Plan Review Details - Permit 09120196
Plan Review Stops For Permit 09120196 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2010-02-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-02-10 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-02-10 |
Time |
16:21 |
Sent To |
|
|
Notes |
2010-02-10 16:21:33 | PROVISO - NO "PICKETS" PER CONTRACTOR |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2010-02-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-02-10 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-02-10 |
Time |
13:20 |
Sent To |
|
|
Notes |
2010-02-10 13:22:31 | ****PROVISO**** | | ****REVISION REQUIRED**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | PROVIDE INFORMATION REGARDING THE PICKETS. EITHER | | INDICATE THESE AS EXISTING OR PROVIDE A DETAIL TO SHOW | | HOW THEY WILL RESIST WIND LOADS, FBC R301. PROVIDE | | ENOUGH INFORMATION TO SHOW THE NATURE AND CODE | | COMPLIANCE OF PROPOSED INSTALLATION. PLEASE PROVIDE | | INFORMATION SUCH AS ATTACHMENTS, MATERIAL, LOCATION | | (INSIDE OR OUTSIDE OF THE SCREEN), ETC. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2010-02-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-02-04 |
Time |
13:18 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-02-04 |
Time |
13:18 |
Sent To |
Z |
|
Notes |
2010-02-04 13:20:51 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. THE DETAIL SUBMITTED BY EMAIL DOES NOT MATCH THE | | PLAN ORIGINALLY SUBMITTED; THEREFORE, THERE ARE NEW | | COMMENTS. | | | | 2. PROVIDE INFORMATION REGARDING THE PICKETS (NEW SINCE | | PREVIOUS REVIEW). EITHER INDICATE THESE AS EXISTING OR | | PROVIDE A DETAIL TO SHOW HOW THEY WILL RESIST WIND | | LOADS, FBC R301. PROVIDE ENOUGH INFORMATION TO SHOW THE | | NATURE AND COMPLIANCE OF PROPOSED INSTALLATION. PLANS | | DO NOT INDICATE ANY ATTACHMENTS, MATERIAL, OR LOCATION | | (INSIDE OR OUTSIDE OF THE SCREEN), HOW THIS AFFECTS THE | | INSTALLATION SPECIFICATIONS. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2009-12-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-12-23 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-12-23 |
Time |
14:11 |
Sent To |
|
|
Notes |
2009-12-23 14:17:30 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. DETAILS PROVIDED FROM THE AAF GUIDE ARE FOR ALUMINUM | | POSTS, PLAN SHOWS WOOD POSTS. PROVIDE APPROPRIATE | | DETAILS/CONNECTION SPECIFICATIONS. | | | | THE DETAILS SENT VIA EMAIL CONFLICT WITH THE AAF | | STANDARD WALL DETAIL, PAGE 3-3. A CURSORY REVIEW WAS | | DONE; PLEASE NOTE THAT WE DO NOT ACCEPT RESUBS VIA | | EMAIL AT THIS TIME. FOR EXAMPLE, AN EMAIL WAS SENT WITH | | DETAIL C3 CIRCLED, BUT THE WALL DETAIL (AAF PAGE 3-3) | | SHOWS DETAIL C7/C8 AT THIS LOCATION (INTERMEDIATE | | POSTS). PLEASE REVISE THE PLAN TO SHOW LOCATION OF | | PROPOSED DETAILS AND CONFIRM THAT PLANS SUBMITTED ARE | | CONSISTENT WITH THIS SPECIFIC JOB. | | | | NEW COMMENT: | | | | 2. THE EXISTING PORCH WAS DESIGNED TO BE OPEN; PLEASE | | INCLUDE INFORMATION REGARDING THE HOST STRUCTURE'S | | ABILITY TO RESIST ADDITIONAL WIND LOADS CREATED BY THE | | SCREEN ENCLOSURE. FBC R301.1. | | | | PLEASE REVISE PLANS AND RESUBMIT, TWO SETS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-12-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-12-16 |
Time |
09:40 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-12-16 |
Time |
09:40 |
Sent To |
|
|
Notes |
2009-12-16 09:41:07 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. DETAILS PROVIDED FROM THE AAF GUIDE ARE FOR ALUMINUM | | POSTS, PLAN SHOWS WOOD POSTS. PROVIDE APPROPRIATE | | DETAILS/CONNECTION SPECIFICATIONS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2009-12-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-12-16 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-12-10 |
Time |
09:00 |
Sent To |
|
|
Notes |
2009-12-10 09:01:03 | TO ZONING | | | 2009-12-09 09:53:38 | TO UNDER $5K BLDG BOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2009-12-10 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-12-10 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-12-10 |
Time |
09:45 |
Sent To |
B |
|
Notes |
|
|
|