Plan Review Details - Permit 09120243
Plan Review Stops For Permit 09120243
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2011-04-14 Cont ID  
Sent By jgomez Date 2011-04-14 Time 10:12 Rev Time 0.00
Received By jgomez Date 2011-04-14 Time 10:12 Sent To  
Notes
2011-04-14 10:19:16MASTER PLAN (MODEL B) FOR NEW SINGLE FAMILY RESIDENCE
 (R3), BUILDING REVIEW THIRD CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 SUPPLEMENTS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT
 COMMENT. NOT ADDRESSED AT ALL. NEED THE ENERGY
 CALCULATIONS FOR WORST CASE SCENARIO WHEN APPLYING FOR
 A MASTER PERMIT ).
  
  
 ****REVIEW IN PROGRESS*** REVIEW STOPPED FEES ARE NOT
 PAID. CONTRACTOR WAS NOTIFIED BY LUIS MARTINEZ
 REGARDING THE FEES.
  
  
  
  
 3- ALL DRAWINGS HAVE THE LOT 42 ON THE TITLE BLOCK.
 DELETE AS REQUIRED.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES. NOA 07-1120.14 SUBMITTED WAS
 SUPERSEDED ON THE MIAMI DADE WEBSITE. PROVIDE CURRENT
 NOA.
  
 B) SINGLE HUNG WINDOWS. NOA 07-0322.06 SUBMITTED
 EXPIRES ON MARCH 23, 2011. MASTER PLAN WILL HAVE TO BE
 REVISED FOR FUTURE SUBMITTAL AFTER THIS DATE.
  
 C) WINDOW MULLIONS. NOA 06-0125.06 SUBMITTED EXPIRES ON
 JUNE 28, 2011. MASTER PLAN WILL HAVE TO BE REVISED FOR
 FUTURE SUBMITTAL AFTER THIS DATE.
  
 D) ENTRY DOOR. TWO DIFFERENT NOA'S WERE SUBMITTED. NOA
 06-0501.02 WHICH REQUIRES SHUTTERS AND NOA 07-0629.10
 WHICH DOESN'T REQUIRE SHUTTERS. CLARIFY WHICH ONE IS
 GOING TO BE USED.
  
 E) REAR DOOR BY KITCHEN AREA AS SHOWN ON PLANS. (REPEAT
 COMMENT).
  
 F) STORAGE DOUBLE DOORS AS SHOWN ON PLANS. (REPEAT
 COMMENT).
  
 G) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 H) STORM SHUTTERS. COORDINATE WITH ITEM # 4D ABOVE. AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE. ALSO, MARK ON
 SHUTTERS DRAWING SPECIFIC MOUNTING CONDITION AND ANCHOR
 TYPE AND SPACING.
  
 I) TRUSS CONNECTORS. PROVIDE ONLY THE FRONT PAGE OF
 PRODUCT APPROVAL AND PAGE SHOWING THE CONNECTOR.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS
 APPLIES TO NOA'S NO SUBMITTED YET.
  
 6- DESIGN CRITERIA: BUILDING EXPOSURE WAS REVISED TO
 EXPOSURE "C" BUT THE DOORS AND WINDOWS DESIGN PRESSURES
 ON SHEETS A-3.0, A-4.0, A-5.0 AND A-7.0 WERE NOT
 CHANGED TO REFLECT EXPOSURE "C".
  
 7- TRUSS PACKAGE:
 A) REVISE BUILDING EXPOSURE. NEED TO DESIGN TRUSSES TO
 EXPOSURE "C". REVISE TRUSS LAYOUT PAGE AND INDIVIDUAL
 TRUSSES ACCORDINGLY.
  
 B) TRUSS COVER SHEET TO PROVIDE ALL THE INFORMATION,
 INCLUDING THE ARCHITECT OF RECORD INFORMATION.
  
 C) TRUSS ENGINEER TO PROVIDE ORIGINAL SIGNATURE (NOT
 COPY) AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 8- REVISED SHEET A-2.0:
 A) DETAIL 1, DETAIL 5 AND WALL SECTION A SPECIFIES 10
 MIL VAPOR BARRIER, WHILE FOUNDATION PLAN SPECIFIES 6
 MIL VAPOR BARRIER. REVISE AS REQUIRED TO MATCH.
  
 B) WALL SECTION A: SPECIFY CORRECT SECTION FOR THE
 ATTIC VENTILATION. SEE 2007 FLORIDA RESIDENTIAL CODE.
  
 C) REVISE NOTE REGARDING TRUSS ANCHORS. USING SIMPSON
 NOT USP, AND REFER TO CORRECT SHEET.
  
 9- SHEET A-7.0: CLARIFY NOTE ON FRONT ELEVATION
 REGARDING DECORATIVE LOUVER. THERE IS NOT LOUVER SHOWN
 ON THE ELEVATION.
  
 10- REVISE HANDRAIL DETAIL #2 ON SHEET A-5.0. GUARDS
 CAN'T BE LOWER THAN 36" IN HEIGHT. SEE SEC. R312.1.
  
 11- SHEET A-6.0:
 A) COORDINATE DETAIL 4/A-6.0 WITH FASTENERS SPECIFIED
 ON STRUCTURAL CONNECTOR SCHEDULE. REVISE TYPE OF
 FASTENERS TO MATCH.
  
 B) FASTENER SPECIFIED ON DETAIL 5/A-6.0 CAN'T BE USED
 BECAUSE IT DOESN'T PROVIDE ANY UPLIFT. SEE SIMPSON
 CATALOG. REVISE AS REQUIRED AND COORDINATE DETAIL AND
 TRUSS ANCHOR SCHEDULE
  
 JULIO GOMEZ
 COMBINATION COMMERCIAL PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-01-24 Cont ID  
Sent By jgomez Date 2011-01-24 Time 14:09 Rev Time 0.00
Received By jgomez Date 2011-01-24 Time 09:27 Sent To  
Notes
2011-01-24 14:10:00MASTER PLAN (MODEL B) FOR NEW SINGLE FAMILY RESIDENCE
 (R3), BUILDING REVIEW SECOND CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 SUPPLEMENTS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 2- SHEET A/A1.0: LEAVE LOCATION MAP BOX IN BLANK. THIS
 IS APPLICATION FOR MASTER NOT FOR A SPECIFIC LOT.
  
 3- ALL DRAWINGS HAVE THE LOT 42 ON THE TITLE BLOCK.
 DELETE AS REQUIRED.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES. NOA 07-1120.14 SUBMITTED WAS
 SUPERSEDED ON THE MIAMI DADE WEBSITE. PROVIDE CURRENT
 NOA.
  
 B) SINGLE HUNG WINDOWS. NOA 07-0322.06 SUBMITTED
 EXPIRES ON MARCH 23, 2011. MASTER PLAN WILL HAVE TO BE
 REVISED FOR FUTURE SUBMITTAL AFTER THIS DATE.
  
 C) WINDOW MULLIONS. NOA 06-0125.06 SUBMITTED EXPIRES ON
 JUNE 28, 2011. MASTER PLAN WILL HAVE TO BE REVISED FOR
 FUTURE SUBMITTAL AFTER THIS DATE.
  
 D) ENTRY DOOR. TWO DIFFERENT NOA'S WERE SUBMITTED. NOA
 06-0501.02 WHICH REQUIRES SHUTTERS AND NOA 07-0629.10
 WHICH DOESN'T REQUIRE SHUTTERS. CLARIFY WHICH ONE IS
 GOING TO BE USED.
  
 E) REAR DOOR BY KITCHEN AREA AS SHOWN ON PLANS. (REPEAT
 COMMENT).
  
 F) STORAGE DOUBLE DOORS AS SHOWN ON PLANS. (REPEAT
 COMMENT).
  
 G) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 H) STORM SHUTTERS. COORDINATE WITH ITEM # 4D ABOVE. AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE. ALSO, MARK ON
 SHUTTERS DRAWING SPECIFIC MOUNTING CONDITION AND ANCHOR
 TYPE AND SPACING.
  
 I) TRUSS CONNECTORS. PROVIDE ONLY THE FRONT PAGE OF
 PRODUCT APPROVAL AND PAGE SHOWING THE CONNECTOR.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS
 APPLIES TO NOA'S NO SUBMITTED YET.
  
 6- DESIGN CRITERIA: BUILDING EXPOSURE WAS REVISED TO
 EXPOSURE "C" BUT THE DOORS AND WINDOWS DESIGN PRESSURES
 ON SHEETS A-3.0, A-4.0, A-5.0 AND A-7.0 WERE NOT
 CHANGED TO REFLECT EXPOSURE "C".
  
 7- TRUSS PACKAGE:
 A) REVISE BUILDING EXPOSURE. NEED TO DESIGN TRUSSES TO
 EXPOSURE "C". REVISE TRUSS LAYOUT PAGE AND INDIVIDUAL
 TRUSSES ACCORDINGLY.
  
 B) TRUSS COVER SHEET TO PROVIDE ALL THE INFORMATION,
 INCLUDING THE ARCHITECT OF RECORD INFORMATION.
  
 C) TRUSS ENGINEER TO PROVIDE ORIGINAL SIGNATURE (NOT
 COPY) AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 8- REVISED SHEET A-2.0:
 A) DETAIL 1, DETAIL 5 AND WALL SECTION A SPECIFIES 10
 MIL VAPOR BARRIER, WHILE FOUNDATION PLAN SPECIFIES 6
 MIL VAPOR BARRIER. REVISE AS REQUIRED TO MATCH.
  
 B) WALL SECTION A: SPECIFY CORRECT SECTION FOR THE
 ATTIC VENTILATION. SEE 2007 FLORIDA RESIDENTIAL CODE.
  
 C) REVISE NOTE REGARDING TRUSS ANCHORS. USING SIMPSON
 NOT USP, AND REFER TO CORRECT SHEET.
  
 9- SHEET A-7.0: CLARIFY NOTE ON FRONT ELEVATION
 REGARDING DECORATIVE LOUVER. THERE IS NOT LOUVER SHOWN
 ON THE ELEVATION.
  
 10- REVISE HANDRAIL DETAIL #2 ON SHEET A-5.0. GUARDS
 CAN'T BE LOWER THAN 36" IN HEIGHT. SEE SEC. R312.1.
  
 11- SHEET A-6.0:
 A) COORDINATE DETAIL 4/A-6.0 WITH FASTENERS SPECIFIED
 ON STRUCTURAL CONNECTOR SCHEDULE. REVISE TYPE OF
 FASTENERS TO MATCH.
  
 B) FASTENER SPECIFIED ON DETAIL 5/A-6.0 CAN'T BE USED
 BECAUSE IT DOESN'T PROVIDE ANY UPLIFT. SEE SIMPSON
 CATALOG. REVISE AS REQUIRED AND COORDINATE DETAIL AND
 TRUSS ANCHOR SCHEDULE
  
 JULIO GOMEZ
 COMBINATION COMMERCIAL PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-12-01 Cont ID  
Sent By jgomez Date 2010-09-23 Time 15:34 Rev Time 0.00
Received By jgomez Date 2010-09-23 Time 15:34 Sent To  
Notes
2010-12-01 15:46:10RESIDENTIAL (R3) MASTER PERMIT, BUILDING REVIEW
 CHECKLIST
 2007 FBC WITH 2009 REVISIONS.
  
  
 1- PACKAGE SUBMITTED NEED TO BE PROPERLY COORDINATED.
 MASTER PERMIT #09120243 IS ONLY FOR MODEL "B" AND THE
 ADDRESS IS 1107 22 ST. PACKAGE SUBMITTED SHOWS MODELS
 A, A1, A2 AND B. ALL THE PERMIT APPLICATIONS SUBMITTED
 SHOW THE SAME MASTER NUMBER (09120243) AND THE SAME
 ADDRESS (1107 22 ST). PLEASE COORDINATE EACH MASTER
 PERMIT NUMBER WITH EACH MASTER MODEL AND EACH ADDRESS
 AS REQUIRED.
  
 2- LUIS MARTINEZ TALKED TO DON WOODS SO CONTRACTOR
 COORDINATES PLANS AND PERMIT APPLICATIONS.
 JULIO GOMEZ
  
  
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-17 Cont ID  
Sent By jgomez Date 2009-12-17 Time 08:22 Rev Time 0.00
Received By jgomez Date 2009-12-17 Time 08:22 Sent To  
Notes
2009-12-17 08:25:38NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 SUPPLEMENTS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 **NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE.
  
 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 4- DRAWINGS SUBMITTED ARE DESIGNED UNDER THE 2004 FBC.
 ALL DRAWINGS NEED TO SPECIFY CURRENT CODE (2007 FLORIDA
 RESIDENTIAL CODE WITH 2009 SUPPLEMENTS) AND CURRENT
 EDITION OF THE REFERENCED STANDARDS. REVISE SHEETS
 A/A1.0, A/2.01 AND S/3.01.
  
 5- ALL PLANS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. SEC. 481 FLORIDA STATUTE.
  
 6- SHEET A/A1.0:
 A) PROVIDE SITE PLAN FOR CURRENT HOUSE TO BE BUILT.
 SPECIFY ALL LOT DIMENSIONS, BUILDING DIMENSIONS AND
 SETBACKS.
  
 B) REVISE INFORMATION ON LOCATION MAP TO MATCH ACTUAL
 HOUSE TO BE BUILT.
  
 7- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES.
 B) SINGLE HUNG WINDOWS.
 C) WINDOW MULLIONS. AND SPECIFY MULLION SIZE AND
 ANCHORS.
 D) ENTRY DOOR.
 E) REAR DOOR.
 F) STORAGE DOUBLE DOORS.
 G) PRECAST LINTELS AS SPECIFIED ON PLANS.
 H) STORM SHUTTERS. AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE. ALSO, MARK ON SHUTTERS DRAWING SPECIFIC
 MOUNTING CONDITION AND ANCHOR TYPE AND SPACING.
 I) TRUSS CONNECTORS. PROVIDE ONLY THE FRONT PAGE OF
 PRODUCT APPROVAL AND PAGE SHOWING THE CONNECTOR.
  
 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 9- PROVIDE 2 COPIES OF SOIL TEST REPORT. SEC. R401.4 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 10- SHEET A/2.01: SPECIFY SAFETY GLASS FOR WINDOW THAT
 IS ADJACENT TO THE ENTRY DOOR. SEC. R308.4(6).
  
 11- SHEET S/3.01: REVISE THE FLORIDA BUILDING CODE
 DESIGN PARAMETERS. ACCORDING TO SEC. R301.2.1.4.3 OF
 2009 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE
 THIS HOUSE IS LOCATED ON EXPOSURE "C" NOT "B". NEED TO
 REVISE THE EXPOSURE AND THE DESIGN PRESSURES SHOWN ON
 SHEET A/3.01.
  
 12- OWES $2727.14 FOR THE PERMIT FEE BALANCE.
  
 JULIO GOMEZ
 COMBINATION COMMERCIAL PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2011-02-01 Cont ID  
Sent By rlecky Date 2011-02-01 Time 12:49 Rev Time 0.00
Received By rlecky Date 2011-02-01 Time 12:20 Sent To  
Notes
2011-02-01 12:52:45PROVIDE INTERRUPTING (AIC) CURRENT RATING FOR THE
 ELECTRICAL SERVICE. NEC 110.9
 CORRECT NOTES TO REFLECT THE CURRENT ELECTRIC CODE:
 2008 NEC
 PROVIDE AN INTERSYSTEM BONDING BAR AT THE SERVICE. NEC
 250.94
 THREE RECEPTACLES REQUIRED IN TWO HALLWAYS. NEC 210.52
 (H)
 A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR
 ELEVATION. NEC 210.8, 210.52 (E) (1)
 NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT
 RECEPTACLES. NEC 406.11
 AT LEAST ONE SWITCH CONTROLLED LIGHTING OUTLET SHALL BE
 PROVIDED ON THE EXTERIOR SIDE OF THE SIDE ENTRANCE. NEC
 210.70 (A) (2) (B).
 BEDROOM RECEPTACLES MUST BE PROTECTED WITH COMBINATION
 - TYPE AFCI'S. NEC 210.12 (B)
  
 ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-09-22 Cont ID  
Sent By jleahy Date 2010-09-22 Time 07:11 Rev Time 0.00
Received By jleahy Date 2010-09-22 Time 07:10 Sent To  
Notes
2010-09-22 07:39:281) AIC RATING FOR SERVICE 110.9
  
 2) INTERSYSTEM BONDINF STRIP AT SERVICE 250.94
  
 3) LIGHT AND SWITCH AT REAR DOOR 210.70 A2B
  
 4) OUTLET AT BACK OF RESIDENCE MISSING 210.52 E1
  
 5) NOTE STATES BEDROOM OUTLETS AND SMOKE DETECTORS ON
 ARC FAULTS SEE 210.12 B FOR ADDITIONAL OUTLET
 PROTECTION.
  
 6) OUTLET MISSING BY BEDROOM 1 AND 2 HALLWAY 210.52 H
  
 7) NOTE #5 ON A-9.0 QUOTES 2002 NEC?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-22 Cont ID  
Sent By btrobaug Date 2009-12-22 Time 11:27 Rev Time 0.00
Received By btrobaug Date 2009-12-22 Time 09:44 Sent To  
Notes
2009-12-22 11:22:44 
  
 APPLICATION #09120136 ELECTRICAL PLAN REVIEW
 1107 22ND STREET 12/22/09
 WEST PALM BEACH, FL.
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET A-1 ALL THE ???APPLICABLE CODES??? NOTED ARE
 FROM THE PREVIOUS CODE CYCLE, CORRECT SAME.
  
 2} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLANS, MUST SIGN AND SEAL THE PLAN PER 481.221(1)
 (B) FS.
  
 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 4} AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. 250.94, 2008 NEC.
  
 5} NOTE #4 IN THE ???GENERAL NOTES??? SHEET E2.01
 REFERENCES ARC FAULT PROTECTION FOR BEDROOMS. SEE
 210.12, 2008 NEC TO CORRECT THE NOTE.
  
 NOTE: CHANGE IN THE 2008 NEC AN INTERSYSTEM BONDING
 TERMINATION FOR CONNECTING INTERSYSTEM BONDING AND
 GROUNDING CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL
 BE PROVIDED EXTERNAL TO ENCLOSURES AT THE SERVICE
 EQUIPMENT AND AT THE DISCONNECTING MEANS FOR ANY
 ADDITIONAL BUILDINGS OR STRUCTURES. 250.94, 2008 NEC.
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-11-18 Cont ID  
Sent By shill Date 2011-04-14 Time 14:15 Rev Time 0.00
Received By shill Date 2011-03-29 Time 13:13 Sent To  
Notes
2011-11-18 14:27:2111/17/11 CLOSED "I" STOP FOR REPORTING PURPOSES
2011-03-31 13:14:15R--25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-05 Cont ID  
Sent By lmartine Date 2011-01-05 Time 13:10 Rev Time 0.00
Received By lmartine Date 2011-01-05 Time 13:10 Sent To  
Notes
2011-01-05 13:10:22R--19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-01-06 Cont ID  
Sent By jgomez Date 2010-01-06 Time 10:35 Rev Time 0.00
Received By jgomez Date 2009-12-15 Time 09:40 Sent To  
Notes
2009-12-15 09:48:05R 15./WRT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2011-01-24 Cont ID  
Sent By jgomez Date 2011-01-24 Time 14:07 Rev Time 0.00
Received By jgomez Date 2011-01-24 Time 14:07 Sent To  
Notes
2011-01-24 14:08:30NO REQUIRED FOR MASTER PLAN. REQUIRED WHEN APPLYING FOR
 EACH HOUSE TO BE BUILT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-12-16 Cont ID  
Sent By jgomez Date 2009-12-16 Time 16:39 Rev Time 0.00
Received By jgomez Date 2009-12-16 Time 16:39 Sent To  
Notes
2009-12-16 16:40:30BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) FOR
 IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2011-01-24 Cont ID  
Sent By jgomez Date 2011-01-24 Time 15:23 Rev Time 0.00
Received By jgomez Date 2011-01-24 Time 15:23 Sent To  
Notes
2011-01-24 15:24:29NO REQUIRED FOR MASTER. REQUIRED FOR EACH INDIVIDUAL
 LOT ONLY. SEE ZONING COMMENTS BY LINDA FRANCO.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-12-30 Cont ID  
Sent By rkussner Date 2009-12-30 Time 09:11 Rev Time 0.00
Received By rkussner Date 2009-12-30 Time 09:11 Sent To  
Notes
2009-12-30 09:33:07***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR. PLEASE NOTE THAT THERE MUST BE 120%
 IRRIGATION COVERAGE TO ALL LANDCAPED AREAS INCLUDING
 THE ADJACENT RIGHTS-OF-WAY.
  
 2. PURSUANT TO SECTION 94-448 (D) (2), THE LANDSCAPE
 PLAN SHALL CONTAIN ALL OF THE INFORMATION REQUIRED IN
 THIS SECTION.
  
 3. PLEASE PROVIDE SCREENING FOR THE AIR CONDITIONING
 UNIT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-01-24 Cont ID  
Sent By jgomez Date 2011-01-24 Time 13:55 Rev Time 0.00
Received By jgomez Date 2011-01-24 Time 13:55 Sent To  
Notes
2011-01-24 14:06:13NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 SECOND CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 2- PROVIDE COOLING AND HEATING LOAD CALCULATIONS AS
 REQUIRED BY SEC. N1107.AB OF 2007 FLORIDA RESIDENTIAL
 CODE. (REPEAT COMMENT. NOT ADDRESSED).
  
 3- SPECIFY SUPPLY AND RETURN CFM'S ON EACH ROOM ROOM.
 COORDINATE WITH THE HEATING AND COOLING CALCULATIONS
 REQUIRED BY SEC. N1100.AB. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 4- SHEET A-8.0:
 A) REVISE MECHANICAL NOTE #3:. REVISE MINIMUM SEER AND
 COORDINATE EQUIPMENT MODEL WITH LOAD CALCULATIONS
 REQUIRED ON ITEM #2 ABOVE.
  
 B) REVISE OUTSIDE AIR CALCULATIONS NOTE: SEE 2007
 FLORIDA RESIDENTIAL CODE. CITE CORRESPONDING SECTION
 AND MAKE SURE CONDITIONED FLOOR AREA MATCHES FLOOR AREA
 SPECIFIED ON THE ARCHITECTURAL PLANS. (REPEAT COMMENT).
 CLARIFY WHY CITING THIS CODE SECTION. USING NATURAL OR
 MECHANICAL VENTILATION?
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-01-06 Cont ID  
Sent By jgomez Date 2010-01-06 Time 09:50 Rev Time 0.00
Received By jgomez Date 2010-01-06 Time 09:50 Sent To PC
Notes
2010-01-06 10:35:42NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE COOLING AND HEATING LOAD CALCULATIONS AS
 REQUIRED BY SEC. N1107.AB OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 3- SPECIFY SUPPLY AND RETURN CFM'S ON EACH ROOM ROOM.
 COORDINATE WITH THE HEATING AND COOLING CALCULATIONS
 REQUIRED BY SEC. N1100.AB.
  
 4- SHEET M2.01:
 A) UPDATE MECHANICAL NOTE #1. CURRENT CODE IS THE 2007
 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 B) REVISE MECHANICAL NOTE #3:. REVISE MINIMUM SEER AND
 COORDINATE EQUIPMENT MODEL WITH LOAD CALCULATIONS
 REQUIRED ON ITEM #2 ABOVE.
  
 C) REVISE OUTSIDE AIR CALCULATIONS NOTE: SEE 2007
 FLORIDA RESIDENTIAL CODE. CITE CORRESPONDING SECTION
 AND MAKE SURE CONDITIONED FLOOR AREA MATCHES FLOOR AREA
 SPECIFIED ON THE ARCHITECTURAL PLANS.
  
 5- PLANS NEED TO BE SIGNED AND SEALED BY THE
 PROFESSIONAL OF RECORD AS REQUIRED BY CHAPTER 481
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-01-24 Cont ID  
Sent By jgomez Date 2011-01-24 Time 12:06 Rev Time 0.00
Received By jgomez Date 2011-01-24 Time 12:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-12-22 Cont ID  
Sent By kstevens Date 2009-12-22 Time 15:19 Rev Time 0.00
Received By kstevens Date 2009-12-22 Time 15:19 Sent To  
Notes
2009-12-22 15:55:29DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
 FBC-2007 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A1.0 INDICATES THE DESIGN TO BE PER FBC-2004.
 ALL PLANS SUBMITTED FOR PERMIT AFTER MARCH 1, 2009
 SHALL BE DESIGNED TO THE FBC-2007 EDITION WITH 2009
 SUPPLEMENTALS. PLEASE CORRECT CODE REFERENCES. SECTION
 106.1.1.
  
 2. ALL SHEETS DESIGNED BY AN ARCHITECT OR ENGINEER
 SHALL BE SIGNED, SEALED & DATED PER CHAPTERS 481 & 471
 OF THE FLORIDA STATUTES AND SECTION 106.1.
  
 3. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION. PLEASE INDICATE THE
 ADDRESS OF THE RESIDENCE ON THE TITLE BLOCK OF EACH
 SHEET. SECTION 106.1.1.
  
 4. SHT P2.01 GENERAL PLUMBING NOTES #7 INDICATES A
 1-1/4 INCH METER AND A 1-1/4 INCH WATER SERVICE WITH
 GATE VALVE AT THE HOUSE. PER TABLE 603.1 18 FIXTURE
 UNITS OR LESS ONLY REQUIRES A 5/8 INCH METER AND 3/4
 INCH WATER SERVICE. THE TOTAL FIXTURE UNITS FOR THE
 RESIDENCE IS ONLY 14. PLEASE CLARIFY IF THE METER AND
 GATE VALVE INDICATED AS WELL SUB-NOTES A THRU E ARE
 REQUIRED FOR THIS RESIDENCE.
  
 5. SHT P2.01 GENERAL PLUMBING NOTES #8 INDICATES AIR
 CHAMBERS AT EACH FIXTURE. AIR CHAMBERS ARE NOT APPROVED
 AND SHALL BE DELETED. PDI-WH 201.
  
 6. SHT P2.01 SANITARY RISER DIAGRAM. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH
 DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES IN
 DIAMETER. SECTION 406.3/P2718.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status N Date 2011-01-14 Cont ID  
Sent By lfranco Date 2011-01-14 Time 18:32 Rev Time 0.00
Received By lfranco Date 2011-01-14 Time 18:31 Sent To  
Notes
2011-01-19 16:41:18PLANNING AND ZONING: **** ZONING REVIEW NOT REQUIRED
 FOR MASTER BUILDING PERMIT FOR SINGLE FAMILY HOME. DUE
 TO NO SPECIFIC SITE LOCATION, THE PLANNING AND ZONING
 DEPARTMENT CANNOT REVIEW FOR SETBACKS, HEIGHT,
 DRIVEWAY, LANDSCAPING OR ANY ZONING AND LAND
 DEVELOPMENT REGULATIONS ("ZLDR") THAT MAY PERTAIN TO A
 SPECIFIC LOCATION. WHEN A SITE IS ASSOCIATED TO THIS
 MASTER BUILDING PERMIT, THEN A ZONING REVIEW WILL BE
 REQUIRED. *****
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-12-29 Cont ID  
Sent By lfranco Date 2009-12-29 Time 17:15 Rev Time 0.00
Received By lfranco Date 2009-12-29 Time 17:15 Sent To L
Notes
2009-12-29 17:57:56PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE
 REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE ZLDR.
  
 4. SHEET A A1.0 ("OVERALL SITE PLAN") DEPICTS A
 CONCRETE WALK, DRIVE, AND APRON TO BE COORDINATED WITH
 EXISTING UTILITIES. PROVIDE DIMENSIONS FOR THE DRIVE
 AND INCLUDE THE INFORMATION TO ADDRESS
 PERVIOUS/IMPERVIOUS AREA:
  
 NOTE: A SEPARATE PERMIT SHALL BE APPROVED FOR THE
 RIGHT-OF-WAY DRIVEWAY APRON BY THE ENGINEERING
 DEPARTMENT PRIOR TO FINAL BUILDING PERMIT APPROVAL BY
 THE PLANNING AND ZONING DEPARTMENT. SUBMIT A COPY OF
 PERMIT ALONG WITH THE RE-SUBMITTAL.
  
 PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
  
 PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE
 SURFACES (EXISTING AND PROPOSED) LOCATED WITHIN THE
 FRONT YARD (FROM FRONT PROPERTY LINE TO THE FRONT
 BUILDING FACADE).
  
 5. ELEVATIONS DO NOT SHOW TOTAL HEIGHT DIMENSIONS,
 INCLUDING ROOF TOP. PROVIDE DIMENSION OF ROOF OVERHANG
 THAT IS ENCROACHING INTO THE SETBACK.
  
 6. MECHANICAL SHEET M 2.01 AND OTHER SHEETS SHOW A
 CONDENSING UNIT ON THE WEST SIDE OF THE BUILDING.
 INDICATE SETBACK DIMENSIONS FROM PROPOSED CONDENSER
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION
 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. SHOW
 CONDENSER UNIT ON OVERALL SITE PLAN.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  