Plan Review Details - Permit 10010182
Plan Review Stops For Permit 10010182
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-24 Cont ID  
Sent By jgomez Date 2010-03-24 Time 16:30 Rev Time 0.00
Received By jgomez Date 2010-03-24 Time 15:47 Sent To  
Notes
2010-03-24 16:42:26BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE REVISION
 FOR APPROVAL PRIOR TO CONSTRUCTION TO AVOID CONFLICTS
 OR DELAYS).
  
 1- AREA BY THE DOOR LEADING TO THE WOMEN'S VESTIBULE
 NEED TO COMPLY WITH THE DIMENSIONS SHOWN ON FIGURE
 25(A) OF CHAPTER 11 OF 2007 FBC FOR FRONT APPROACH. SEE
 COPY OF FIGURE 25(A) ATTACHED ON DRAWING A-101.
 ***NOTE: REVISION #1 SHOWN ON SHEET A-101 IS NOT DRAWN
 TO SCALE. 2'-6" DOOR DOESN'T COMPLY. REVISE AS REQUIRED
 TO COMPLY WITH FIGURE 25(A).
  
 2- DOOR FOR THE UTILITY CLOSET NEED TO COMPLY WITH SEC.
 11-4.13.5 FBC 2007. 2'-8" DOOR DOESN'T PROVIDE 32"
 CLEAR OPENING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-01-28 Cont ID  
Sent By jgomez Date 2010-01-28 Time 16:56 Rev Time 0.00
Received By jgomez Date 2010-01-28 Time 16:56 Sent To  
Notes
2010-01-28 16:58:43BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- AREA BY THE DOOR LEADING TO THE WOMEN'S VESTIBULE
 DOESN'T COMPLY WITH THE MANEUVERING CLEARANCES AT
 DOORS. SEC. 11-4.13.6 FBC 2007. IT DOESN'T HAVE THE
 DIMENSIONS REQUIRED ON FIGURE 25(A) FOR FRONT APPROACH.
  
 2- DOOR FOR THE UTILITY CLOSET DOESN'T COMPLY WITH THE
 MINIMUM DOOR SIZE REQUIRED BY SEC. 11-4.13.5 FBC 2007.
 NOTE: THIS UTILITY CLOSET DOESN'T MEET THE EXCEPTION,
 THEREFORE 32" CLEAR OPENING IS REQUIRED.
  
 3- SHEET A-100: REVISE THE CODE SUMMARY INFORMATION.
 THE CURRENT CODE IN EFFECT IS THE 2007 FBC WITH 2009
 REVISIONS. NOT 2004 FBC.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-30 Cont ID  
Sent By btrobaug Date 2010-03-30 Time 10:48 Rev Time 0.00
Received By btrobaug Date 2010-03-30 Time 10:27 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-01-20 Cont ID  
Sent By dpalmer Date 2010-01-20 Time 17:00 Rev Time 0.00
Received By dpalmer Date 2010-01-20 Time 17:00 Sent To  
Notes
2010-01-20 17:01:09** DENIED *
  
 1) NOTE: PLANS STATE 2004 FLORIDA BUILDING CODE WITH
 2006 AND 2007 AMENDMENTS.
 ALL PERMIT APPLICATIONS MADE AFTER MARCH 1ST, 2009 AND
 OCTOBER 1ST, 2009 HAVE NEW CODES.
  
 PLANS SHOULD HAVE THE FOLLOWING.
 2007 FBC W/ 2009 SUPPLEMENTS
 2008 NFPA-70 ( NEC).
  
 2) NOTE: ALL HORN, STROBE AND DEVICE LEVELS AND HEIGHTS
 TO BE PART OF SYMBOL LEGEND FOR ADA COMPLIANCE. FBC
 11-4.28, .1, .2 AND .3.
 BASE PLANS ARE REQUIRED TO SHOW BASE DESIGN INTENT EVEN
 THOUGH FIRE ALARM WILL BE UNDER SEPARATE PERMITS.
  
 3) NOTE: PLEASE SEE FBC 13-415.AB.5 FOR INTERIOR
 LIGHTING PERFORMANCE CALCULATIONS. THE * J* FIXTURES
 WHICH ARE SHOWN ON LEGEND AND IN CALCULATIONS FOR
 RESTROOM COULD NOT BE LOCATED ON PLANS.
 THE B1 FIXTURE ON THE CALCULATIONS IS SHOWN AS 20W
 FIXTURE HOWEVER BASED ON THE FIXTURE LISTED THIS IS A
 70W FIXTURE. THE RATING OF THE FIXTURE NOT THE BULB IS
 REQUIRED TO BE USED FOR PERFORMANCE CALCULATIONS.
  
 4) NOTE: ALL CIRCUITING IS REQUIRED TO BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. SOME CIRCUITS FOR
 EXAMPLE A-29 APPEARS TO BE DEDICATED FOR A REFRIGERATOR
 HOWEVER PANEL SCHEDULE ONLY INDICATES THIS AS AN
 *EXISTING RECEPT*.
 LOADS FOR ALL CIRCUITS AND PANEL CAN NOT BE VERIFIED
 WITHOUT THIS SPECIFIC INFORMATION. DESIGNATION FOR
 AREAS AND ROOMS MAY BE ALPHA OR NUMERIC.
 PLEASE SEE 408.4 SPECIFIC, SEE COMMENTARY IN HANDBOOK,
 220, 310.16 GIVEN IN GENERAL FOR LOADS AND SIZING OF
 BRANCH CIRCUITS.
 ** ONCE COMMENTS 1-3 ABOVE ARE ADDRESSED THIS COMMENT
 MAY BE SET UP AS A PROVISO TO HAVE ALL CIRCUITING CAN
 BE UPDATED AND ACCURATE IN THE PANEL SCHEDULE BEFORE
 FINAL.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-25 Cont ID  
Sent By mawillia Date 2010-03-25 Time 11:03 Rev Time 0.00
Received By mawillia Date 2010-03-25 Time 10:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-01-28 Cont ID  
Sent By mawillia Date 2010-01-28 Time 14:43 Rev Time  
Received By mawillia Date 2010-01-28 Time 14:22 Sent To  
Notes
2010-01-28 20:42:56*****PARTIAL APPROVAL*****
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED ONCE
 COMMENTS FROM THE BUILDING AND ELECTRICAL PLAN
 REVIEWERS HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-22 Cont ID  
Sent By lmartine Date 2010-03-18 Time 16:11 Rev Time 0.00
Received By lmartine Date 2010-03-18 Time 16:11 Sent To  
Notes
2010-03-22 16:12:06B--4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-12 Cont ID  
Sent By lmartine Date 2010-02-02 Time 10:24 Rev Time 0.00
Received By lmartine Date 2010-01-13 Time 13:38 Sent To  
Notes
2010-01-13 14:04:38TO C2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-01-27 Cont ID  
Sent By jgomez Date 2010-01-27 Time 16:23 Rev Time 0.00
Received By jgomez Date 2010-01-27 Time 16:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-01-28 Cont ID  
Sent By rregueir Date 2010-01-28 Time 17:18 Rev Time 0.00
Received By rregueir Date 2010-01-28 Time 17:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-01-19 Cont ID  
Sent By kstevens Date 2010-01-19 Time 11:17 Rev Time 0.00
Received By kstevens Date 2010-01-19 Time 11:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2010-02-02 Cont ID  
Sent By lfranco Date 2010-02-02 Time 11:45 Rev Time 0.00
Received By lfranco Date 2010-02-02 Time 11:45 Sent To I
Notes
2010-02-02 11:49:33PLANNING AND ZONING: **** N/A ****
  
 ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]