Plan Review Details - Permit 09120523
Plan Review Stops For Permit 09120523
Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date 2009-12-28 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-01-14 Cont ID  
Sent By rregueir Date 2010-01-14 Time 10:38 Rev Time 0.00
Received By rregueir Date 2010-01-14 Time 10:19 Sent To Z
Notes
2010-01-14 10:37:23REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. CONDENSING UNITS ORIGINALLY SHOWN AS GROUND-MOUNTED,
 NOW SHOWN AS MOVED TO THE ROOF. THESE UNITS ARE WITHIN
 10 FEET OF THE ROOF EDGE AND GUARDS ARE REQUIRED IN
 ACCORDANCE WITH FBC-M 304.10.
  
 2. ROOF STAND FOR CONDENSERS IS NOW SHOWN ON PLANS.
 PROVIDE COMPLETE ENGINEERING DETAIL FOR CONSTRUCTION OF
 THE STAND AND ATTACHMENT OF THE CONDENSERS TO THE STAND
 FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.13.
 ALTERNATIVELY, IF A PRE-ENGINEERED A/C STAND IS USED,
 PROVIDE PRODUCT APPROVAL DOCUMENTATION IN ACCORDANCE
 WITH FBC-B 106.3.3 AND FAC RULE 9B-72.
  
 3. EXHAUST FANS FOR THE TOILET ROOMS HAVE BEEN
 ELIMINATED FROM THE PLANS. SHOW HOW THE REQUIRED
 EXHAUST IS TO BE PROVIDED IN THESE SPACES PER FBC-M
 TABLE 403.3.
  
 4. THE SIZE, AND LOCATION OF OUTSIDE AIR DUCTS ARE NOT
 SHOWN ON THE PLANS. ALSO, THE LOCATION OF OUTSIDE AIR
 INTAKES IS NOT SHOWN ON THE PLANS. SHOW MISSING
 INFORMATION TO DEMONSTRATE COMPLIANCE WITH FBC-M 603.1
 AND FBC-M 401.5.
  
 5. RETURN AIR FLEX DUCT SIZES ARE NOT SHOWN ON PLANS.
 PROVIDE MISSING INFORMATION TO DEMONSTRATE COMPLIANCE
 WITH FBC-M 601.4 AND 603.1.
  
 6. DUE TO THE RELOCATION OF THE CONDENSERS TO THE ROOF,
 A ZONING REVIEW IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2010-01-20 Cont ID  
Sent By eschneid Date 2010-01-20 Time 13:31 Rev Time 0.75
Received By eschneid Date 2010-01-20 Time 13:31 Sent To  
Notes
2010-01-20 14:14:56FAILED
  
 1) SECTION 94-221(D)(8) REQUIRES THAT MECHANICAL
 SYSTEMS, BACKFLOW PREVENTERS, TELEVISION ANTENNAS,
 SATELLITE DISHES AND SIMILAR DEVICES SHALL BE SCREENED
 FROM VIEW ON ALL SIDES TO THE FULL HEIGHT OF THE
 STRUCTURE BY LANDSCAPING OR BUILT ELEMENTS DESIGNED AS
 AN INTEGRAL PART OF THE BUILDING ARCHITECTURE. PLEASE
 PROVIDE ELEVATION DRAWINGS OF THE STRUCTURE WHICH SHOW
 HOW THE NEW ROOFTOP A/C EQUIPMENT LOCATED ON THE ROOF
 MEETS THIS CODE PROVISION.
  
 2) PROVIDE THE FULL HEIGHT OF THE ACCU AND THE METAL
 STAND.
  
 3) IF THE SITE PLAN, LANDSCAPE PLAN AND/OR ELEVATIONS
 APPROVED AS PART OF PERMIT NUMBER 07050617 CHANGE DUE
 TO THE A/C UNIT NO LONGER ON THE GROUND, THE APPLICABLE
 BUILDING PERMIT APPROVED PLANS SHALL BE REVISED PRIOR
 TO THE ZONING FINAL INSPECTION FOR PERMIT NUMBER
 07050617.
  
 4) NOTE: IF ANY PLANS ARE REVISED, PRIOR TO THEIR
 SUBMITTAL TO THE CONSTRUCTION SERVICES DEPARTMENT, THE
 PLANS SHALL BE SUBMITTED TO THE PLANNING AND ZONING
 DEPARTMENT AND REVIEWED THROUGH THE SITE PLAN AMENDMENT
 PROCESS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.