|
 |
 |
 |
 |
 |
Plan Review Details - Permit 09120523
Plan Review Stops For Permit 09120523 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
|
Received By |
|
Date |
2009-12-28 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2010-01-14 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2010-01-14 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2010-01-14 |
Time |
10:19 |
Sent To |
Z |
|
Notes |
2010-01-14 10:37:23 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. CONDENSING UNITS ORIGINALLY SHOWN AS GROUND-MOUNTED, | | NOW SHOWN AS MOVED TO THE ROOF. THESE UNITS ARE WITHIN | | 10 FEET OF THE ROOF EDGE AND GUARDS ARE REQUIRED IN | | ACCORDANCE WITH FBC-M 304.10. | | | | 2. ROOF STAND FOR CONDENSERS IS NOW SHOWN ON PLANS. | | PROVIDE COMPLETE ENGINEERING DETAIL FOR CONSTRUCTION OF | | THE STAND AND ATTACHMENT OF THE CONDENSERS TO THE STAND | | FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.13. | | ALTERNATIVELY, IF A PRE-ENGINEERED A/C STAND IS USED, | | PROVIDE PRODUCT APPROVAL DOCUMENTATION IN ACCORDANCE | | WITH FBC-B 106.3.3 AND FAC RULE 9B-72. | | | | 3. EXHAUST FANS FOR THE TOILET ROOMS HAVE BEEN | | ELIMINATED FROM THE PLANS. SHOW HOW THE REQUIRED | | EXHAUST IS TO BE PROVIDED IN THESE SPACES PER FBC-M | | TABLE 403.3. | | | | 4. THE SIZE, AND LOCATION OF OUTSIDE AIR DUCTS ARE NOT | | SHOWN ON THE PLANS. ALSO, THE LOCATION OF OUTSIDE AIR | | INTAKES IS NOT SHOWN ON THE PLANS. SHOW MISSING | | INFORMATION TO DEMONSTRATE COMPLIANCE WITH FBC-M 603.1 | | AND FBC-M 401.5. | | | | 5. RETURN AIR FLEX DUCT SIZES ARE NOT SHOWN ON PLANS. | | PROVIDE MISSING INFORMATION TO DEMONSTRATE COMPLIANCE | | WITH FBC-M 601.4 AND 603.1. | | | | 6. DUE TO THE RELOCATION OF THE CONDENSERS TO THE ROOF, | | A ZONING REVIEW IS REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2010-01-20 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2010-01-20 |
Time |
13:31 |
Rev Time |
0.75 |
Received By |
eschneid |
Date |
2010-01-20 |
Time |
13:31 |
Sent To |
|
|
Notes |
2010-01-20 14:14:56 | FAILED | | | | 1) SECTION 94-221(D)(8) REQUIRES THAT MECHANICAL | | SYSTEMS, BACKFLOW PREVENTERS, TELEVISION ANTENNAS, | | SATELLITE DISHES AND SIMILAR DEVICES SHALL BE SCREENED | | FROM VIEW ON ALL SIDES TO THE FULL HEIGHT OF THE | | STRUCTURE BY LANDSCAPING OR BUILT ELEMENTS DESIGNED AS | | AN INTEGRAL PART OF THE BUILDING ARCHITECTURE. PLEASE | | PROVIDE ELEVATION DRAWINGS OF THE STRUCTURE WHICH SHOW | | HOW THE NEW ROOFTOP A/C EQUIPMENT LOCATED ON THE ROOF | | MEETS THIS CODE PROVISION. | | | | 2) PROVIDE THE FULL HEIGHT OF THE ACCU AND THE METAL | | STAND. | | | | 3) IF THE SITE PLAN, LANDSCAPE PLAN AND/OR ELEVATIONS | | APPROVED AS PART OF PERMIT NUMBER 07050617 CHANGE DUE | | TO THE A/C UNIT NO LONGER ON THE GROUND, THE APPLICABLE | | BUILDING PERMIT APPROVED PLANS SHALL BE REVISED PRIOR | | TO THE ZONING FINAL INSPECTION FOR PERMIT NUMBER | | 07050617. | | | | 4) NOTE: IF ANY PLANS ARE REVISED, PRIOR TO THEIR | | SUBMITTAL TO THE CONSTRUCTION SERVICES DEPARTMENT, THE | | PLANS SHALL BE SUBMITTED TO THE PLANNING AND ZONING | | DEPARTMENT AND REVIEWED THROUGH THE SITE PLAN AMENDMENT | | PROCESS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |