Plan Review Details - Permit 10010099
Plan Review Stops For Permit 10010099
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-20 Cont ID  
Sent By jgomez Date 2010-01-20 Time 15:40 Rev Time 0.00
Received By jgomez Date 2010-01-20 Time 13:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-01-07 Cont ID  
Sent By jgomez Date 2010-01-07 Time 14:13 Rev Time 0.00
Received By jgomez Date 2010-01-07 Time 13:33 Sent To PC
Notes
2010-01-07 14:29:52RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- FLAT ROOF COMMENTS:
 A) SELECTED FLAT ROOF APPROVED SYSTEM W-26 ON SHEET 10
 OF 32 IS GOOD FOR THE DESIGN PRESSURES OF -60PSF. NEED
 TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY LIMITATION #5.6 ON SHEET 4 OF 5 TO MEET THE
 DESIGN PRESSURES AT ROOF PERIMETER AND CORNER AREAS.
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". SEC.
 R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 RESIDENTIAL
 CODE.
  
 2- ACCORDING TO MIAMI-DADE COUNTY WEBSITE NOA
 07-0111.03 SUBMITTED IS SUPERSEDED. NEED TO PROVIDE
 CURRENT NOA.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2010-01-07 Cont ID  
Sent By swurafti Date 2010-01-07 Time 10:55 Rev Time 0.00
Received By swurafti Date 2010-01-07 Time 10:55 Sent To  
Notes
2010-01-07 10:55:36HISTORIC APPROVED BY FMITTNER