Plan Review Details - Permit 10010071
Plan Review Stops For Permit 10010071
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-11 Cont ID  
Sent By jgomez Date 2010-01-11 Time 08:31 Rev Time 0.00
Received By jgomez Date 2010-01-11 Time 08:31 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-01-07 Cont ID  
Sent By jgomez Date 2010-01-07 Time 09:03 Rev Time 0.00
Received By jgomez Date 2010-01-07 Time 08:43 Sent To PC
Notes
2010-01-07 09:31:45RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE PRODUCT APPROVAL FOR FLAT ROOF TO BE USED.
 NO INFORMATION WAS SUBMITTED.
  
 2- CLEARLY MARK ON PRODUCT APPROVAL SPECIFIC APPROVED
 ASSEMBLY AND BASE SHEET FASTENING OPTION TO BE USED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301 OF 2007 FLORIDA RESIDENTIAL CODE.
 ***NOTE 1: PROVIDE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS IF SELECTED
 ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7. (CHECK
 PRODUCT APPROVAL SUBMITTED TO SEE IF RAS 117
 CALCULATIONS NEED TO BE SIGNED AND SEALED). IF SELECTED
 ASSEMBLY IS LIMITED BY GENERAL LIMITATION #9, THEN IT
 MAY NOT BE USED IN THIS BUILDING IF THE DESIGN
 PRESSRUES ASRE TOO LOW.
 ***NOTE 2: BUILDING IS LOCATED ON EXPOSURE "C". TAKE
 THIS INTO CONSIDERATION WHEN DOING THE RAS 117
 CALCULATIONS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712