Plan Review Details - Permit 10010056
Plan Review Stops For Permit 10010056 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2010-01-07 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-01-07 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-01-07 |
Time |
15:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2010-01-07 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-01-07 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-01-07 |
Time |
14:44 |
Sent To |
|
|
Notes |
2010-01-07 14:55:09 | RESIDENTIAL (R3) REROOF BUILDING REVIEW SECOND | | CHECKLIST. | | | | 1- SELECTED APPROVED ASSEMBLY ON SHEET 29 OF NOA | | 09-0224.01 SUBMITTED IS LIMITED BY GENERAL LIMITATION | | #7. ACCORDING TO GENERAL LIMITATION #7 ON LAST PAGE OF | | NOA SUBMITTED NEED TO PROVIDE SIGNED AND SEALED RAS 117 | | CALCULATIONS TO MEET THE PERIMETER AND CORNER AREAS | | DESIGN PRESSURES REQUIRED BY SEC. R301 OF 2007 FLORIDA | | RESIDENTIAL CODE. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2010-01-05 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2010-01-05 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2010-01-05 |
Time |
16:28 |
Sent To |
PC |
|
Notes |
2010-01-05 16:53:53 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PROVIDE COMPLETE PRODUCT APPROVAL FOR ROOF TILE TO | | BE INSTALLED. ONLY THE FLORIDA PRODUCT APPROVAL COVER | | PAGES WERE SUBMITTED, BUT THE REPORT THAT WAS SUBMITTED | | TO GET THE APPROVAL WAS NOT SUBMITTED. | | | | 2- SPECIFY HOW IS THE TILE GOING TO BE INSTALLED. IF | | USING NAILS OR SCREWS SPECIFY NUMBER TO BE USED TO | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301 OF 2007 FLORIDA RESIDENTIAL CODE. IF USING | | ADHESIVE, THEN PROVIDE THE ADHESIVE PRODUCT APPROVAL AS | | REQUIRED BY DCA RULE 9B-72. | | | | 3- FLAT ROOF PRODUCT APPROVAL SUBMITTED: CLEARLY MARK | | WHICH APPROVED ASSEMBLY IS GOING TO BE USED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. | | ***NOTE: IF SELECTED ASSEMBLY DON'T MEET THE DESIGN | | PRESSURES REQUIRED BY SEC. R301, THEN SIGNED AND SEALED | | CALCULATIONS ARE REQUIRED. SEE GENERAL NOTES ON PRODUCT | | APPROVAL SUBMITTED. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2010-01-05 |
|
|
Cont ID |
|
Sent By |
mmiller |
Date |
2010-01-05 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
mmiller |
Date |
2010-01-05 |
Time |
15:28 |
Sent To |
|
|
Notes |
2010-01-05 15:28:54 | OK PER JILLIAN PAPA MMILLER |
|
|
|