Plan Review Details - Permit 10010145
Plan Review Stops For Permit 10010145
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 16:19 Rev Time 0.00
Received By shill Date 2010-03-16 Time 16:19 Sent To  
Notes
2010-03-16 16:22:31****PROVISOS****
 REVISION, SHEET A2, A5
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FBC1013.2, EGRESS SHALL NOT PASS THROUGH A ROOM THAN
 CAN BE LOCKED TO PREVENT ACCESS - STORAGE AREA BEHIND
 OFFICE #2.
  
 2. THIS REVISION WILL BE ISSUED WITH PROVISO -
 FBC11-4.5.2, CHANGE IN ELEVATION OF 1/2" AT EXIT DOORS
 ARE TO BE BEVELED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-02-03 Cont ID  
Sent By shill Date 2010-02-03 Time 11:17 Rev Time 0.00
Received By shill Date 2010-02-03 Time 11:17 Sent To  
Notes
2010-02-03 11:20:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FBC1013.2, EGRESS SHALL NOT PASS THROUGH STOARAGE
 ROOMS (NEW PARTITION WALL).
  
 2. FBC1013.2, EGRESS SHALL NOT PASS THROUGH A ROOM THAN
 CAN BE LOCKED TO PREVENT ACCESS. THE DOOR AND RELATED
 HARDWARE WAS NOT INCLUDED ON THE DOOR SCHEDULE.
  
 3. SEE ISSUED PERMIT SET AND PLAN REVIEW NOTES FOR
 MASTER. THIS PERMIT WAS ISSUED WITH A PROVISO FROM THE
 PLUMBING REVIEWER, PLANS SHALL BE REVISED TO SHOW A
 FORWARD APPROACH FOR THE DRINKING FOUNTAINS. THIS
 PROVISO WAS NOT ADDRESSED, PLANS STILL SHOW A PARALLEL
 APPROACH, FBC11-4.15.5. PLEASE REVISE SHEET A2 AS
 REQUIRED.
  
 4. THIS REVISION WILL BE ISSUED WITH PROVISO -
 FBC11-4.5.2, CHANGE IN ELEVATION OF 1/2" AT EXIT DOORS
 ARE TO BE BEVELED.
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-01-21 Cont ID  
Sent By dpalmer Date 2010-01-21 Time 14:26 Rev Time 0.00
Received By dpalmer Date 2010-01-21 Time 14:25 Sent To M
Notes
2010-01-21 14:26:40 
 ** REDLINED PLANS FROM ORIGINAL REVIEW FROM 12/2008.
  
 WATER HEATER LOADS IS REQUIRED AT 125%. 422.13.
 WATER HEATER PROTECTION PER 422.17
 PANEL SCHEDULE REDLINED FOR CIRCUITING PER 408.4. ALL
 CIRCUITS ARE REQUIRED TO BE SPECIFIC TO ROOMS ARE AREAS
 IN WHICH THEY FEED. FOR EXAMPLE BAY C AND B INDICATE *
 GENERAL RECEPTS* INSTEAD OF NORTH, SOUTH, WEST ETC.
 408.4
  
  
2010-01-21 14:26:23** RECEIVED PLANS 1/21 1PM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-01-23 Cont ID  
Sent By rregueir Date 2010-01-23 Time 14:22 Rev Time 0.00
Received By rregueir Date 2010-01-23 Time 14:21 Sent To B
Notes
2010-01-23 14:22:08REVISED MP-1 DELTA 10

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***