Plan Review Details - Permit 09120456
Plan Review Stops For Permit 09120456
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-02-25 Cont ID  
Sent By mawillia Date 2010-02-25 Time 11:26 Rev Time 0.00
Received By mawillia Date 2010-02-25 Time 10:10 Sent To  
Notes
2010-02-25 10:17:57*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED. THE TWO SHEETED FIRE ALARM PLAN WAS STAMPED,
 INITIALED, AND DATED; READY FOR PERMIT ISSUANCE.
  
 PLEASE BE ADVISED THAT PRIOR TO THE FIRE ALARM FINAL
 (302), REVISED PLANS ARE REQUIRED SHOWING THE ADDITION
 OF SMOKE DETECTOR(S) AS FOLLOWS: 1. IN THE AREA OF THE
 ANNUNCIATOR & 2. IN THE AREA OF THE FIRE ALARM CONTROL
 PANEL (IF NEEDED, AS PER NFPA 72 - 2002 EDITION) . ANY
 REVISIONS SHALL BE REFLECTED IN THE RISER DIAGRAM ALSO.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2010-01-29 Time 15:30 Rev Time 0.00
Received By mawillia Date 2010-01-29 Time 14:43 Sent To  
Notes
2010-01-29 15:03:38*****DENIED*****
  
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW
 STILL NEED TO BE ADRESSED:
  
 4. SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00,
 THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT
 THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A
 COPY THEROF.
  
 6. SHOW THE LOCATION OF THE EXISTING FIRE ALARM DEVICES
 IN WHAT IS SHOWN ON THE PLAN AS AN EXISTING THEATRE.
  
 *NEW COMMENT
  
 A. HOW WILL THE PROPOSED FIRE ALARM SYSTEM BE
 INTEGRATED WITH THE EXISTING FIRE ALARM SYSTEM IN THE
 THEATRE AREA?
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-01-12 Cont ID  
Sent By mawillia Date 2010-01-11 Time 11:40 Rev Time 0.00
Received By mawillia Date 2010-01-07 Time 15:30 Sent To  
Notes
2010-01-13 15:16:50*****DENIED*****
  
 01. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET. THE NAME OF THE
 OWNER AND/OR OCCUPANT MAY BE ALSO INCLUDED IN THIS
 TITLE BLOCK.
  
 02. INFORMATION, DRAWINGS, SPECIFICATIONS, AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATRE OF
 THE PERSON RESPONSIBLE FLER THE DESIGN.
  
 03. THE UPDATED PLANS/SHOP DRAWINGS ARE TO BE PRESENTED
 WITH NO INK, PENCIL, OR ANY OTHER HAND-DRAWN MARKINGS
  
 04. SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00,
 THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT
 THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A
 COPY THEROF.
  
 05. COULD NOT LOCATE THE FIRE ALARM CONTROL PANEL
 (FACP) ON THE FIRE ALARM PLAN SHEET.
  
 06. SHOW THE LOCATION OF THE EXISTING FIRE ALARM
 DEVICES IN WHAT IS SHOWN ON THE PLAN AS AN EXISTING
 THEATRE.
  
 07. IT WAS LEARNED THAT THE EXISTING THEATRE WILL BE NO
 LONGER. LIST ON PLANS WHAT IS PROPOSED FOR THAT AREA.
  
 08. PLEASE LIST THE INTENSITY LEVEL OF THE VISUAL
 ALARMS.
  
 09. DUCT SMOKE DETECTORS REQUIRED IN HVAC SYSTEM OVER
 2000 CFM. AS PER LOCAL CODE, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 10. THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED.
 THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL STATION SERVICE.
  
  
 SORRY FOR THE DELAY IN CONDUCTING THIS FIRE PLAN
 REVIEW, BUT BASED UPON INFORMATION GAINED FROM THE
 OWNER AND REPRESENTATIVES FROM WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT, IT HAS BEEN
 DETERMINED THAT THE PROJECT SITE IS A CHANGE OF
 OCCUPANCY FROM AN EXISTING ASSEMBLY OCCUPANCY (WITH
 ANCILLIARY USE - CLASS ROOMS, OFFICES) TO A NEW DAY
 CARE OCCUPANCY. THEREFORE, SEPARATE PLANS/PERMITS TO
 REFLECT THIS CHANGE OF OCCUPANCY SHALL BE REQUIRED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-02-17 Cont ID  
Sent By lmartine Date 2010-02-16 Time 09:34 Rev Time 0.00
Received By lmartine Date 2010-02-16 Time 09:34 Sent To  
Notes
2010-02-17 09:34:27IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-21 Cont ID  
Sent By jwitmer Date 2010-01-21 Time 09:37 Rev Time 0.00
Received By jwitmer Date 2010-01-21 Time 09:37 Sent To FIRE
Notes
2010-01-21 09:38:29INCOMING SENT TO FIRE BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-01-12 Cont ID  
Sent By mawillia Date 2010-01-13 Time 14:39 Rev Time 0.00
Received By mawillia Date 2009-12-29 Time 08:21 Sent To  
Notes
2009-12-29 08:21:48TO FIRE IN BOX./WRT.