2009-12-26 22:32:15 | *****DENIED***** |
| |
| 1. THE CORRECT ADDRESS (8101 OKEECHOBEE BLVD., WEST |
| PALM BEACH) SHALL BE IN THE TITLE BLOCK OF EACH |
| SUBMITTED PLAN SHEET AND ANY OTHER DOCUMENTS/SUBMITTALS |
| WHICH REFERENCE THIS PROJECT SITE. INCORRECT NUMERICAL |
| ALSO SHOWN ON SHEET 3 IN THE INFORMATION FOR THE |
| HYDRAULICALLY CALCULATED SYSTEM. |
| |
| 2. AMEND SUPPLY FLOW TEST DATA TO REFLECT THAT THE TEST |
| WAS CONDUCTED BY WEST PALM BEACH FIRE RESCUE. |
| |
| 3. AMEND PAGES 1 AND 2 OF THE HYDRAULIC OVERVIEW |
| SUBMITTALS TO REFLECT THE CORRECT NUMERICAL ADDRESS, |
| THE CORRECT CITY, AND THE CORRECT AUTHORITY HAVING |
| JURISDICTION (AHJ). |
| |
| 4. IN THE SPRINKLER LEGEND ON SHEET 1 OF 3, EXPLAIN THE |
| DIFFERENT DEGREE LISTINGS (200, 155) FOR THE TYCO) 3/4" |
| EXTENDED COVERAGE PENDANT. |
| |
| 5. DUE TO THE SIMILIARITY IN THE CIRCULAR DEVICES, IT |
| IS DIFFICULT TO DETERMINE THE 9 (SHEET 1) AND 5 (SHEET |
| 2) TYCO 1/2" BRASS UPRIGHT SPRINKLERS. |
| |
| 6. ADD TO GENERAL NOTES: " KNOX LOCKING CAPS SHALL BE |
| REQUIRED FOR THE FIRE DEPARTMENT CONNECTION (FDC). " |
| FOR APPLICATIONS CONTACT WEST PALM BEACH FIRE RESCUE AT |
| 561-804-4724 |
| |
| 7. SPRINKLER PROTECTION FOR THE CANOPY TO BE DETERMINED |
| BY WEST PALM BEACH FIRE PREVENTION UPON |
| VERIFICATION/DOCUMENTATION OF NONCOMBUSTIBLE OR LIMITED |
| COMBUSTIBLE CONSTRUCTION. |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |