Plan Review Details - Permit 10010259
Plan Review Stops For Permit 10010259
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-04-09 Cont ID  
Sent By lmartine Date 2010-04-09 Time 13:07 Rev Time 0.00
Received By lmartine Date 2010-04-09 Time 13:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-04-08 Cont ID  
Sent By rmcdouga Date 2010-04-08 Time 09:34 Rev Time 0.00
Received By rmcdouga Date 2010-04-08 Time 09:34 Sent To  
Notes
2010-04-08 09:41:162007 FBC W/2009 REVISIONS
 TEMPORARY SALES OFFICE
  
 DENIED BY BUILDING
  
 1) ITEM #8 FROM THE FIRST REVIEW HAS NOT BEEN
 ADDRESSED. SHOW COMPLIANCE WITH FBC 11-4.1.2(5) AND
 11-4.6 FOR ACCESSIBLE PARKING REQUIREMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-01-27 Cont ID  
Sent By rmcdouga Date 2010-01-27 Time 13:07 Rev Time 0.00
Received By rmcdouga Date 2010-01-27 Time 13:07 Sent To  
Notes
2010-01-27 09:02:182007 FBC W/2007 REVISIONS
 SALES OFFICE
  
 DENIED BY BUILDING
  
 1) THE GARAGE IS REQUIRED TO BE CONVERTED BACK TO THE
 ORIGINAL CONDITION WHEN THE TIME ALLOTED BY ZONING FOR
 THE TEMPORARY SALES OFFICE HAS EXPIRED.
  
 2) SPECIFY THE APPLICABLE CODE INFORMATION ON THE
 PLANS.
  
 3) SPECIFY THE WIND DESIGN DATA ON THE PLANS AS
 REQUIRED BY FBC 1603.1. SPECIFY THE BASIC WINDSPEED,
 IMPORTANCE FACTOR, EXPOSURE, COMPONENT AND CLADDING
 PRESSURES, ETC.
  
 4) SPECIFY THE HURRICANE STRAPS AND CONNECTORS THAT
 WILL BE USED ON THE EXTERIOR WOOD FRAME IN-FILL WALL AT
 THE GARAGE DOOR OPENING AND SUBMIT 2 COPIES OF PRODUCT
 APPROVALS FOR THEM AS REQUIRED BY DCA RULE 9B-72.
  
 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS AS REQUIRED BY DCA RULE
 9B-72.
  
 6) ELEVATION NOTE #2 ON SO-1 REFERENCE FBC
 2510.5.1/2517.5.11. ACCORDING TO THE 2007 FBC THE FIRST
 SECTION IS NOT RELEVANT AND THE SECOND DOES NOT EXIST.
 PLEASE CORRECT.
  
 7) THE SALES OFFICE IS REQUIRED TO BE EQUIPPED WITH A
 TOILET FACILITIES PER 2007 FBC PLUMBING SECTIONS 403.1,
 403.2 AND 403.4. THE PLANS SHOW THAT THE DOOR FROM THE
 GARAGE (SALES OFFICE) TO THE DWELLING UNIT IS TO BE
 BLOCKED OFF. IF THE SALES OFFICE AREA IS SEPARATED FROM
 THE DWELLING UNIT, THEN A TOILET FACILITY IS REQUIRED
 IN THE SALES OFFICE. IN ORDER FOR THE TOILET ROOM IN
 THE DWELLING UNIT TO BE USED THE DOOR CAN NOT BE
 BLOCKED AND BECAUSE FBC 11-4.1.1(4) REQUIRES TEMPORARY
 STRUCTURES TO COMPLY WITH ACCESSIBILITY, THE TOILET
 ROOM IS REQUIRED TO BE ON AN ACCESSIBLE ROUTE PER
 11-4.1.3 (11).
  
 8) SUBMIT TWO COPIES OF A SITE PLAN WITH DETAILS
 SHOWING COMPLIANCE WITH FBC 11-4.1.2 (5) AND 11-4.6 FOR
 ACCESSIBLE PARKING REQUIREMENTS AND ACCESSIBLE ROUTES.
  
 9) THE DOORS IN THE OFFICE AREA ARE REQUIRED TO COMPLY
 WITH FBC 11-4.13.6 FOR MANEUVERING CLEARANCES AND
 11-4.13.9 FOR HARDWARE.
  
 10) PROVIDE DETAILS OF PROPOSED DROPPED CEILING IN
 OFFICE AREA. SPECIFY HEIGHT, MATERIALS, AND STRUCTURAL
 DETAILS.
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-30 Cont ID  
Sent By btrobaug Date 2010-03-30 Time 14:01 Rev Time 0.00
Received By btrobaug Date 2010-03-30 Time 12:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-01 Cont ID  
Sent By dpalmer Date 2010-02-01 Time 15:34 Rev Time 0.00
Received By dpalmer Date 2010-02-01 Time 15:34 Sent To  
Notes
2010-02-01 15:34:42 
 ** DENIED REVIEW *
  
 1) NOTE: NO DESIGN CODES ON PLANS FOR PERMIT
 APPLICATION MADE AFTER OCTOBER 1ST, 2009.
 SHOULD HAVE THE FOLLOWING AT A MINIMUM.
 2008 NFPA-70
 2006 NFPA-101
  
 2) NOTE: MIXED USE OCCUPANCY CLASSIFICATION UNDER FBC
 CHAPTER 3. THIS IS A COMMERCIAL OFFICE SPACE.
 PLEASE SEE FBC CHAPTER 13, 13-415.AB.5 FOR LIGHTING
 PERFORMANCE CALCULATIONS. THE SUBMITTED FORM FOR
 RESIDENTIAL USE IS NOT ACCEPTABLE. THE PERSON PREPARING
 DOCUMENTS MUST HAVE AN ORIGINAL SIGNATURE. THE
 SUBMITTED FORM IS NOT ORIGINAL SIGNATURE.
 FBC 13-103.1
  
 3) NOTE: PLEASE SUBMIT PANEL SCHEDULE AND LOAD
 CALCULATIONS FOR OCCUPANCY AND ADJUST PER NEC
 220.12,220.14,220.42 ETC
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%.
 215.3, 230.42
  
 4) NOTE: PLEASE SEE NEC AND FBC FOR *TEMPORARY USE* AND
 TIME LIMITATIONS.
 RE-PLAT HOLD STILL ON SYSTEM TO BE ADDRESSED BEFORE USE
 PROPOSED. NEEDS TO BE A FEE SIMPLE TOWN-HOUSE. THIS IS
 NOT A MULTI-FAMILY BUILDING OR CONDO.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-04-06 Cont ID  
Sent By mawillia Date 2010-04-06 Time   Rev Time 0.00
Received By mawillia Date 2010-04-06 Time 10:15 Sent To  
Notes
2010-04-06 10:24:54*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; SINGLE PLAN SHEET SO-1 WAS STAMPED,
 INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-02-09 Cont ID  
Sent By mawillia Date 2010-02-09 Time 11:52 Rev Time 0.00
Received By mawillia Date 2010-02-09 Time 11:26 Sent To  
Notes
2010-02-09 11:52:52*****DENIED*****
  
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 ATTENTION: THE SCOPE OF WORK SHALL BE REVIEWED AS A NEW
 BUSINESS OCCUPANCY (CHAPTER 38 OF NFPA 101)
  
 3. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALLL BE
 REFERENCED.
  
 4. PROVIDE OCCUPANT LOAD CHARACTERISTIC OF THE USE OF
 THE SPACE.
  
 5. IT APPEARS THAT THERE WILL BE A SINGLE EXIT ONLY,
 SHOW THAT THE TOTAL DISTANCE FROM ANY POINT SHALL NOT
 EXCEED 100 FEET.
  
 6. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASAS B, OR CLASS C. SPECIFY
 INTERIOR FLOOR FIONISH IN TERMS OF CLASS I OR CLASS II.
  
 7. SHOW LOCATION OF THE 2A10:BC RATED PROTABLE FIRE
 EXTINGUISHER IN THE BUSINESS OCCUPANCY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-22 Cont ID  
Sent By lmartine Date 2010-03-18 Time 15:52 Rev Time 0.00
Received By lmartine Date 2010-03-18 Time 15:52 Sent To  
Notes
2010-03-22 15:52:59C--18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-02-09 Time   Rev Time 0.00
Received By shill Date 2010-01-19 Time 10:37 Sent To  
Notes
2010-01-19 10:37:18C 24
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-01-27 Cont ID  
Sent By rmcdouga Date 2010-01-27 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2010-01-27 Time 14:04 Sent To  
Notes
2010-01-27 14:05:59NO IMPACT FEES REQUIRED FOR TEMPORARY SALES OFFICE PER
 PHONE CONVERSATION WITH WILLIE SWOOPES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-02-02 Cont ID  
Sent By hmoser Date 2010-02-02 Time 10:09 Rev Time 0.00
Received By hmoser Date 2010-02-02 Time 10:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-04-06 Cont ID  
Sent By lwagner Date 2010-04-06 Time 10:09 Rev Time 0.00
Received By lwagner Date 2010-04-05 Time 14:45 Sent To  
Notes
2010-04-05 15:09:28DUE TO TEMPORARY USE, WATER COOLER WILL BE USED.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-01-20 Cont ID  
Sent By kstevens Date 2010-01-20 Time 14:46 Rev Time 0.00
Received By kstevens Date 2010-01-20 Time 14:46 Sent To  
Notes
2010-01-20 14:50:35DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 1. PER TABLE 403.1 A TOILET ROOM AND A DRINKING
 FOUNTAIN ARE REQUIRED.
  
 2. PER SECTION 11-4.1.3 THE PROVIDED TOILET ROOM SHALL
 BE ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING THE
 LOCATION OF THE ACCESSIBLE TOILET ROOM AND COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19, & 11-4.22 WITH ALL
 SUBSECTIONS.
  
 3. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2010-04-08 Cont ID  
Sent By eschneid Date 2010-04-08 Time 15:56 Rev Time 0.50
Received By eschneid Date 2010-04-08 Time 15:56 Sent To  
Notes
2010-04-08 16:09:16PASSED
  
 1) THE TEMPORARY SALES OFFICE FEATURES SHALL BE SHOWN
 ON THE PENDING MINOR PD AMENDMENT.
  
 2) NOTE: PER ORDINANCE NUMBER 4221-09, THE DEVELOPER'S
 SALES OFFICE SHALL PROMINENTLY DISPLAY A SIGN AT A
 MINIMUM SIZE OF ONE AND A HALF (1.5) FEET X TWO (2)
 FEET STATING, "THIS PROJECT CONTAINS WORKFORCE HOUSING
 UNITS". THE SIGN SPECIFICATIONS AND LOCATION SHALL BE
 SHOWN ON THE TEMPORARY MODEL DWELLING UNIT PLANS
 INCLUDED AS PART OF THIS PERMIT.
  
 3) NOTE: PER ORDINANCE NUMBER 4221-09:
  
 A) DEVELOPER SHALL DISCLOSE THE EXISTENCE OF WORKFORCE
 HOUSING UNITS TO ALL PURCHASERS OF UNITS WITHIN OAKTON
 PRESERVE AND SHALL DISCLOSE THE RESTRICTIVE COVENANTS
 REGARDING THE WORKFORCE HOUSING TO ALL QUALIFIED BUYERS
 OF SUCH WORKFORCE HOUSING UNITS.
  
 B) THE OAKTON PRESERVE PORTION OF THE CPD WILL BE
 SUBJECT TO A DECLARATION CREATING A HOMEOWNERS
 ASSOCIATION. THE DECLARATION OF SUCH ASSOCIATION SHALL
 DISCLOSE IN ALL CAPITALIZED AND UNDERLINED WORDING THAT
 THE DEVELOPMENT INCLUDES 13 WORKFORCE HOUSING UNITS.
  
 C) PRIOR TO THE FIRST CONVEYANCE OF ANY INDIVIDUAL UNIT
 OR THE ISSUANCE OF THE BUILDING PERMIT FOR THE THIRD
 RESIDENTIAL BUILDING TO BE CONSTRUCTED, WHICHEVER FIRST
 OCCURS, THE DEVELOPER SHALL RECORD THE OAKTON PRESERVE
 PLAT, IN THE PUBLIC RECORDS OF PALM BEACH COUNTY.
 CONCURRENTLY WITH THE RECORDING THE OAKTON PRESERVE
 PLAT, THE DEVELOPER SHALL RECORD THE WORKFORCE HOUSING
 RESTRICTIVE COVENANT AGAINST EACH OF THE 13 WORKFORCE
 HOUSING UNITS, IN FORM AND SUBSTANCE SIMILAR TO EXHIBIT
 G OF ORDINANCE NO. 4162-08 . THE RECORDED WORKFORCE
 HOUSING RESTRICTIVE COVENANT SHALL INCLUDE THE LEGAL
 DESCRIPTION, THE PROPERTY CONTROL NUMBER (PCN) AND THE
 ADDRESS OF EACH OF THE 13 WORKFORCE HOUSING UNITS.
  
 4) PLEASE NOTE THAT THE TEMPORARY MODEL DWELLING UNIT
 MAY BE USED FOR SALES FOR ONLY 2 YEARS FROM THE
 CERTIFICATE OF OCCUPANCY (C.O.) OF THE TEMPORARY MODEL
 DWELLING UNIT. NOTE: THE PLANNING AND ZONING
 ADMINISTRATOR MAY GRANT UP TO AN ADDITIONAL TWO YEARS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 2 Status F Date 2010-03-24 Cont ID  
Sent By eschneid Date 2010-03-24 Time 15:07 Rev Time 0.20
Received By eschneid Date 2010-03-24 Time 15:07 Sent To  
Notes
2010-03-24 15:20:15FAILED
  
 1) REPEAT COMMENT: THE LATEST MINOR AMENDMENT FOR THE
 PARKING FOR THE TEMPORARY MODEL DWELLING UNIT HAS NOT
 BEEN APPROVED BY ZONING. THE MOST RECENT COMMENTS
 ISSUED ON MARCH 24, 2010, HAVE NOT BEEN ADDRESSED.
  
 A. THE CUT SHEET PROVIDED FOR THE TEMPORARY MODEL
 DWELLING WITH THE MINOR AMENDMENT PARKING INCLUDES A
 PORTABLE RESTROOM. IN ORDER FOR STAFF TO APPROVE A
 PORTABLE RESTROOM, IT SHALL BE SCREENED WITH A
 PODOCARPUS HEDGE INSTALLED TO THE HEIGHT OF THE
 PORTABLE RESTROOM AND PLANTED SO THAT THE BRANCHES
 TOUCH TO PROVIDE A FULL SCREEN. THE HEDGE SHALL ENCLOSE
 THE PORTABLE RESTROOM AND THE WALKWAY LEADING TO THE
 RESTROOM.
  
 2) NO BUILDING PERMIT TO INSTALL THE PARKING FOR THE
 TEMPORARY MODEL DWELLING UNIT HAS BEEN APPROVED -
 RESPONSE COMMENTS STATE THAT PARKING AREA INCLUDED IN
 THIS PERMIT VALUE, THEREFORE SEE COMMENT BELOW AND NOTE
 FEE INCREASE TO REVIEW PARKING AREA AND PARKING AREA
 LANDSCAPE.
  
 A. IF THE PARKING IS INCLUDED AS PART OF THIS PERMIT,
 THEN THE TEMPORARY MODEL DWELLING UNIT PARKING AND
 LANDSCAPE PLANS APPROVED BY ZONING THROUGH THE MINOR
 AMENDMENT PROCESS SHALL BE SUBMITTED WITH THIS PERMIT.
  
 3) NOTE: PER ORDINANCE NUMBER 4221-09, THE DEVELOPER'S
 SALES OFFICE SHALL PROMINENTLY DISPLAY A SIGN AT A
 MINIMUM SIZE OF ONE AND A HALF (1.5) FEET X TWO (2)
 FEET STATING, "THIS PROJECT CONTAINS WORKFORCE HOUSING
 UNITS". THE SIGN SPECIFICATIONS AND LOCATION SHALL BE
 SHOWN ON THE TEMPORARY MODEL DWELLING UNIT PLANS
 INCLUDED AS PART OF THIS PERMIT.
  
 4) NOTE: PER ORDINANCE NUMBER 4221-09:
  
 A) DEVELOPER SHALL DISCLOSE THE EXISTENCE OF WORKFORCE
 HOUSING UNITS TO ALL PURCHASERS OF UNITS WITHIN OAKTON
 PRESERVE AND SHALL DISCLOSE THE RESTRICTIVE COVENANTS
 REGARDING THE WORKFORCE HOUSING TO ALL QUALIFIED BUYERS
 OF SUCH WORKFORCE HOUSING UNITS.
  
 B) THE OAKTON PRESERVE PORTION OF THE CPD WILL BE
 SUBJECT TO A DECLARATION CREATING A HOMEOWNERS
 ASSOCIATION. THE DECLARATION OF SUCH ASSOCIATION SHALL
 DISCLOSE IN ALL CAPITALIZED AND UNDERLINED WORDING THAT
 THE DEVELOPMENT INCLUDES 13 WORKFORCE HOUSING UNITS.
  
 C) PRIOR TO THE FIRST CONVEYANCE OF ANY INDIVIDUAL UNIT
 OR THE ISSUANCE OF THE BUILDING PERMIT FOR THE THIRD
 RESIDENTIAL BUILDING TO BE CONSTRUCTED, WHICHEVER FIRST
 OCCURS, THE DEVELOPER SHALL RECORD THE OAKTON PRESERVE
 PLAT, IN THE PUBLIC RECORDS OF PALM BEACH COUNTY.
 CONCURRENTLY WITH THE RECORDING THE OAKTON PRESERVE
 PLAT, THE DEVELOPER SHALL RECORD THE WORKFORCE HOUSING
 RESTRICTIVE COVENANT AGAINST EACH OF THE 13 WORKFORCE
 HOUSING UNITS, IN FORM AND SUBSTANCE SIMILAR TO EXHIBIT
 G OF ORDINANCE NO. 4162-08 . THE RECORDED WORKFORCE
 HOUSING RESTRICTIVE COVENANT SHALL INCLUDE THE LEGAL
 DESCRIPTION, THE PROPERTY CONTROL NUMBER (PCN) AND THE
 ADDRESS OF EACH OF THE 13 WORKFORCE HOUSING UNITS.
  
 5) PLEASE NOTE THAT THE TEMPORARY MODEL DWELLING UNIT
 MAY BE USED FOR SALES FOR ONLY 2 YEARS FROM THE
 CERTIFICATE OF OCCUPANCY (C.O.) OF THE TEMPORARY MODEL
 DWELLING UNIT. NOTE: THE PLANNING AND ZONING
 ADMINISTRATOR MAY GRANT UP TO AN ADDITIONAL TWO YEARS.
  
 6) NEW COMMENT: STAFF PERFORMED A SITE VISIT AND NOTED
 THAT THE ENTRYWAY BETWEEN UNITS 57 AND 58 WERE NOT
 CONSTRUCTED ACCORDING THE APPROVED SITE PLANS,
 LANDSCAPE PLANS AND SURVEYS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2010-01-27 Cont ID  
Sent By eschneid Date 2010-01-27 Time 14:07 Rev Time 0.25
Received By eschneid Date 2010-01-27 Time 14:07 Sent To  
Notes
2010-01-27 14:24:33FAILED
  
 1) THE LATEST MINOR AMENDMENT FOR THE PARKING FOR THE
 TEMPORARY MODEL DWELLING UNIT HAS NOT BEEN APPROVED BY
 ZONING. THE COMMENTS OF NOVEMBER 12, 2009, HAVE NOT
 BEEN ADDRESSED.
  
 2) NO BUILDING PERMIT TO INSTALL THE PARKING FOR THE
 TEMPORARY MODEL DWELLING UNIT HAS BEEN APPROVED.
  
 3) PER ORDINANCE NUMBER 4221-09, THE DEVELOPER???S
 SALES OFFICE SHALL PROMINENTLY DISPLAY A SIGN AT A
 MINIMUM SIZE OF ONE AND A HALF (1.5) FEET X TWO (2)
 FEET STATING, ???THIS PROJECT CONTAINS WORKFORCE
 HOUSING UNITS???. THE SIGN SPECIFICATIONS AND LOCATION
 SHALL BE SHOWN ON THE TEMPORARY MODEL DWELLING UNIT
 PLANS INCLUDED AS PART OF THIS PERMIT.
  
 4) PER ORDINANCE NUMBER 4221-09:
  
 A) DEVELOPER SHALL DISCLOSE THE EXISTENCE OF WORKFORCE
 HOUSING UNITS TO ALL PURCHASERS OF UNITS WITHIN OAKTON
 PRESERVE AND SHALL DISCLOSE THE RESTRICTIVE COVENANTS
 REGARDING THE WORKFORCE HOUSING TO ALL QUALIFIED BUYERS
 OF SUCH WORKFORCE HOUSING UNITS.
  
 B) THE OAKTON PRESERVE PORTION OF THE CPD WILL BE
 SUBJECT TO A DECLARATION CREATING A HOMEOWNERS
 ASSOCIATION. THE DECLARATION OF SUCH ASSOCIATION SHALL
 DISCLOSE IN ALL CAPITALIZED AND UNDERLINED WORDING THAT
 THE DEVELOPMENT INCLUDES 13 WORKFORCE HOUSING UNITS.
  
 C) PRIOR TO THE FIRST CONVEYANCE OF ANY INDIVIDUAL UNIT
 OR THE ISSUANCE OF THE BUILDING PERMIT FOR THE THIRD
 RESIDENTIAL BUILDING TO BE CONSTRUCTED, WHICHEVER FIRST
 OCCURS, THE DEVELOPER SHALL RECORD THE OAKTON PRESERVE
 PLAT, IN THE PUBLIC RECORDS OF PALM BEACH COUNTY.
 CONCURRENTLY WITH THE RECORDING THE OAKTON PRESERVE
 PLAT, THE DEVELOPER SHALL RECORD THE WORKFORCE HOUSING
 RESTRICTIVE COVENANT AGAINST EACH OF THE 13 WORKFORCE
 HOUSING UNITS, IN FORM AND SUBSTANCE SIMILAR TO EXHIBIT
 G OF ORDINANCE NO. 4162-08 . THE RECORDED WORKFORCE
 HOUSING RESTRICTIVE COVENANT SHALL INCLUDE THE LEGAL
 DESCRIPTION, THE PROPERTY CONTROL NUMBER (PCN) AND THE
 ADDRESS OF EACH OF THE 13 WORKFORCE HOUSING UNITS.
  
 5) PLEASE NOTE THAT THE TEMPORARY MODEL DWELLING UNIT
 MAY BE USED FOR SALES FOR ONLY 2 YEARS FROM THE
 CERTIFICATE OF OCCUPANCY (C.O.) OF THE TEMPORARY MODEL
 DWELLING UNIT. NOTE: THE PLANNING AND ZONING
 ADMINISTRATOR MAY GRANT UP TO AN ADDITONAL TWO YEARS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  