Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-01-21 Cont ID  
Sent By hmoser Date 2010-01-21 Time 14:15 Rev Time 0.00
Received By hmoser Date 2010-01-21 Time 14:15 Sent To  
Notes
2010-01-21 14:26:31PASS PROVISO
 1) PLEASE REFER TO SECTION 508.1 MAKEUP AIR
 FOR MECHANICAL MAKEUP AIR SYSTEMS , THE EXHAUST AND
 MAKEUP AIR SYSTEMS SHALL BE ELECTRICALLY INTERLOCKED TO
 INSURE THAT MAKEUP AIR IS PROVIDE WHENEVER THE EXHAUST
 SYSTEM IS IN OPERATION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-01-12 Cont ID  
Sent By hmoser Date 2010-01-12 Time 13:10 Rev Time 0.00
Received By hmoser Date 2010-01-12 Time 13:10 Sent To  
Notes
2010-01-12 13:27:24PLAN DENIED.
 1) PLEASE REFER TO SECTION 508.1 MAKEUP AIR 2007 FBC
 (M)
 2) PLEASE REFER TO SECTIOM 506.3.10 DUCT INCLOSURE 2007
 FBC (M)
 3) PLEASE REFER TO SECTION 301.12 WIND RESISTANCE . THE
 FAN MUST BE DESIGNED TO RESIST THE WIN PRESSURE NOT THE
 TIEDOWN OR STRAPPING OF THE EQUIPMENT.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732