Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-12 Cont ID  
Sent By shill Date 2010-01-12 Time 14:12 Rev Time 0.00
Received By shill Date 2010-01-12 Time 14:12 Sent To  
Notes
2010-01-12 14:24:38****PROVISO****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE PAVILLIONS ARE TO BE LOCATED ON AN ACCESSIBLE
 ROUTE, FBC11-4.1.2(2). (NO RESPONSE OR ACTION REQUIRED)
  
 2. FBC1802.2, PROVIDE TWO ORIGINAL SOILS REPORTS.
 (PROVIDE AT INSPECTION)
  
 3. FAC9B72, PROVIDE PRODUCT APPROVAL FOR THE ROOF. WIND
 DESIGN CRITERIA (COMPONENTS & CLADDING PRESSURES)
 REQUIRED FOR THE ROOF, FBC1603.1.4. SEE ALSO ITEM 4.
 PRIOR TO SUBMITTAL, THE PRODUCT APPROVALS SHOULD BE
 REVIEWED BY DESIGNER OF RECORD. ALSO, PRIOR TO
 SUBMITTAL, DESIGNER OF RECORD IS TO CONFIRM WITH THE
 METAL ROOF MANUFACTURER THAT THE PRODUCT IS SUITABLE
 FOR THIS PROJECT (COASTAL/CORROSIVE) OR LETTER FROM DOR
 OR OWNER STATING THAT THIS ISSUE HAS BEEN INVESTIGATED.
 (PRIOR TO FINAL INSPECTION)
  
 4. PAGE LD2 HAS A NOTE WHICH STATES "REFER TO ANCHOR
 AND FOOTING DOWLOAD SHEETS FOR GENERAL INFORMATION . .
 . " (ETC.). THESE SHEETS WERE NOT SUBMITTED. NO
 STRUCTURAL INFORMATION REGARDING THE PROPOSED SHELTER
 OR FOOTING WAS SUBMITTED. DETAILS ON LD1 ARE FOR THE
 10X10 TENNIS SHELTER (NOT THE 20X20 PICNIC SHELTERS). A
 REVISION IS REQUIRED PRIOR TO FINAL INSPECTION -
 MINIMUM DESIGN CRITERIA IS 140MPH EXPOSURE C. (PRIOR TO
 FINAL INSPECTION)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-30 Cont ID  
Sent By shill Date 2009-12-30 Time 11:34 Rev Time 0.00
Received By shill Date 2009-12-30 Time 11:33 Sent To  
Notes
2009-12-30 12:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. APPLICATION IS FOR "2 PICNIC PAVILLIONS," BUT PLANS
 SHOW OTHER ITEMS. SOME SHEETS, SUCH AS E5 AND LD1, HAVE
 DETAILS FOR OTHER STRUCTURES ON THIS SITE BUT NO
 DETAILS ON THOSE PAGES FOR THE TWO PICNIC PAVILLIONS.
 PLEASE BE ADVISED THAT ONLY THE PICNIC PAVILLIONS ARE
 BEING REVIEWED AT THIS TIME. OTHER DETAILS WILL BE
 CROSSED OFF PRIOR TO ISSUANCE UNLESS SCOPE OF WORK ON
 THE PERMIT APPLICATION IS REVISED. PLEASE REMOVE SHEETS
 WHICH DO NOT APPLY TO THIS PERMIT.
  
 2. THE PAVILLIONS ARE TO BE LOCATED ON AN ACCESSIBLE
 ROUTE, FBC11-4.1.2(2). IT APPEARS THAT THE SIDEWALK IS
 THE ACCESSIBLE ROUTE; PLEASE CONFIRM.
  
 3. FBC1802.2, PROVIDE TWO ORIGINAL SOILS REPORTS.
  
 4. FAC9B72, PROVIDE PRODUCT APPROVAL FOR THE ROOF.
 PRIOR TO SUBMITTAL, THE PRODUCT APPROVALS SHOULD BE
 REVIEWED BY DESIGNER OF RECORD. ALSO, PRIOR TO
 SUBMITTAL, DESIGNER OF RECORD IS TO CONFIRM WITH THE
 METAL ROOF MANUFACTURER THAT THE PRODUCT IS SUITABLE
 FOR THIS PROJECT (COASTAL/CORROSIVE).
  
 5. PAGE LD2 HAS A NOTE WHICH STATES "REFER TO ANCHOR
 AND FOOTING DOWLOAD SHEETS FOR GENERAL INFORMATION . .
 . " (ETC.). THESE SHEETS WERE NOT SUBMITTED. NO
 STRUCTURAL INFORMATION REGARDING THE PROPOSED SHELTER
 OR FOOTING WAS SUBMITTED. DETAILS ON LD1 ARE FOR THE
 10X10 TENNIS SHELTER (NOT THE 20X20 PICNIC SHELTERS).
 PLEASE PROVIDE OR REVISE PLANS TO INCLUDE STRUCTURAL
 INFORMATION.
  
 6. WIND DESIGN CRITERIA (COMPONENTS & CLADDING
 PRESSURES) REQUIRED FOR THE ROOF, FBC1603.1.4.
  
 7. SEPARATE PERMIT WILL BE REQUIRED FOR THE ROOF. THIS
 MAY BE DONE PRIOR TO INSTALLATION. A ROOF PERMIT WILL
 REQUIRE ROOF FASTENING OPTIONS TO BE INDICATED ON THE
 PRODUCT APPROVAL.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-01-14 Cont ID  
Sent By shill Date 2010-01-14 Time 13:27 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2009-12-29 10:39:37C 10

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2010-01-14 Cont ID  
Sent By shill Date 2010-01-14 Time 13:26 Rev Time 0.00
Received By shill Date 2010-01-14 Time 13:26 Sent To  
Notes
2010-01-14 13:27:35CONTRACTOR HAD SAME PLAN REVIEWED UNDER PERMIT
 #09060761 AND APPLIED FOR LANDSCAPE PERMIT WITH
 REFERENCE TO 09060761 AS MASTER. THEREFORE A LANDSCAPE
 PERMIT SHOULD NOT BE ISSUED ASSOCIATED WITH THIS PERMIT
 (09120495).
 SHEETS REMOVED
  

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2010-01-05 Cont ID  
Sent By rkussner Date 2010-01-05 Time 17:07 Rev Time 0.00
Received By rkussner Date 2010-01-05 Time 17:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-01-12 Cont ID  
Sent By kstevens Date 2010-01-12 Time 08:20 Rev Time 0.00
Received By kstevens Date 2010-01-11 Time 16:55 Sent To  
Notes
2010-01-12 08:21:30IRRIGATION PERMIT REQUIRED. SEE SHT IR-1.

Review Stop Z ZONING
Rev No 1 Status P Date 2010-01-13 Cont ID  
Sent By jroach Date 2010-01-13 Time 11:44 Rev Time 0.00
Received By jroach Date 2010-01-13 Time 11:44 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved