Plan Review Details - Permit 09120475
Plan Review Stops For Permit 09120475
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-09 Cont ID  
Sent By shill Date 2010-03-09 Time 11:58 Rev Time 0.00
Received By shill Date 2010-03-09 Time 11:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-01-06 Cont ID  
Sent By shill Date 2010-01-06 Time 11:04 Rev Time 0.00
Received By shill Date 2010-01-06 Time 11:04 Sent To  
Notes
2010-01-06 11:15:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THIS PLAN REVIEW WILL REMAIN IN FAILED STATUS UNTIL
 APPLICATION BY A LICENSED CONTRACTOR IS SUBMITTED.
  
 2. PLEASE HAVE ARCHITECT SIGN THE PLANS, FS481.
  
 3. CERTIFICATE OF AUTHORIZATION REQUIRED FOR THE FIRM
 AND THE LICENSE NUMBER SHOULD BE INCLUDED ON THE PLAN,
 FS481. PLEASE CONTACT ME IF YOU NEED ASSISTANCE. (SPOKE
 WITH TERRY; WILL APPLY)
  
 4. BREAK ROOM SINK IS TO BE ACCESSIBLE, FBC11-4.24.
 PROVIDE A DETAIL.
  
 5. FIRE SPRINKLER PLANS ARE REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79(2). ALSO SEE DCA LETTER. IF THIS IS UNDER
 SEPARATE PERMIT, PLEASE PROVIDE PERMIT NUMBER.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-03-18 Cont ID  
Sent By btrobaug Date 2010-03-18 Time 10:21 Rev Time 0.00
Received By btrobaug Date 2010-03-18 Time 09:21 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-02-11 Cont ID  
Sent By dpalmer Date 2010-02-11 Time 16:25 Rev Time 0.00
Received By dpalmer Date 2010-02-11 Time 16:25 Sent To  
Notes
2010-02-11 16:26:03*DENIED **
  
 1) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3 FOR DEVICE
 LOCATIONS FOR HORNS, STROBES, HORN/STROBES ETC.
 LOCATIONS SHOWN ON PLANS DO NOT MEET MINIMUM FOR ADA.
 ALL LOCATIONS WHICH ARE ACCESSIBLE SHALL HAVE COVERAGE.
 DEVICE HEIGHTS, ALONG WITH PULL STATION HEIGHTS ARE
 ALSO REQUIRED.
  
 2) NOTE: PLEASE COORDINATE PANELS. RISER INDICATES
 200AMP MLO, HOWEVER PANELS ARE SHOWN AS 225AMP.
 215.5.
 ** THIS WOULD HAVE BEEN REDLINE DIF ONLY COMMENT.
  
 3) NOTE: LIGHTING CONTROLS STILL REQUIRED TO MEET FBC
 13-415.AB.1.1,.1.2 AND .1.3.
 PLEASE SEE .1.3, THE ADDITIONAL CONTROLS FOR LIGHTING
 SUCH AS FIXTURE B. THE ROCKER SWITCH ON FIXTURE B IS
 NOT ACCEPTABLE TO MEET MINIMUM CODE.
  
 4) NOTE: THE FIXTURE LEGEND INDICATES A NEW FIXTURE *C*
 HOWEVER COULD NOT LOCATE THIS ON PLANS.
 13-415.AB.5. CAN NOT CONFIRM ATTACHED METHOD B AS
 COMPLIANT AT THIS TIME.
  
 5) NOTE: THE PREVIOUS NOTES MENTIONED THAT ROOM NOW
 LABELED AS STORAGE DID NOT MEET NEC 645 OR NFPA-75 FOR
 DEFINITIONS AS AN IT ROOM. HOWEVER THIS ROOM COULD BE
 LABELED AS TELEPHONE ROOM, TELCOM ROOM, COMPUTER ROOM
 ETC. PLANS NOW LABEL THIS AS A *STORAGE ROOM*. IS THIS
 TRUE WITH ALL OF THE ELECTRICAL AND OVER CURRENT
 PROTECTION SHOWN ON PLANS? PLEASE SEE 240.24 FOR
 LOCATION OF OVER CURRENT PROTECTION DEVICES NOT
 PERMITTED IN STORAGE ROOM
 PLEASE CALL TO GO OVER.
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-30 Cont ID  
Sent By dpalmer Date 2009-12-30 Time 16:21 Rev Time 0.00
Received By dpalmer Date 2009-12-30 Time 16:21 Sent To  
Notes
2009-12-30 16:21:50 
 ** DENIED *
  
  
  
  
  
 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION WITHOUT
 A LICENSED CONTRACTOR UNDER *TBD* (TO BE DETERMINED).
 EVEN ONCE PLANS ARE FOUND TO BE CODE COMPLIANT REVIEW
 WILL STILL REMAIN IN FAILED STATUS UNTIL LICENSED
 CONTRACTOR HAS APPLIED.
  
 2) NOTE: BOTH SETS OF PLANS SUBMITTED DO NOT CONTAIN AN
 ORIGINAL SIGNATURE BY THE LICENSED DESIGN PROFESSIONAL.
 THE USE OF A *RUBBER-STAMP* IS NOT PERMITTED.
 FS 481.221
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE
 REVIEW.
  
 3) NOTE: THE SUBMITTED FLA COM METHOD B CALCULATIONS
 ALSO CONTAIN A RUBBER STAMP FOR THE ARCHITECT OF
 RECORD. THESE ARE ALSO NOT SEALED WITH THE RAISED SEAL
 AS REQUIRED.
 FS 481.221, FAC 61G1-16.002. FBC 13-103.1
  
 4) NOTE: THE ARCHITECTURAL FIRM LISTED ON THE TITLE
 BLOCKS ARE REQUIRED TO DISPLAY THE FIRM LICENSED NUMBER
 ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 WHICH REQUIRES THE INFORMATION TO BE LOCATED ON TITLE
 BLOCKS. PLEASE SEE FLORIDA STATUTES 481.219 WHICH
 REQUIRES THE FIRM TO HAVE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE REVIEW.
  
 5) NOTE: PLEASE SEE SHEET T1. THE PLANS CONTAINS
 RELEVANT CODES FOR ELECTRICAL AS THE 2008 AND 2005
 NFPA-70.
 PLEASE KNOW THAT ON OCTOBER 1ST, 2009 THE SECOND SET OF
 2009 SUPPLEMENTS TO THE FLORIDA BUILDING CODE WAS
 ADOPTED. THIS INCLUDES THE ADOPTION OF THE 2008
 NFPA-70.
 ** PLEASE ADJUST CODES ON PLANS.
 OTHER RELEVANT CODES ON PLANS SHALL BE LISTED AS
 FOLLOWS.
  
 2006 NFPA-101 ( LIFE SAFETY CODE)
 2002 NFPA-72 ( NATIONAL FIRE ALARM CODE)
 2007 FLORIDA FIRE PREVENTION CODE.
  
 ADOPTED BY FBC AND FAC 69A-60.004, 69A-03.012
  
 6) NOTE: ROOM 008 IS LABELED AS AN IT ROOM ON PLANS.
 PLEASE SEE NFPA-75 2003 EDITION AND 2008 NFPA-70 FOR
 DEFINITIONS OF AN *IT ROOM*. PLEASE SEE NEC 645.4
 (1-5). THE NEC SPECIFICALLY IN 645 ALLOWS LESS
 STRINGENT WIRING METHODS THAN REQUIRED IN CHAPTERS 1-4
 OF THE NEC. HOWEVER IN ORDER TO CONSIDERED AN IT ROOM
 BY DEFINITION, ALL CONSTRUCTION MUST MEET NFPA-75 AND
 ALL ITEMS LISTED IN 645.4(1-5) MUST BE MET. BASED ON
 THE PLANS SUBMITTED THIS LOCATION DOES NOT MEET THE
 MINIMUM REQUIREMENTS TO BE CONSIDERED AN IT ROOM.
  
 ** IF THIS IS NOT GOING TO BE AN IT ROOM BY DEFINITION,
 PLEASE ADJUST ROOM DESIGNATION AND PLEASE PLACE NOTE ON
 ELECTRICAL PLANS WHICH STATES: *NO WIRING METHODS PER
 NEC 645 PERMITTED*, OR WORDS TO THAT AFFECT.
 PLEASE CALL TO GO OVER ANY QUESTIONS.
  
 7) NOTE: PLEASE INDICATE ALL CIRCUITS ON PLANS AND
 COORDINATE WITH PANEL SCHEDULES. BRANCH CIRCUIT LOADS,
 WIRING ETC CAN NOT BE FULLY VERIFIED AT THIS TIME.
 E 1.1 INDICATES THIS AS A CABLING PLAN. THERE IS NO
 POWER PLAN AND POWER FOR RECEPTACLES IS ALL SHOWN ON
 E1.1. PLEASE COMPLETE.
 NEC 240.4, 310.16, 408.4, 210.19, 210.20, 210.21 ETC
 PLEASE BE SURE TO SEE THE FOLLOWING FROM NEC 408.4
 WHICH DOES NOT PERMIT THE GENERAL DESCRIPTION AS
 *RECEPTACLES* OR *LIGHTS*. ALL AREAS ARE REQUIRED TO BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH EACH BREAKER
 FEEDS. EXAMPLE: LF-7, OFFICE 004 RECEPTACLES. THESE MAY
 BE ALPHA OR NUMERIC DESIGNATIONS.
 ** TEXT FROM CODE COMMENTARY IN THE NEC*
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 8) NOTE: PLEASE SEE 210.8B1-5 WHICH REQUIRES GFI
 RECEPTACLES OR GFI PROTECTION. RECEPTACLES IN LOCATIONS
 SUCH AS KITCHEN BREAK AREAS, BATHROOMS AND ALL
 RECEPTACLES WITHIN 6FT OF OTHER SINKS ARE ALL REQUIRED.
  
 9) NOTE: PLANS CONTAIN NOTES FOR FIRE ALARM HOWEVER
 NONE SHOWN ON PLANS. EVEN THOUGH FIRE ALARM PERMITS ARE
 SEPARATE ALONG WITH SEPARATE SHOP DRAWINGS, THE BASE
 PLANS ARE ALL REQUIRED TO SHOW MINIMUM REQUIRED FOR
 DESIGN INTENT. FS 633
 PLEASE SHOW ALL LOCATIONS, HEIGHTS AND MINIMUM LEVELS
 FOR ADA COMPLIANCE.
 PLEASE SEE FBC 11-4.28.1,.2 AND .3.
  
 10) NOTE: PLEASE INCLUDE NOTES FOR WIRING PER NEC 517,
 PART II. PER THE SCOPE OF WORK AND OCCUPANCY WIRING
 SHALL CONTAIN REDUNDANT GROUNDING PER 517.13.
  
 11) NOTE: RISER INDICATES TWO METERS AND TENANT
 DISCONNECTS FOR ONE TENANT SPACE. NOTES ON PLANS STATE
 THESE AS * SERVICES* HOWEVER PER NEC 100 THESE ARE NOT
 SERVICES. PLEASE VERIFY WITH FIRE MARSHAL THAT MORE
 THAN ONE DISCONNECTING MEANS WILL BE PERMITTED FOR ONE
 TENANT SPACE.
  
 12) NOTE: THE AIR CONDITIONING EQUIPMENT IS SHOWN ON
 M-SHEETS HOWEVER NOT ON ELECTRICAL SHEETS. IN FACT
 THERE ARE MORE BREAKERS FOR A/C EQUIPMENT IN PANEL HC
 THAN SHOWN ON RISER.
 IT IS UNCLEAR WHERE THE OTHER BRANCH CIRCUITS LISTED ON
 PANEL HC IS?
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-02-26 Cont ID  
Sent By mawillia Date 2010-02-26 Time 14:08 Rev Time 0.00
Received By mawillia Date 2010-02-26 Time 13:43 Sent To  
Notes
2010-02-26 13:52:37*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A1, A2, A5A, A7, & E2 WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-01-20 Cont ID  
Sent By mawillia Date 2010-01-20 Time 13:39 Rev Time 0.00
Received By mawillia Date 2010-01-20 Time 12:25 Sent To  
Notes
2010-01-20 13:34:48*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. EFFECTIVE 12/31/2008, THE 2007 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE BASED ON NFPA 1, UNIFORM
 FIRE CODE, 2006 EDITION AND NFPA 101, LIFE SAFETY CODE,
 2006 EDITION SHALL BE REFERENCED.
  
 3. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIAL IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 4. ON THE FLOOR PLAN AND/OR EQUIPMENT PLAN, SHOW THE
 LOCATION OF THE PORTABLE FIRE EXTINGUISHER(S) WHICH
 SATISFY THE 75' TRAVEL DISTANCE.
  
 5. AS PER LOCAL CODE, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 6. THE 2002 OF NFPA 72 - NATIONAL FIRE ALARM CODE -
 SHALL BE REFERENCED.
  
 7. CORRELATE SYMBOLS FOR FIRE ALARM HORN STROBES ON
 SHEET E-1 WITH THE ELECTRICAL SYMBOLS SHOWN ON THE E-4
 SHEET.
  
 8. PLEASE EXPLAIN WHY NO VISUAL STROBES ARE SHOWN IN
 THE TOILETS/BATHROOMS/RESTROOMS (SHEET E-1) .
  
 9. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 CODE COMPLIANCE. THESE DEVICES MAY BE SHOWN ON THE
 REFLECTED CEILING PLAN SHEET.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED ON THE
 THE APPROPIATE PLAN SHEET.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 09:06 Rev Time 0.00
Received By shill Date 2010-03-16 Time 09:06 Sent To  
Notes
2010-03-16 09:06:18TO ELECTRIC
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-08 Cont ID  
Sent By dpalmer Date 2010-02-08 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2010-02-08 Time 16:15 Sent To  
Notes
2010-02-08 16:15:46C-28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-01-20 Time 12:25 Rev Time 0.00
Received By jgomez Date 2009-12-23 Time 15:54 Sent To  
Notes
2009-12-23 15:54:42SENT TO C8.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-03-09 Cont ID  
Sent By shill Date 2010-03-09 Time 11:58 Rev Time 0.00
Received By shill Date 2010-03-09 Time 11:58 Sent To  
Notes
2010-03-09 11:58:57INTERIOR RENOVATION
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-03-04 Cont ID  
Sent By rregueir Date 2010-03-04 Time 09:54 Rev Time 0.00
Received By rregueir Date 2010-03-04 Time 09:19 Sent To  
Notes
2010-03-04 09:56:04**PROVISO**
  
 1. PROVIDE MANUFACTURER'S DATA FOR CONDENSING UNIT AND
 ROOF CAP SHOWING THESE TO BE DESIGNED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12.
  
 2. PAGE M-2 AHU INSTALLATION DETAIL STILL CALLS FOR
 CONDENSATE TO DISCHARGIN INTO HUB DRAIN. CONDENSATE
 SHALL NOT DISCHARGE INTO SANITARY SEWER SYSTEM PER
 FBC-M 307.2.1 AND CITY ORDINANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-01-20 Cont ID  
Sent By rregueir Date 2010-01-20 Time   Rev Time 0.00
Received By rregueir Date 2010-01-19 Time 11:23 Sent To  
Notes
2010-01-19 16:36:30REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1 AND "MECHANIACL CODE NOTES" #5 CALLS FOR
 DUCT SMOKE DETECTORS TO BE INSTALLED ON THE RETURN
 DUCT. SMOKE DETECTORS SHALL BE INSTALLED IN THE SUPPLY
 AIR SYSTEM IN ACCORDANCE WITH FBC-M 606.2.1.
  
 2. PAGE M1 SHOWS EXHAUST DUCTS LOCATED IN THE RETURN
 AIR PLENUM SPACE. EXHAUST DUCTS UNDER POSITIVE PRESSURE
 SHALL NOT BE LOCATED IN A PLENUM IN ACCORDANCE WITH
 FBC-M 601.5.
  
 3. PAGE M1 SHOWS EF-3 TO NEW CURB AND ROOF CAP. ROOF
 CURB AND CAP SHALL BE DESIGNED AND INSTALLED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. PROVIDE
 STRUCTURAL INSTALLATION DETAIL FOR THE NEW ROOF CURB
 AND MANUFACTURER'S DATA WITH INSTALLATION INSTRUCTIONS
 SHOWING WIND RESISTANCE CAPABILITIES OF THE PROPOSED
 ROOF CAP.
  
 4. HVAC-1 CONDENSING UNIT IS PROPOSED FOR ROOF
 INSTALLATION. PROVIDE STRUCTURAL INSTALLATION DETAIL
 FOR WIND RESISTANT INSTALLATION OF CONDENSER IN
 ACCORDANCE WITH FBC-M 301.12. ALSO PROVIDE
 MANUFACTURER'S DATA SHOWING THE CONDENSER IS DESIGNED
 FOR WIND RESISTANCE. IF A PRE-ENGINEERED ROOF STAND IS
 USED, PROVIDE PRODUCT APPROVAL IN ACCORDANCE WITH FBC-B
 106.3.3 AND FAC RULE 9B-72.
  
 5. NEW CONDENSING UNIT ON THE ROOF SHALL COMPLY WITH
 THE REQUIREMENTS FOR GUARDS IF WITHIN 10 FEET OF THE
 ROOF EDGE IN ACCORDANCE WITH FBC-M 304.10. PERMANENT
 MEANS OF ACCESS MAY ALSO BE REQUIRED IN ACCORDANCE WITH
 FBC-M 306.5. PROVIDE ROOF PLAN SHOWING PROPOSED
 INSTALLATION LOCATION OF CONDENSING UNIT.
  
 6. PAGE M2 NOTE CALLS FOR HVAC-1 CONDENSATE TO
 DISCHARGE INTO HUB DRAIN. CONDENSATE SHALL NOT
 DISCHARGE INTO SANITARY SYSTEM PER CITY ORDINANCE.
 CONDENSATE SHALL BE DISCHARGED IN AN APPROVED LOCATION
 IN ACCORDANCE WITH FBC-M 307.2.1.
  
 7. PLANS SHOW EXHAUST DUCTS WITHIN THE RETURN AIR
 PLENUM SPACE. EXHAUST DUCTS UNDER POSITIVE PRESSURE
 SHALL NOT PASS THROUGH A PLENUM IN ACCORDANCE WITH
 FBC-M 601.5.
  
 8. PLANS SHALL BE PROPERLY SIGNED AND SEALED WITH
 ORIGINAL SIGNATURE IN ACCORDANCE WITH FS 481. FULL
 TITLE BLOCK INFORMATION AND CERTIFICATE OF
 AUTHORIZATION NUMBER ARE ALSO REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-02-17 Cont ID  
Sent By kstevens Date 2010-02-17 Time 16:40 Rev Time 0.00
Received By kstevens Date 2010-02-17 Time 16:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-01-07 Cont ID  
Sent By kstevens Date 2010-01-07 Time 14:02 Rev Time 0.00
Received By kstevens Date 2010-01-07 Time 14:02 Sent To  
Notes
2010-01-07 14:30:28DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1 ADMIN.
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB CODE OF ORDINANCES
  
 1. ALL ARCHITECTURAL SHEETS, SHEET M 1 & ALL ELECTRICAL
 SHEETS. PER FAC 61G1-16.004(2)(6) THE FIRM LICENSE
 NUMBER, (CERTIFICATE OF AUTHORIZATION), AND PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN
 THE TITLE BLOCK OF EACH SHEET. FS 481.2055.
  
 2. SHEETS M 2, P 1 & P 2 A TITLE BLOCK MUST APPEAR ON
 ALL ARCHITECTURAL OR INTERIOR DESIGN DRAWINGS AND
 SPECIFICATION IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TLEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
 THE ABOVE SHEETS HAVE NO TITLE BLOCK AS REQUIRED. FS
 481.2055.
  
 3. SHT P 1 SHOWS CONDENSATE FROM HVAC-1 DRAINING TO
 MS-1. THIS IS NOT APPROVED PER CITY CODE ARTICLE III
 SECTION 90-124. THE CONDENSATE SHALL DRAIN FROM THE
 BUILDING SEPARATELY AND TERMINATE IN A DRYWELL, A STORM
 DRAIN, (RELIEF VENT REQUIRED AS CONDENSATE EXITS THE
 BUILDING), OR TO A PLANTED AREA.
  
 4. SHTS P 1 & P 2 THE VENT FOR THE MOP SINK. PER
 SECTION 905.4 EVER DRY VENT SHALL RISE VERTICALLY TO A
 MINIMUM OF 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. THE PLANS
 SHOW THE VENT RUNNING HORIZONTALLY UNDER THE SLAB.
  
 5. SUBMIT A WATER ISOMETRIC RISER DIAGRAM AS REQUIRED
 IN SECTION 106.3.5.1.3. SHOW ALL PIPE SIZE, VALVES AND,
 (WHERE REQUIRED BY SECTION 604.9) WATER HAMMER
 ARRESTORS). WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE
 CEILING. PDI-WH 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-01-06 Cont ID  
Sent By jroach Date 2010-01-06 Time 21:35 Rev Time 0.00
Received By jroach Date 2010-01-06 Time 21:35 Sent To  
Notes
***NONE***