Plan Review Details - Permit 09120164
Plan Review Stops For Permit 09120164
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-12-17 Cont ID  
Sent By jwitmer Date 2009-12-17 Time 11:21 Rev Time 0.77
Received By jwitmer Date 2009-12-17 Time 10:30 Sent To  
Notes
2009-12-17 11:21:55WILL NEED IMPACT FEE ASSESSMENT FOR THE FIRST FLOOR
 STORAGE TO MERCANTILE

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-01-12 Cont ID  
Sent By dpalmer Date 2010-01-12 Time 11:06 Rev Time 0.00
Received By dpalmer Date 2010-01-07 Time 17:00 Sent To FIRE
Notes
2010-01-12 11:06:21** PROVISO *
  
 * REVISE BEFORE FINALS.
  
  
 1) NOTE: PLEASE PROVIDE COPY OF UNITY OF TITLE AS
 ELECTRICAL CROSSES THE PROPERTY LINES SHOWN ON PALM
 BEACH COUNTY PROPERTY APPRAISER WEB-SITE.
  
 2) NOTE: SIGN CIRCUIT REQUIRED PER 600.5 ( 1200 VA MIN)
  
 3) NOTE: ALL CONTINUOUS LOADS INCLUDING SIGN ABOVE ARE
 REQUIRED TO BE FIGURED AT 125%.
 215.3, 230.42 ETC.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-22 Cont ID  
Sent By dpalmer Date 2009-12-22 Time 11:06 Rev Time 0.00
Received By dpalmer Date 2009-12-22 Time 11:06 Sent To  
Notes
2009-12-22 11:06:51** DENIED 2ND **
  
 MINIMUM DOCUMENTS FOR CODE COMPLIANCE HAS NOT ALL BEEN
 SUBMITTED.
  
 1) NOTE: THIS IS A CHANGE IN OCCUPANCY WHICH IS
 REQUIRED TO MEET MINIMUMS UNDER THE EXISTING BUILDING
 CODE, ELECTRICAL CODE AND ENERGY CODE.
 PLEASE SUBMIT COMPLETED PLANS AND SUPPORTING DOCUMENTS.
 PLEASE SEE EXISTING BUILDING CODE 2007 W/ 2009
 SUPPLEMENTS, SEE CHAPTER 9.
 PLEASE SEE FBC 2007 W2009 SUPPLEMENTS FOR CHAPTER
 13.101.3
 CHANGES IN OCCUPANCY TO A HIGHER HAZARD ALSO REQUIRES
 ALL ELECTRICAL TO MEET CURRENT ADOPTED CHAPTER 27 OF
 THE FBC.
  
 2) NOTE: PLEASE HAVE OWNER FILE FOR A UNITY OF TITLE
 FOR THIS PROPERTY AND THE SEPARATE LEGAL PROPERTY TO
 THE WEST WHICH IS 342 CONNISTON RD. BASED ON THE PALM
 BEACH COUNTY PROPERTY APPRAISER OFFICE RECORD, MAPS,
 AND PLANS THERE IS STRUCTURAL AND ELECTRICAL WHICH
 CROSS THE PROPERTY LINE WHICH IS NOT PERMITTED.
  
 3) NOTE: NEW RISER NOW INDICATES A TOTAL OF 525AMPS
 WORTH OF SERVICE AND SERVICE ENTRANCE CONDUCTORS ONLY
 RATED FOR 200AMPS. PLEASE SEE 240.4, 310.16 FOR MINIMUM
 SIZING.
  
 4) NOTE: PLEASE SUBMIT LOAD CALCULATIONS BASED ON MIXED
 USE OCCUPANCY AS NOW STATED AND SHOWN ON PLANS.
 PLEASE SEE NEC 220, MORE SPECIFICALLY 220.12, 220.14,
 220.42, 220.43, ETC.
 PLEASE ALSO SEE 215.3, 230.42 FOR ALL CONTINUOUS LOADS
 @125%.
 PLEASE SEE 422.13 FOR ANY STORAGE TYPE WATER HEATERS
 WHICH ALSO REQUIRED CONTINUOUS LOADS AT 125%.
  
 5) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS
 ALONG WITH LIGHTING PERFORMANCE CALCULATIONS. PLEASE
 SEE FBC 13-101.3, 13-400, 13-103, 13-415.AB.5,
 13-415.AB.2.2 ETC
  
 6) NOTE: PLEASE SHOW ALL MINIMUM CIRCUITING FOR NEW
 OCCUPANCY BASED ON COMMERCIAL USE. ALL CIRCUITING IS TO
 BE SHOWN ON PLANS AND NEEDS TO COORDINATE WITH
 SUBMITTED PANEL SCHEDULE(S).
 PANEL SCHEDULE MAY NOT ONLY STATE *RECEPTACLES OR
 LIGHTING* IN GENERAL TERMS. CIRCUITS ARE TO BE SPECIFIC
 TO ROOMS AND AREAS IN WHICH THEY FEED. ALPHA OR NUMERIC
 DESIGNATIONS MAY BE USED.
 408.4, 220.12, 220.14, 220.18, 220.43, 220.44 ETC
  
 7) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY
 LIGHTING AND EXIT LIGHTS. THESE ARE REQUIRED TO BE
 CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT IN ANY ONE
 AREA.
  
 8) NOTE: PLEASE SEE 600.5 FOR REQUIRED SIGN CIRCUIT.
 PLEASE BE SURE TO INCLUDE MINIMUM BRANCH CIRCUIT LOAD.
  
 9) NOTE: PLEASE SEE 210.62 FOR SHOW WINDOW RECEPTACLES
 REQUIRED. PLEASE SEE 220.43 FOR REQUIRED LOAD IN LOAD
 CALCULATIONS.
  
 10) NOTE: PLANS INDICATE SMOKE DETECTORS HOWEVER NO
 INFORMATION ON FIRE ALARM PANEL, LOCATION ETC IS SHOWN.
 PLEASE COMPLETED PLANS IF THIS IS A REQUIRED SYSTEM. FS
 633 REQUIRES ANY REQUIRED SYSTEM DESIGN INTENT TO BE
 SHOWN ON BASE PLANS EVEN WHEN FIRE ALARM PERMITS ARE
 FILED UNDER SEPARATE PERMITS. IF THIS IS A REQUIRED
 SYSTEM PLEASE BE SURE TO SEE FBC CHAPTER 11, 11-4.28.1,
 .2 AND .3 FOR MINIMUM LEVELS FOR ADA COMPLIANCE.
  
 11) NOTE: BATHROOM RECEPTACLES SHALL BE GFI/GFI
 PROTECTED PER 210.8B
  
 12) NOTE: EXTERIOR LIGHTING SHALL MEET CONTROLS UNDER
 FBC 13-415.AB.1.4
  
 13) NOTE: EXTERIOR RECEPTACLE ON PLANS IS REQUIRED TO
 BE GFI/GFI PROTECTED. 210.8B5
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-01-12 Cont ID  
Sent By mawillia Date 2010-01-12 Time 15:10 Rev Time 0.00
Received By mawillia Date 2010-01-12 Time 14:55 Sent To  
Notes
2010-01-12 15:10:43*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; SHEET A03 OF 03 STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-28 Cont ID  
Sent By mawillia Date 2009-12-28 Time 14:47 Rev Time 0.00
Received By mawillia Date 2009-12-22 Time 15:18 Sent To  
Notes
2009-12-28 14:37:13*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS REVIEW (UNDER
 #09070059) STILL NEED TO BE ADDRESSED:
  
 3. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 4. PLEASE PROVIDE TRAVEL DISTANCE TO THE EXITS.
  
 5. SHOW THE LOCATION OF THE EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S) FOR THE REMODELED
 FLOOR PLAN.
  
 6. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7. SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS
 I OR CLASS II.
  
 8. ARE THE DEVICES SHOWN IN THE ELECTRICAL FLOOR PLAN
 (SHEET A03) SMOKE DETECTORS (SD) OR SMOKE ALARMS (SA) ?
 PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE TIED
 INTO A BUILDING'S FIRE ALARM SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-30 Cont ID  
Sent By lmartine Date 2009-12-29 Time 09:24 Rev Time 0.00
Received By lmartine Date 2009-12-29 Time 09:24 Sent To  
Notes
2009-12-30 09:25:15GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-12-28 Time   Rev Time 0.00
Received By jwitmer Date 2009-12-17 Time 11:23 Sent To  
Notes
2009-12-17 11:24:211ST FLOOR CHANGE OF OCCUPANCY STORAGE TO MERCANTILE
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-01-12 Cont ID  
Sent By jwitmer Date 2010-01-12 Time 11:17 Rev Time 0.00
Received By jwitmer Date 2010-01-12 Time 11:17 Sent To  
Notes
2010-01-12 11:18:13BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-12-17 Cont ID  
Sent By jwitmer Date 2009-12-17 Time 11:22 Rev Time 0.50
Received By jwitmer Date 2009-12-17 Time 11:22 Sent To  
Notes
2009-12-17 11:23:21MECHANICAL PERMIT 09070050 MUST BE ISSUED, 4 X FEE
 BEFORE INSPECTIONS

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-02-02 Cont ID  
Sent By dwise Date 2010-02-02 Time 11:20 Rev Time 0.00
Received By dwise Date 2010-02-02 Time 11:20 Sent To  
Notes
2010-02-02 11:25:09APPROVED WITH PROVISO: MUST PROVIDE DRINKING FOUNTAIN
 DUE TO CHANGE IN OCCUPANCY FROM BUSINESS TO MERCANTILE
 (MORE INTENSIVE USE PER EXISTING BUILDING VOLUME).
 OTHERWISE EXISTING FIXTURES SUFFICE AND
 DISPROPORTIONALITY WILL APPLY.

Review Stop Z ZONING
Rev No 1 Status P Date 2010-01-28 Cont ID  
Sent By eschneid Date 2010-01-28 Time 09:02 Rev Time 0.25
Received By eschneid Date 2010-01-28 Time 09:02 Sent To  
Notes
2010-01-28 09:02:43PERMIT VALUE OF JOB ($18K) IS LESS THAN 50% OF
 STRUCTURE VALUE. CITY INSTALLED CURB FOR THE 2
 RELOCATED PARKING SPACES AS PART OF SIDEWALK REPAIR.
  
 UNITY OF TITLE ADDED ADDITONAL PARKING ON-STREET.
  
 NOTE: NO ZONING STAMP ON REVISED PLANS.