Plan Review Details - Permit 09120528
Plan Review Stops For Permit 09120528
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-14 Cont ID  
Sent By rmcdouga Date 2010-01-14 Time 08:33 Rev Time 0.00
Received By rmcdouga Date 2010-01-14 Time 08:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-30 Cont ID  
Sent By rmcdouga Date 2009-12-30 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2009-12-30 Time 07:29 Sent To  
Notes
2009-12-30 09:47:482007 FBC W/2009 REVISIONS
 REVISION
  
 DENIED BY BUILDING
  
 1) THIS PACKAGE SHOULD HAVE BEEN SUBMITTED AS A
 REVISION TO THE PERMITS THAT HAVE ALREADY BEEN ISSUED
 FOR THIS WORK. A NEW PERMIT WILL NOT BE ISSUED. WHEN
 THIS IS RESUBMITTED USE THE PROPER RESUBMITTAL FORM.
  
 2) SUBMIT 2 SETS OF REVISED PLANS WITH THE CHANGES
 INDICATED BY CLOUDS AND REVISION NUMBER. FBC 106.1 CITY
 AMENDMENTS
  
 3) THE ONE SET OF PLANS THAT WAS SUBMITTED INDICATES
 THAT A BATH ROOM HAS BEEN ADDED AND THE UTILITY ROOM
 HAS BEEN MOVED. WHEN SPECIFYING THE DESCRIPTION OF WORK
 ON A REVISION FORM PROVIDE THIS INFORMATION.
  
 4) THE VALUE OF THE ADDITIONAL WORK WILL BE ADDED TO
 THE MASTER PERMIT AND A REVISION FEE WILL BE CHARGED
 FOR THE REVISED SHEETS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-01-19 Cont ID  
Sent By btrobaug Date 2010-01-19 Time 10:31 Rev Time 0.00
Received By btrobaug Date 2010-01-19 Time 10:18 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-29 Cont ID  
Sent By btrobaug Date 2009-12-29 Time 13:27 Rev Time 0.00
Received By btrobaug Date 2009-12-29 Time 13:25 Sent To  
Notes
2009-12-29 13:27:03 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE THE CONDUIT AND CONDUCTOR SIZES FROM PANEL
 "A" TO PANEL "B" ON THE RISER. 215.5
  
 2} 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS,
 AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS
 WITH EACH APPLICATION FOR A PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-11 Cont ID  
Sent By dpalmer Date 2010-01-11 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2010-01-11 Time 16:16 Sent To  
Notes
2010-01-11 16:16:47R10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-30 Cont ID  
Sent By rmcdouga Date 2009-12-30 Time 11:48 Rev Time 0.00
Received By rmcdouga Date 2009-12-28 Time 16:18 Sent To  
Notes
2009-12-28 16:18:34ZONING IN BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-01-14 Cont ID  
Sent By rmcdouga Date 2010-01-14 Time 08:33 Rev Time 0.00
Received By rmcdouga Date 2010-01-14 Time 08:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-12-30 Cont ID  
Sent By rmcdouga Date 2009-12-30 Time 11:48 Rev Time 0.00
Received By rmcdouga Date 2009-12-30 Time 11:48 Sent To  
Notes
2009-12-30 12:21:032007 FBC W/2009 REVISIONS
 MECHANICAL REVISIONS
  
 DENIED
  
 1) TWO SETS OF OF REVISED PLANS ARE REQUIRED.
  
 2) MECHANICAL VENTILATION DISCHARGED TO THE EXTERIOR IS
 REQUIRED IN THE BATHROOMS PER FBCR M 1507.2. THE
 EXHAUST CAPACITY OF 50 CFM INTERMITTENT IS REQUIRED PER
 M 1507.3.
  
 3) TRANSFER DUCTS ARE REQUIRED TO BE TO BE 1.5 TIMES
 THE CROSS SECTIONAL AREA OF THE SUPPLY DUCT ENTERING
 THE ROOM. PLEASE REVISE. SEE FBCR M 1602.4.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-01-14 Cont ID  
Sent By rmcdouga Date 2010-01-14 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2010-01-14 Time 08:33 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-12-30 Cont ID  
Sent By rmcdouga Date 2009-12-30 Time 11:12 Rev Time 0.00
Received By rmcdouga Date 2009-12-30 Time 11:12 Sent To  
Notes
2009-12-30 11:47:482007 FBC W/2009 REVISIONS
 PLUMBING REVISIONS
  
 DENIED
  
 1) TWO SETS OF REVISED PLANS ARE REQUIRED. FBC 106.1
 CITY AMENDMENTS
  
 2) PLEASE INDICATE CHANGES FROM THE APPROVED PLANS WITH
 CLOUDS OR OTHER ACCEPTABLE METHODS.
  
 3) THE PLUMBING RISER DIAGRAM DOES NOT MATCH THE
 ARCHITECTURAL PLANS.
  
 4) SPECIFY ALL DWV PIPE SIZES ON THE PLANS. FBCR
 P3005.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]