2010-01-13 15:16:50 | *****DENIED***** |
| |
| 01. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE |
| BLOCK OF EACH SUBMITTED PLAN SHEET. THE NAME OF THE |
| OWNER AND/OR OCCUPANT MAY BE ALSO INCLUDED IN THIS |
| TITLE BLOCK. |
| |
| 02. INFORMATION, DRAWINGS, SPECIFICATIONS, AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATRE OF |
| THE PERSON RESPONSIBLE FLER THE DESIGN. |
| |
| 03. THE UPDATED PLANS/SHOP DRAWINGS ARE TO BE PRESENTED |
| WITH NO INK, PENCIL, OR ANY OTHER HAND-DRAWN MARKINGS |
| |
| 04. SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00, |
| THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED |
| NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT |
| THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A |
| COPY THEROF. |
| |
| 05. COULD NOT LOCATE THE FIRE ALARM CONTROL PANEL |
| (FACP) ON THE FIRE ALARM PLAN SHEET. |
| |
| 06. SHOW THE LOCATION OF THE EXISTING FIRE ALARM |
| DEVICES IN WHAT IS SHOWN ON THE PLAN AS AN EXISTING |
| THEATRE. |
| |
| 07. IT WAS LEARNED THAT THE EXISTING THEATRE WILL BE NO |
| LONGER. LIST ON PLANS WHAT IS PROPOSED FOR THAT AREA. |
| |
| 08. PLEASE LIST THE INTENSITY LEVEL OF THE VISUAL |
| ALARMS. |
| |
| 09. DUCT SMOKE DETECTORS REQUIRED IN HVAC SYSTEM OVER |
| 2000 CFM. AS PER LOCAL CODE, DUCT SMOKE DETECTORS SHALL |
| INITIATE A GENERAL FIRE ALARM. |
| |
| 10. THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED. |
| THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL LISTED |
| CENTRAL STATION APPROVED FOR CENTRAL STATION SERVICE. |
| |
| |
| SORRY FOR THE DELAY IN CONDUCTING THIS FIRE PLAN |
| REVIEW, BUT BASED UPON INFORMATION GAINED FROM THE |
| OWNER AND REPRESENTATIVES FROM WEST PALM BEACH |
| CONSTRUCTION SERVICES DEPARTMENT, IT HAS BEEN |
| DETERMINED THAT THE PROJECT SITE IS A CHANGE OF |
| OCCUPANCY FROM AN EXISTING ASSEMBLY OCCUPANCY (WITH |
| ANCILLIARY USE - CLASS ROOMS, OFFICES) TO A NEW DAY |
| CARE OCCUPANCY. THEREFORE, SEPARATE PLANS/PERMITS TO |
| REFLECT THIS CHANGE OF OCCUPANCY SHALL BE REQUIRED. |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |