROTECTION FOR AHU PER NEC 424.3. ( 125% )
  
 7) NOTE: PLEASE SEE 225.31-225.39 AS A DISCONNECTING
 MEANS IS REQUIRED AT DETACHED BUILDING. THE PANEL IS
 SHOWN AS A 100AMP MLO WHICH IS NOT ACCEPTABLE.
  
 8) NOTE: PLEASE SEE 440.11 AND 440.12 FOR MISSING AHU
 DISCONNECT.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2010-02-01 Cont ID  
Sent By dlauderm Date 2010-02-01 Time 10:15 Rev Time 1.00
Received By dlauderm Date 2010-02-01 Time 10:15 Sent To  
Notes
2010-02-01 10:16:50PASSED WITH PROVISO:
 NEED CERTIFIED ENGINEERS STATEMENT CONCERNING THE
 INCREASE IN IMPERVIOUS AREAS AND THE DECREASE IN
 PERVIOUS AREAS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-04-05 Cont ID  
Sent By mawillia Date 2010-04-05 Time 12:37 Rev Time 0.00
Received By mawillia Date 2010-04-05 Time 12:19 Sent To  
Notes
2010-04-05 12:35:55*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-2 AND E-1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-02-22 Cont ID  
Sent By mcarsill Date 2010-02-22 Time 08:12 Rev Time 0.00
Received By mcarsill Date 2010-02-22 Time 08:09 Sent To  
Notes
2010-02-22 08:12:541301 SUMMIT BOULEVARD
 PROPOSED KOALA EXHIBIT / PETTING AREA
 PERMIT # 10010306
  
 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 2. PROVIDE ILLUMINATED EXIT SIGNS AT EXIT DOOR
 LOCATIONS AND AT LEAST ONE PORTABLE FIRE EXTINGUISHER
 WITH A CURRENT SERVICE TAG.
  
 3. CORRECT ALL OTHER CODE RELATED COMMENTS FROM THE
 OTHER PLAN REVIEWERS OF THE CITY.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-04-26 Cont ID  
Sent By shill Date 2010-04-26 Time 14:54 Rev Time 0.00
Received By shill Date 2010-04-26 Time 14:54 Sent To  
Notes
2010-04-26 14:54:44BLDG SUBMITTAL ROUTED TO JW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-25 Cont ID  
Sent By lmartine Date 2010-03-24 Time 16:29 Rev Time 0.00
Received By lmartine Date 2010-03-24 Time 16:29 Sent To  
Notes
2010-04-06 16:45:55ROUTED TO DWISE DESK FOR PLUMBING REVIEW
  
 ----------------------------
2010-03-25 16:37:00C--30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-25 Cont ID  
Sent By lmartine Date 2010-03-01 Time 16:29 Rev Time 0.00
Received By lmartine Date 2010-01-19 Time 11:44 Sent To  
Notes
2010-01-21 11:44:37C-31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-04-14 Cont ID  
Sent By jwitmer Date 2010-04-14 Time 10:46 Rev Time 0.00
Received By jwitmer Date 2010-04-14 Time 10:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-04-06 Cont ID  
Sent By rregueir Date 2010-04-06 Time 16:45 Rev Time 0.00
Received By rregueir Date 2010-04-06 Time 16:45 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-02-01 Cont ID  
Sent By rregueir Date 2010-02-01 Time 15:12 Rev Time 0.00
Received By rregueir Date 2010-02-01 Time 15:06 Sent To  
Notes
2010-02-01 15:11:10REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. VENTILATION CALCULATIONS CALL FOR AIR EXHCHANGES PER
 HOUR. PLAN SHOWS EXHAUST FAN HANGING DETAIL BUT NO
 EXHAUST FAN LOCATIONS ARE SHOWN ON PLANS. ALSO, EXHAUST
 FANS ARE NOT SHOWN ON THE ELECTRICAL PLANS. SHOW ON
 PLANS HOW THE REQUIRED AIR EXCHANGES ARE TO BE ACHIEVED
 WITHOUT ANY EXHAUST OR SHOW THE EXHAUST ON THE PLANS,
 INCLUDING EXHAUST DISCHARGE LOCATION.
  
 2. THE PRINTED NAME AND LICENSE NUMBER OF THE ENGINEER
 SHALL APPEAR ON THE PLANS IN ACCORDANCE WITH FAC
 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-04-07 Cont ID  
Sent By lwagner Date 2010-04-07 Time 10:04 Rev Time 0.00
Received By lwagner Date 2010-04-07 Time 10:04 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-01-27 Cont ID  
Sent By kstevens Date 2010-01-27 Time 16:40 Rev Time 0.00
Received By kstevens Date 2010-01-27 Time 16:40 Sent To  
Notes
2010-01-27 16:46:51DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P1 & P2. THE TITLE BLOCKS FOR THE ENGINEER
 SHALL LEGIBLY INDICATE THE NAME AND LICENSE NUMBER OF
 THE ENGINEER AS WELL AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. FAC 61G15-23.002(2) & FS 471.025. (THE CA#
 EB-000306 IS NOT ON FILE).
  
 2. SHT P1 A TRAP IS REQUIRED ON THE SANITARY DRAIN FOR
 THE TRENCH DRAIN. SECTION 1002.1. PLEASE INDICATE IF
 THERE IS MORE THAN ONE DRAIN AS THIS IS NOT SHOWN ON
 THE RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-04-14 Cont ID  
Sent By jroach Date 2010-04-14 Time 08:43 Rev Time 0.00
Received By jroach Date 2010-04-14 Time 08:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-03-01 Cont ID  
Sent By jroach Date 2010-03-01 Time 14:16 Rev Time 0.00
Received By jroach Date 2010-03-01 Time 14:16 Sent To  
Notes
2010-03-01 14:16:26ZONING PLAN REVIEW
  
 PERMIT NO.: 10010306
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT: WESLEY CONSTRUCTION COMPANY ???
 CHARLES BRATNELL
 TELEPHONE NO.: 561.741.2963
 SCOPE OF REVIEW: NEW CONSTRUCTION OF 896 SQUARE FOOT
 ANIMAL EXHIBIT.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) SITE PLAN SHALL INDICATE THE SETBACKS OF THE
 PROPOSED STRUCTURE, AS MEASURED FROM THE PROPERTY LINE
 TO THE CLOSEST POINT OF THE STRUCTURE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved