Plan Review Details - Permit 09120266
Plan Review Stops For Permit 09120266
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-12-21 Cont ID  
Sent By jwitmer Date 2009-12-21 Time 10:45 Rev Time 0.55
Received By jwitmer Date 2009-12-21 Time 10:45 Sent To  
Notes
2009-12-21 16:25:34BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 1) PLEASE SEE SHEET A1.2 REDLINED INFO REQUIRED. DOOR
 CIRCLED NOT IDENTIFIED NEEDS TO BE A 45 MINUTE RATED
 TENANT SEPERATION DOOR. TABLE 715.4 FBC- BUILDING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-12-22 Cont ID  
Sent By dpalmer Date 2009-12-22 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2009-12-22 Time 14:50 Sent To  
Notes
2009-12-22 14:50:57 
 ** PROVISO **
  
 ** THE FOLLOWING ITEMS ARE REQUIRED TO BE REVISED
 BEFORE ROUGH ELECTRICAL INSPECTIONS. THE LAST NOTE IS
 REQUIRED TO BE REVISED BEFORE FINAL. ** ALL REVISIONS
 SHALL BE SUBMITTED FOR REVIEW, STAMPING AND ON SITE FOR
 ELECTRICAL INSPECTOR TO AVOID RE-INSPECTION FEES.
  
 1) NOTE: THE LS SHEETS INDICATE SOME CODES WHICH ARE
 INCORRECT.
 PLANS LIST ON SHEET LS THE FOLLOWING:
  
 2004 EDITION OF NFPA-1, HOWEVER AS OF DECEMBER 31ST,
 2008 FAC 69A-3.012, 69A-60.003 ADOPTED THE 2006 NFPA-1.
 2005 NFPA-70 ( NATIONAL ELECTRICAL CODE) HOWEVER AS OF
 OCTOBER 1ST 2009, THE STATE ADOPTED THE 2008 EDITION.
 2003 NFPA-101, HOWEVER AS OF DECEMBER 31ST, 2008 FAC
 69A-3.012, 69A-60.004 ADOPTED THE 2006 NFPA-101.
  
 ** PLEASE BE SURE TO ADJUST:
 ** PLANS ALSO NEED TO REFLECT THE 2002 NFPA-72 NATIONAL
 FIRE ALARM CODE
  
 2) NOTE: THE MINIMUM CANDELA LEVELS ON PLANS SHALL
 COMPLY WITH NFPA-72 AND FBC CHAPTER 11. PLEASE SEE FBC
 11-4.28.3(4) WHICH REQUIRES ALL ADA AREAS TO HAVE A
 CANDELA LEVEL OF 75.
 PLEASE ALSO SHOW HORN DEVICES AS THEY ARE NOT CLEAR ON
 PLANS MEETING MINIMUMS FOR ADA.
 PLEASE LIST THE DEVICE HEIGHTS AND LOCATIONS TO MEET
 MINIMUM CODES IN AREAS FOR SCOPE OF WORK. IF EXISTING
 PLEASE SHOW.
  
 3) NOTE: TO BE NOTED: ALL LOW VOLTAGE SYSTEMS SUCH AS
 SPEAKERS, DATA, PHONE SHALL BE UNDER SEPARATE PERMITS.
  
 4) NOTE: TO BE NOTED: AS THIS IS AN EXISTING LOCATION
 AND CIRCUITING FOR LOCAL LIGHTING CAN NOT BE VERIFIED
 FOR CODE COMPLIANCE, PLEASE BE SURE TO SEE 700.12 OF
 NFPA-70. THIS REQUIRES EMERGENCY LIGHTING TO BE
 CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT IN ANY
 ONE AREA.
  
 5) NOTE: NO NEW LIGHTING IS PERMITTED TO BE INSTALLED.
 PLANS INDICATE ALL EXISTING TO REMAIN. IF ANY NEW
 LIGHTING IS PROPOSED, THEN LIGHTING PERFORMANCE
 CALCULATIONS ARE REQUIRED TO MEET PRESCRIPTIVE
 REQUIREMENTS PER FBC 13-415.AB.5.
  
 6) NOTE: PANEL SCHEDULES SHALL BE REVISED BEFORE FINAL
 INSPECTION. THE USE OF *RECEPTACLES*, *LIGHTING* ETC IN
 OFFICES IS NOT ACCEPTABLE. PLEASE SEE REVISIONS MADE TO
 THE 2005 NEC IN SECTION 408.4 WHICH REQUIRES ALL
 CIRCUITS TO BE IDENTIFIED TO SPECIFIC ROOMS AND AREAS
 IN WHICH THEY FEED. THIS MAY BE ALPHA OR NUMERIC
 DESIGNATIONS SUCH AS * RECEPTACLES RMS 101,102, *LIGHTS
 EAST HALLWAY* ETC THE FOLLOWING IS TAKEN FROM THE CODE
 COMMENTARY.
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-08-13 Cont ID  
Sent By mcarsill Date 2010-08-13 Time 13:52 Rev Time 0.00
Received By mcarsill Date 2010-08-13 Time 13:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-12-28 Cont ID  
Sent By mawillia Date 2009-12-28 Time 13:46 Rev Time 0.00
Received By mawillia Date 2009-12-28 Time 13:24 Sent To B
Notes
2009-12-28 13:45:27*****APPROVED*****
  
  
 PLAN SHEETS LS.1, A1.2, E3.1, AND E3.2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-29 Cont ID  
Sent By lmartine Date 2009-12-28 Time 15:49 Rev Time 0.00
Received By lmartine Date 2009-12-14 Time 15:33 Sent To  
Notes
2009-12-14 15:33:27C20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-12-21 Cont ID  
Sent By rregueir Date 2009-12-21 Time 13:58 Rev Time 0.00
Received By rregueir Date 2009-12-21 Time 10:46 Sent To  
Notes
2009-12-21 13:58:24REVIEW #: 1ST
 ACTION: **PROVISO**
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M2.2: PLAN SHOWS DUCTS PENETRATING RATED WALLS
 WITHOUT PROTECTION. EXAMPLE: 32X14 AND 75X14 DUCTS
 ENTERING SUITE 220. PLEASE COORDINATE ALL RATED WALL
 LOCATIONS WITH ARCHITECTURAL PLANS AND REVISE
 MECHANICAL PLANS (PRIOR TO INSPECTION) TO SHOW ALL
 PENETRATIONS OF RATED ASSEMBLIES PROTECTED IN
 ACCORDANCE WITH FBC-M 607.8.
  
 2. PAGE M2.2: FILING ROOM 227 IS A SEPARATE FIRE AREA
 AND CAN NOT BE PART OF THE RETURN AIR PLENUM IN
 ACCORDANCE WITH FBC-M 602.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2009-12-23 Cont ID  
Sent By eschneid Date 2009-12-23 Time 14:58 Rev Time 0.10
Received By eschneid Date 2009-12-23 Time 14:58 Sent To  
Notes
2009-12-23 14:58:29INTERIOR LESS THAN 50% VALUE OF STRUCTURE.